Recharging an air conditioner with refrigerant is only truly needed when the unit is short of refrigerant, and because refrigerant circulates in a sealed loop, being short almost always means there is a leak: you measure the pressure to confirm it, find and fix the leak, and only then charge the right refrigerant by the right weight. "Topping up the gas every year" is a sign that the unit is leaking and nobody has fixed it, or that someone charged a unit that did not need it. This lesson is written the way a lead technician coaches an apprentice: telling R32, R410A and R22 apart, reading the gauges, finding leaks, charging by weight, with a worked example whose costs add up.
By the end of this lesson, you will be able to:
- Tell a unit that is genuinely short of refrigerant from one that is dirty, undersized or has a weak fan, before you touch the gauges.
- Read the rating label to find the refrigerant type and factory charge, and choose the right charging method for R32, R410A and R22.
- Measure standing pressure and running suction pressure and compare them with a reference table to decide whether a unit is short, correct or overcharged.
- Find leaks with soap solution and an electronic detector, and pressure-test with nitrogen before charging.
- Charge a wall-mounted inverter unit by weight and write a quote whose figures add up.
Learning the refrigeration and air-conditioning trade properly? Vacuuming, leak testing and charging is step 4 of the roadmap, after electrical and refrigerant safety, the refrigeration cycle and pressure gauges, and installing wall-mounted units. See the 8-step roadmap for refrigeration and air-conditioning technicians to learn in the right order.
When does an air conditioner really need refrigerant?
Refrigerant is not "burned" like petrol in a motorbike. It evaporates in the indoor coil, condenses in the outdoor unit and keeps circulating inside sealed copper pipes. A unit installed correctly, with no leaks, can run for many years without needing a single extra gram.
Three cases that need charging
- New installation with pipes longer than the standard length: the outdoor unit comes pre-charged for a certain pipe length (on the label or in the manual); for longer runs you add the grams per metre the manufacturer specifies.
- A leaking system: a flare nut that is not tight, a cracked brazed joint, a corroded coil, a leaking service valve. Fix the leak first, charge afterwards.
- A system opened for repair: compressor or coil replaced, pipes re-brazed. The refrigerant has been recovered or lost, so you evacuate and recharge the full weight on the label.
Signs that suggest low refrigerant (not yet a diagnosis)
The air gets less cool over several weeks, the difference between return and supply air is below about 6°C, the small pipe or service valve frosts up, and the unit runs non-stop. But dirty filters, dirty coils and a weak fan give similar signs; how to rule them out is covered in Air conditioner not cooling: 9 causes, self-checks and when to call. Only when the unit is clean and the fans run properly should you connect the gauges.
Why "routine gas top-ups" are wrong
Topping up every summer without measuring or looking for the leak costs the customer money every year, releases refrigerant into the air, and leaves the compressor running short for months, so it runs hot and wears quickly. A customer saying "it was topped up only last year" is a reason to search harder for the leak, not to top up again.
R32, R410A and R22: how they differ
Household units in Vietnam mostly use one of three refrigerants. Read the label on the side of the outdoor unit: refrigerant type, factory charge, design pressure. If the label is gone, look up the model in the manual; never guess from the brand or year of purchase.
| Criterion | R22 | R410A | R32 |
|---|---|---|---|
| Where you find it | Old units, most older non-inverter models | Many older inverter units, larger units | Most wall-mounted units sold new in recent years |
| Composition | Single substance (HCFC) | Blend of two (R32 + R125) | Single substance (HFC) |
| Working pressure | Lowest | High, about 1.6 times R22 | High, close to R410A |
| Flammability | Non-flammable | Non-flammable | Mildly flammable (class A2L) |
| Charging | Vapour or liquid | Liquid only | Vapour or liquid, liquid preferred for faster charging |
| Compressor oil | Mineral oil | Synthetic (POE/PVE) | Synthetic (POE/PVE) |
Never mix or swap refrigerants
Each unit uses only the refrigerant on its label. R22 in an R410A unit has the wrong pressures and oil, cools poorly and ruins the compressor. Putting R32 into an R410A unit "because the pressure is similar" is something manufacturers do not allow: the expansion device, charge weight and fire-safety requirements differ. If two refrigerants have been mixed, recover everything, evacuate and recharge from scratch. Cylinder colour is only a quick hint (R22 is often light green, R410A often pink); always read the refrigerant name on the cylinder label.
