Wiring a variable frequency drive (VFD) to a three-phase motor correctly means: supply goes through a circuit breaker into the drive's R, S, T (L1, L2, L3) terminals, the U, V, W (T1, T2, T3) terminals go straight to the motor, the motor is connected star or delta to match the drive's output voltage, and the drive and motor frame share a common earth; the control circuit uses digital inputs (FWD, REV, COM) to start and stop, and a potentiometer or a 0–10 V or 4–20 mA signal to set speed. Then you set at least 8 parameters: motor rating, run command source, frequency source, maximum and minimum frequency, acceleration and deceleration time, and overload protection. This lesson goes from the power diagram, the control diagram and a parameter table to a worked example of a 1.1 kW conveyor, with a safety procedure for the DC capacitors that stay charged after the supply is off.
By the end of this lesson, you will be able to:
- Read a motor nameplate and decide on star or delta to match the output voltage of a single-phase or three-phase drive.
- Draw and wire the R, S, T to U, V, W power circuit and earth, and know the 4 things never to do on the motor side.
- Wire control for forward run, reverse run, speed by potentiometer and a fault relay output.
- Set 8 groups of basic parameters, test run without load and then with load, and work out speed from frequency.
- Work safely with the DC capacitors: wait for discharge and measure for remaining voltage before touching any terminal.
Want to become an industrial electrician the right way? Setting up VFDs and soft starters is step 4, after industrial electrical safety and lockout/tagout (LOTO), reading drawings and switchgear, and wiring three-phase motors and starter circuits. See the 8-step industrial electrician roadmap to know what to learn first.
What a VFD does and choosing one for your motor
A variable frequency drive (VFD, inverter) changes the frequency and voltage supplied to an induction motor to control speed, start smoothly and save energy on pumps and fans. Knowing what is inside helps you understand the rules for wiring it.
What is inside a VFD
- Rectifier: turns the incoming AC into DC.
- DC bus with large filter capacitors: about 1.41 times the supply voltage, so about 310 V DC on a 220 V supply and about 540 V DC on a 380 V supply. These capacitors hold their charge after the supply is cut.
- Inverter: fast-switching semiconductor devices create pulsed voltage at U, V, W at whatever frequency is needed.
Because the output is fast-switching voltage pulses, no power factor capacitors or unsuitable filters may go on the motor side, and long motor cables cause interference and voltage spikes at the motor terminals.
Reading the motor nameplate: star or delta
The motor nameplate shows power, voltage, current, power factor cos φ, speed and frequency (Figure 1). A motor marked 220/380 V is connected delta for 220 V and star for 380 V. A motor marked 380/660 V must be connected delta on a 380 V supply. The rule with a drive: the drive's U, V, W output voltage must equal the nameplate voltage for the connection you choose.
Photo: Bernd Schwabe in Hannover / Wikimedia Commons, CC BY-SA 4.0
Choosing the drive
- Rated output current of the drive must be at least the motor's rated current for the chosen connection; this is the main criterion, and the kW rating is only a guide.
- Load type: pumps and fans are light duty; conveyors, crushers and compressors that start loaded should get one size up or a heavy-duty rating from the catalogue.
- Supply: a 220 V single-phase input drive gives a 220 V three-phase output (the motor must be in delta for 220 V); a 380 V three-phase input drive gives a 380 V three-phase output.
Power circuit wiring diagram
The power circuit is the heavy current path from the supply through the drive to the motor. A mistake here can destroy the drive the first time it is switched on.
Supply side: breaker and R, S, T terminals
- The three-phase supply goes through a circuit breaker (or semiconductor-protection fuses) rated as recommended in the drive manual.
- You can add a contactor on the supply side to cut power on a fault or emergency stop, but never use it for everyday starting and stopping; start and stop with the drive's own commands.
- Connect to R/L1, S/L2, T/L3. A three-phase drive does not care about input phase sequence; the motor's direction depends on the U, V, W order and the FWD/REV command.
- Single-phase input drive: connect L and N to the two supply terminals marked on the label (Figure 2).
Photo: Suyash.dwivedi / Wikimedia Commons, CC BY-SA 4.0
Photo: Suyash.dwivedi / Wikimedia Commons, CC BY-SA 4.0
Motor side: 4 things never to do
Motor leads connect only to the U, V, W terminals (Figure 3), through nothing except intermediate terminal blocks.
- Never connect the supply to U, V, W. Mains on the output destroys the inverter stage instantly.
- Never fit power factor capacitors or capacitor-type surge protection between the drive and the motor.
- Never use a star-delta starter after a drive; the motor is permanently connected star or delta in its terminal box. The drive already starts it smoothly.
- Never switch a motor-side contactor while the drive is running. If an output contactor is unavoidable (for example to switch between motors), only operate it when the drive output is stopped.
Earthing, cables and interference
Connect the drive's earth terminal and the motor frame to the panel earth bar with conductors of adequate size. Use screened motor cable, with the screen earthed at both ends as the maker instructs; run power cables well away from control cables, and cross them at right angles. Long motor cables (usually from a few tens of metres, depending on the maker) need an output reactor or a lower carrier frequency: check the limit in the manual.
| Terminal | Common names | Connects to |
|---|---|---|
| Supply input | R/L1, S/L2, T/L3 (single-phase: L, N) | After the supply breaker |
| Motor output | U/T1, V/T2, W/T3 | Motor terminal box, already in star or delta |
| Earth | PE, earth symbol | Panel earth bar, motor frame |
| Braking resistor | P+ / PB or B1 / B2 | Braking resistor for high-inertia loads, on the terminals the maker specifies |
| DC bus | P+ / N− (or +, −) | Usually left empty; used to check that the capacitors have discharged |
Control circuit wiring diagram
The control circuit uses low voltage (usually the drive's internal 10 V and 24 V), but a wrong connection can still make the motor start unexpectedly or not start at all. Terminal names vary by maker (X1, DI1, S1, FWD...), so always check the manual.
Start, stop and reverse with digital inputs
- A switch or relay contact between X1 (FWD) and COM: closed runs forward, open stops.
- Between X2 (REV) and COM: run reverse. Never allow X1 and X2 to close together (use a 3-position switch or an interlock).
- X3 and X4 can be set for preset speeds, fault reset or coast stop.
- The emergency stop must cut out in hardware according to the machine's safety design (cutting the supply through a contactor, or Safe Torque Off if the drive has it), not rely on a single digital input.
Speed control by potentiometer or analog signal
A potentiometer of about 1–10 kΩ (see the manual): the two outer ends go to 10V and GND, the wiper to AI. Turning it from zero to full gives minimum to maximum frequency. Signals from a PLC or sensor: 0–10 V or 4–20 mA, selected with a DIP switch or an AI parameter. Use twisted, screened cable for analog signals, with the screen earthed at one end, at the drive.
Fault relay output
Relay RA – RB – RC (or TA – TB – TC): RA – RC is normally open, RB – RC normally closed. Set it to "fault" to light a red lamp on the panel door or signal a PLC. Figure 4 shows a working drive with power cables on the lower terminal row and multicoloured control wires on the upper row.
Photo: Rahat ( Talk * Contributions ) 11:43, 6 April 2015 (UTC) / Wikimedia Commons, CC BY-SA 4.0
Basic VFD parameter setup
Each maker uses different parameter codes (F0.01, P0-03, Pr.7...), but the basic groups are the same. The table lists 8 groups you must always review before running. Set them on the drive keypad (Figure 5) or with the maker's software.
| Parameter group | Meaning | Usual setting |
|---|---|---|
| Motor data | Rated power, voltage, current, frequency, speed | Exactly from the nameplate, for the chosen connection |
| Control mode | V/f or sensorless vector | Pumps, fans: V/f; conveyors and machines needing low-speed torque: vector after auto-tune |
| Run command source | Keypad, terminals or communication | Terminals when using push buttons or a PLC |
| Frequency source | Keypad, built-in pot, external AI, preset speeds | AI with an external potentiometer or PLC |
| Maximum / minimum frequency | Speed limits | Maximum usually 50 Hz; minimum to suit the machine, e.g. 10–20 Hz for self-cooled motors |
| Acceleration / deceleration time | Time from 0 to maximum frequency and back | Pumps, fans 5–20 seconds; high-inertia loads need longer or a braking resistor |
| Stop mode | Ramp down or coast | Conveyor: ramp; large fan: usually coast |
| Motor overload protection | Electronic thermal trip current | Nameplate rated current for the chosen connection |
Restore defaults before setting up
A used drive taken from another machine often holds odd settings (command source, keypad lock, minimum frequency). Restore factory defaults as the manual describes, set up from scratch, and record every changed parameter on the handover sheet.