Why R410A must be charged as liquid
R410A is a blend of two substances with slightly different boiling points. Drawing vapour from the cylinder lets the more volatile one come out first, so the refrigerant entering the unit is off-ratio. That is why R410A is always drawn as liquid (position the cylinder as its label instructs) and the charging valve is opened slowly so the liquid has time to vaporise rather than slugging the compressor.
Measuring pressure: reading the gauges and a reference table
A manifold gauge set has two gauges: blue for the low side (suction, the larger pipe) and red for the high side. Wall-mounted units usually only have a charging port on the larger-pipe service valve at the outdoor unit, so you mostly read the blue gauge (Figure 1). R32/R410A need a high-pressure gauge set with 5/16 inch connectors; an old R22 set is not rated for the pressure and has the wrong thread.
Standing pressure: measured with the unit off
Switch the unit off for at least 10–15 minutes so both sides equalise. While liquid refrigerant remains, standing pressure is roughly the saturation pressure at ambient temperature, so it only tells you "is there still liquid or not", not whether a few hundred grams are missing. A standing pressure well below the table means the unit has leaked badly.
Running suction pressure: the key reading
Run in cooling mode at the lowest set temperature and high fan for at least 10–15 minutes. Inverter units must be put into test-run mode (as the manual describes) so the compressor runs at its rated frequency; otherwise the reading drifts constantly. Record suction pressure, outdoor temperature, room temperature and current with a clamp meter.
| Reading (reference) | R22 | R410A | R32 |
|---|---|---|---|
| Standing pressure at about 30°C | About 155–160 psi (10.7–11 bar) | About 255–265 psi (17.6–18.3 bar) | About 260–270 psi (17.9–18.6 bar) |
| Running suction pressure, correctly charged | About 60–80 psi (4.1–5.5 bar) | About 115–145 psi (7.9–10 bar) | About 115–145 psi (7.9–10 bar) |
| Suggests low charge | Below about 55 psi | Below about 105 psi | Below about 105 psi |
Gauges read gauge pressure (above atmospheric); 1 bar is about 14.5 psi. These are reference ranges for wall-mounted units; the correct value depends on temperatures, coil cleanliness and each maker's design, so always check the unit's technical documents. R32 and R410A have almost the same pressures, so you cannot identify the refrigerant from the gauge.
Reading pressure, current and temperature together
- Low suction + current below rated + frost on the small pipe: points to low charge.
- Low suction + dirty indoor coil, weak airflow: the coil is not picking up enough heat; clean it and measure again.
- High suction + high current + very hot outdoor unit: overcharge, a dirty condenser or a weak condenser fan.
- High suction + low current, quiet compressor: a weak compressor, not a refrigerant problem.
Find the leak before charging: a mandatory procedure
Charging without finding the leak just "buys the customer a few cool weeks". Search from the most common leak points to the hardest to see.
The most common leak points
- Flare nuts at the indoor unit (inside the insulation behind the unit) and at the outdoor unit: off-centre flare, scratched flare face, over- or under-tightened.
- Service valves: a leaking Schrader core, a cap missing its seal or not tightened.
- Brazed joints on pipes and coils: poor penetration, cracks from vibration.
- Coils with pinhole corrosion (common near the sea), pipes that are kinked or drilled through when someone hangs something on the wall.
Three ways to find a leak
- Soap solution: thick soapy water or a proper leak-detection fluid brushed all round flare nuts, valves and joints; wait 1–2 minutes. A leak bubbles; a slow leak shows only tiny bubbles.
- Electronic leak detector: hold the probe a few millimetres from the pipe and move slowly; the detector must suit the unit's refrigerant, and wind makes it easy to miss a leak.
- Oil marks: escaping refrigerant often carries compressor oil and leaves a dusty black oily patch. A shiny, oily flare nut is the first suspect.
Nitrogen pressure test when the system is empty or just repaired
When the system is nearly empty the pressure is too low for bubbles to show clearly. Recover what is left, fill with dry nitrogen through a pressure regulator (Figure 2), hold the pressure and watch it. Use the test pressure in the manufacturer's instructions and never exceed the design pressure on the label; many manufacturers' documents allow about 30–40 bar for R32/R410A wall units. Hold for at least 15–30 minutes, longer if you suspect a slow leak. If the pressure clearly drops, brush on soap solution; now the bubbles are easy to see.