Enter motor data and auto-tune
Enter the nameplate figures for the chosen connection. Vector mode needs a motor auto-tune: static or rotating; the rotating type requires the motor to be uncoupled from the load. Bad auto-tune data is a common cause of overcurrent trips and rough running at low speed.
Acceleration, deceleration and frequency
Acceleration time is usually defined as the time from 0 Hz to maximum frequency. Too short causes overcurrent trips at start; too short a deceleration on a heavy load pushes energy back into the capacitors and trips on DC overvoltage. Run above 50 Hz only if the motor and machine makers allow it.
Photo: Suyash.dwivedi / Wikimedia Commons, CC BY-SA 4.0
DC capacitor safety and working procedure
The particular danger of a drive is its DC capacitors: the breaker is off and the display is dark, but the terminals can still carry several hundred volts DC for minutes.
Safety warning: before opening the cover or touching drive terminals: (1) tell the operator and stop the machine; (2) switch off the breaker feeding the drive, lock it with your personal padlock and hang a tag with your name and phone number; (3) wait the full capacitor discharge time stated on the drive label (often about 5–10 minutes, longer on large drives), and the CHARGE lamp must be out; (4) with a meter proven on a live source, on a DC range rated at least 1000 V, measure between P+ and N− and across the supply and motor terminals: it must be close to 0 V before you touch anything; (5) a motor turned by its load (a fan in the wind, a pump with backflow) still generates voltage back to the drive, so block it mechanically. Do not work on 380 V unless trained and assigned, never work alone, and never stand on a wet floor. See also the general rules in 5 mandatory safety rules before you touch any electrical wire.
Insulation testing the motor
Never megger (high-voltage insulation test) a motor while it is still connected to U, V, W: the test voltage can destroy the drive. Disconnect the three motor leads from the drive, test the windings to frame at the motor terminal box, then reconnect.
Temperature and panel ventilation
A drive gives off heat of a few percent of the motor power. Mount it vertically with the top and bottom clearances from the manual, in a panel with an extract fan and dust filter. Dust clogging the heatsink fins is a common cause of overtemperature trips.
Worked example: a 1.1 kW conveyor running at 35 Hz
A packing workshop has a conveyor driven by a 1.1 kW three-phase motor with the nameplate in Figure 1: 220/380 V, 4.5/2.58 A, cos φ 0.78, 950 rpm, 50 Hz (a 6-pole motor). The workshop has a 380 V three-phase supply. Requirements: conveyor speed set by a potentiometer on the panel door, start and stop buttons, a fault lamp, and a normal speed of about 35 Hz.
Choosing the connection and drive
- A 380 V three-phase input drive gives a 380 V output, so the motor is connected star, rated current 2.58 A.
- The conveyor starts loaded, so choose one size up: a 1.5 kW drive whose rated output current (read the label) is at least 2.58 A.
- Settings: motor data 1.1 kW, 380 V, 2.58 A, 50 Hz, 950 rpm; run command from terminals; frequency source AI; maximum 50 Hz, minimum 15 Hz; acceleration 5 seconds, deceleration 5 seconds, ramp stop; overload protection 2.58 A.
Speed and timing
- Synchronous speed at 50 Hz with 6 poles: 120 × 50 ÷ 6 = 1000 rpm; rated speed 950 rpm, so 5% slip.
- At 35 Hz the approximate speed is 950 × 35 ÷ 50 = 665 rpm, or 70% of rated speed.
- Acceleration is set to 5 seconds for 0 → 50 Hz, so 0 → 35 Hz takes 5 × 35 ÷ 50 = 3.5 seconds.