Photo: Seaborg / Wikimedia Commons, CC BY-SA 3.0
Fixing the leak
Leaking flare: cut off the old flare, re-flare at the correct size, put a drop of refrigeration oil on the flare face and tighten with a torque wrench to the maker's torque. Leaking valve core: replace the core. Leaking joint or holed pipe: re-braze with silver or phosphor-copper brazing rod (Figure 3); a coil with several holes should be replaced. Always pressure-test again after the repair.
Photo: 176th Wing Alaska Air National Guard from Anchorage, Alaska, United States / Wikimedia Commons, CC BY 2.0
Charging refrigerant the right way
There are two situations: topping up a unit that still has refrigerant, and recharging completely when the unit is empty or has been opened for repair. For inverter and R410A units that have been opened, the safest method is a full recharge by weight.
Tools to prepare
Gauge set and hoses rated for the refrigerant, refrigerant scale (5–10 g resolution), vacuum pump, micron gauge, nitrogen cylinder and regulator, clamp meter, thermometer, flaring and cutting tools, torque wrench, hex keys, cold-resistant gloves, safety glasses, and a fire extinguisher when working with R32.
Full recharge by weight (recommended)
- Fix the leak, pass the nitrogen test, release the nitrogen.
- Evacuate through the service valve. Many manufacturers and technicians use a target below about 500 microns; then close the valve, switch off the pump and hold for 10–15 minutes: a reading that creeps slightly then stops is a pass; one that keeps rising means a leak or moisture.
- Put the cylinder on the scale, purge air from the hose with a little refrigerant, and tare the scale to zero.
- Work out the charge: the label weight plus the extra for pipe beyond the standard length.
- Charge with the unit off until pressures equalise; add the rest through the suction side with the unit running in cooling mode. R410A always as liquid, valve opened slowly.
- Stop when the scale shows the target weight, close the valve, disconnect the hose quickly to lose little refrigerant, and refit the valve cap with its seal.
- Test-run for at least 15–20 minutes: record suction pressure, current and air temperature difference on the customer's job sheet.
In step 5, one hand works the manifold valve while your eyes follow the gauge and the scale (Figure 4). Stand outdoors, wear gloves and keep your face away from the connections.
Photo: U.S. Air Force photo by Senior Airman Mark Colmenares / Wikimedia Commons, Public domain
Topping up a unit that still has refrigerant
Only when the leak has been fixed without opening the system, and only for R32 or R22 (single-substance refrigerants). Charge into the suction side with the unit in test-run mode, about 50 g at a time, wait 3–5 minutes, then read pressure, current and air temperature again; stop when they are in the maker's range. An R410A unit that has leaked may already be off-ratio, and many makers recommend a full recharge.
Overcharging also damages the unit
Adding "a bit extra for more cooling" causes overcharge: high-side pressure and current rise, the outdoor unit runs very hot, liquid can return and damage the compressor, and the unit actually cools less. Recover the excess into a recovery cylinder; never vent it.
Safety when charging, especially with R32
Charging combines three hazards: 220 V electricity, high-pressure refrigerant and working at height on the outdoor unit. R32 adds a fire risk.
Safety warning: R32 is mildly flammable (A2L): while R32 is in the system or being released or charged, no smoking, no open flame, no brazing; recover all refrigerant and purge the pipes with nitrogen before brazing, work in a ventilated area and keep a fire extinguisher at hand. Never use oxygen, compressed air or fuel gas for pressure testing; oxygen in contact with oil can explode. Liquid refrigerant on skin or eyes causes frostbite: always wear glasses and cold-resistant gloves and never point a hose at anyone. Keep cylinders out of the sun and away from heat, and never fill a recovery cylinder beyond the limit on its label. Switch off the breaker before opening the outdoor unit and wait for the inverter board capacitors to discharge. When mounting or servicing an outdoor unit outside a window or balcony, wear a full-body harness anchored to a solid point.
Recover refrigerant, never vent it
Venting refrigerant is wasteful and harmful: R22 depletes the ozone layer, and R410A and R32 are greenhouse gases. Vietnam is gradually tightening control of these substances in the refrigeration trade; learn to recover with a recovery machine and cylinder, and check the current rules with the environmental authorities yourself.