Materials and labour estimate (reference prices in Vietnam, 2026, varying by region and brand)
| Item | Quantity × unit price | Amount |
|---|---|---|
| Drive, 380 V three-phase, 1.5 kW | 1 × 3,200,000 VND | 3,200,000 VND |
| Three-phase breaker feeding the drive | 1 × 350,000 VND | 350,000 VND |
| Potentiometer, push buttons, pilot lamp | 1 set × 250,000 VND | 250,000 VND |
| Screened motor cable | 15 m × 35,000 VND | 525,000 VND |
| Small enclosure, DIN rail, terminals, trunking | 1 set × 900,000 VND | 900,000 VND |
| Labour: wiring, setup, commissioning | 1 job × 1,000,000 VND | 1,000,000 VND |
| Total | 6,225,000 VND | |
Check: 3,200,000 + 350,000 + 250,000 + 525,000 + 900,000 + 1,000,000 = 6,225,000 VND (about US$240). Prices for a 1.5 kW drive vary widely, about 2,500,000–6,000,000 VND depending on brand and product line (2026 reference).
Commissioning in order
- Double-check: supply to R, S, T, not U, V, W; motor in star; earthing complete.
- Power up, set the parameters, remove the coupling or belt and test run without load from the keypad at 10 Hz: is the direction right? If not, change the run direction setting, or swap 2 of the 3 U, V, W leads after switching off and waiting for the capacitors to discharge.
- Switch the command source to terminals and test the start and stop buttons, the potentiometer from 15 to 50 Hz and the fault lamp.
- Couple the load, run at 35 Hz and read the current on the drive display: it must be below 2.58 A under normal load. Record it on the handover sheet.
Common mistakes when wiring and setting up a VFD
Fault codes vary by maker (OC, OU, LU, OL, GF...); the fault code table is always in the manual.
Overcurrent during acceleration
Sign: the drive trips as soon as you press run. Cause: acceleration time too short, a jammed load, wrong motor data, or shorted motor leads. Fix: lengthen acceleration, check the mechanics, re-enter the nameplate data, disconnect the motor leads and insulation test them.
DC overvoltage during deceleration
Sign: trips when stopping or slowing down. Cause: a high-inertia load returns energy to the capacitors. Fix: lengthen deceleration, set coast stop if the machine allows, or fit a braking resistor of the value the maker recommends.
Undervoltage or input phase loss
Sign: undervoltage trips when other machines in the workshop start. Cause: a weak supply, poor contact at the breaker or terminals, a missing phase. Fix: retighten terminals, measure all three phase voltages under load, check the breaker.
Drive blows up at first power-on
Sign: a bang and a burnt power stage. Cause: supply wired to U, V, W, or 380 V applied to a 220 V drive. Fix: not repairable on site; prevent it with a two-person cross-check and by reading the input voltage on the label before switching on.
Frequently asked questions
Can a single-phase to three-phase drive run a 380 V motor?
A 220 V single-phase input drive usually gives a 220 V three-phase output. A motor marked 220/380 V can run on it in delta at 220 V. A motor marked only 380/660 V is not suitable for this type of drive.
What is different when wiring a VFD for a pump?
The wiring is identical. The differences are in the settings: V/f mode for pump loads, a minimum frequency high enough for the pump to still deliver water, long acceleration and deceleration to avoid water hammer, and often pressure control with a 4–20 mA sensor.
Wrong direction: swap wires or change a setting?
Either works. The quickest is to change the direction parameter or the FWD/REV terminal; swap U, V, W leads only after switching off, waiting for the capacitors to discharge and measuring. Swapping R, S, T does not change direction.
Practice exercises and self-assessment
- Draw the power and control diagrams for a 2.2 kW extract fan with a 380/660 V nameplate on a 380 V supply: choose the motor connection, the drive, a speed potentiometer and a fault lamp.
- On a training board, restore a drive to defaults, set the 8 parameter groups in the table, test run without load and record the current at 20, 35 and 50 Hz.
- Practise the capacitor discharge procedure: switch off, lock, wait, measure P+ to N−, with an instructor supervising.
Self-assessment criteria
- Pass: the diagram has a breaker, R S T on the supply side, U V W to the motor, earthing, and no capacitors or star-delta after the drive.
- Pass: motor data matches the nameplate for the chosen connection; speed at 35 Hz and the matching acceleration time are correct.
- Pass: you always measure close to 0 V DC before touching terminals.
- Not yet: opening the cover right after switching off, meggering the motor while it is still connected to the drive, or using an output contactor to start and stop.
Drives are usually commanded by a PLC, so the next roadmap step is PLC basics and industrial sensors: you will use PLC outputs to send run commands, preset speeds and 0–10 V speed signals to a drive. If you are unsure about terminal boxes and star-delta connections, review Star-delta starter wiring diagram: power, control and timer setting.