When to stop
Stop and call the lead technician if the compressor knocks, there is a burning smell, the breaker trips when the compressor starts, or you are not sure which refrigerant the unit uses. An apprentice does not braze on an R32 unit without supervision.
Worked example: a 12,000 BTU inverter R32 unit "getting weaker"
An apartment in Hanoi with a 12,000 BTU wall-mounted inverter unit on R32, installed 2 years ago. The customer says cooling has been fading since early summer, and cleaning last month did not help. The pipe run from the indoor to the outdoor unit is 10 m.
Measuring and diagnosing
- Filters and indoor coil clean; outdoor fan running properly. Air temperature difference only 5°C.
- Test-run mode on; after 15 minutes the suction pressure is 85 psi (table above: correctly charged is about 115–145 psi), current below rated, light frost on the small-pipe service valve. Conclusion: low charge.
- Soap solution: the large-pipe flare nut at the indoor unit shows tiny bubbles, with a dusty oil mark around it. The flare face is scratched, probably from the original installation.
Repair and charge
- Recover the remaining refrigerant, cut and re-flare the joint, tighten with a torque wrench, re-wrap the insulation.
- Nitrogen test at the maker's allowed pressure, held 30 minutes with no drop. Release the nitrogen, evacuate below 500 microns, hold 15 minutes: pass.
- Label: factory charge 0.60 kg R32 for pipes up to 7.5 m; extra 20 g/m beyond that. Actual pipe 10 m, so 10 − 7.5 = 2.5 m extra and 2.5 × 20 = 50 g. Total charge: 600 + 50 = 650 g.
- Cylinder weight before charging 5,200 g, after 4,550 g: 5,200 − 4,550 = 650 g, matching the calculation.
- Test run 20 minutes: suction 128 psi, air temperature difference 10°C, current within rating. Job sheet completed.
Quote for the customer (2026 reference prices, varying by area)
| Item | Note | Amount |
|---|---|---|
| Inspection, pressure reading, leak search | Gauges, soap solution | 150,000 VND |
| Re-flare joint, re-wrap insulation | 1 joint | 150,000 VND |
| Nitrogen test + evacuation | With micron gauge | 200,000 VND |
| R32 full recharge by weight | 650 g | 450,000 VND |
| Total | 950,000 VND | |
Check: 150,000 + 150,000 + 200,000 + 450,000 = 950,000 VND (about 38 US dollars). A 300,000 VND "top-up" without re-flaring is cheaper this time, but the unit will be short again within months; two or three of those cost more than one proper repair.
Common mistakes when recharging an air conditioner
Charging by feel: "the pipe is cold, so it's enough"
Sign: the customer calls back because the unit cools poorly and draws high current. Cause: charging until the pipe feels cold, without measuring or weighing. Fix: weigh in a full recharge; top up in small steps, reading pressure, current and air temperature after each step.
Reading an inverter unit outside test-run mode
Sign: the pressure keeps changing, one reading looks low and the next looks fine. Cause: the inverter compressor changes speed with room temperature. Fix: switch on test-run mode and wait for it to settle before reading.
Skipping the vacuum
Sign: a newly charged unit runs a few weeks, then suffers moisture blockage, poor cooling or even a failed compressor. Cause: "purging" with refrigerant instead of evacuating, leaving air and moisture in the pipes. Fix: always evacuate with a micron gauge every time the system is opened.
Frequently asked questions
How often does an air conditioner need refrigerant?
A unit with no leak never needs routine recharging. If it needs refrigerant every year, there is a leak to find and fix. Routine maintenance means cleaning and checks, not adding refrigerant.
How much does an air conditioner recharge cost?
2026 reference prices in Vietnam: an R32 or R410A top-up for a wall unit is about 250,000–500,000 VND, a full recharge with evacuation about 450,000–900,000 VND, not including leak repair. Ask for an itemised quote and a job sheet with the readings.
Can an R410A unit be charged with R32?
No, unless the unit's manufacturer explicitly allows it and gives instructions. The pressures are similar, but the charge weight, flammability and expansion device design differ. Charge each unit with the refrigerant on its label.
Can a homeowner recharge an air conditioner at home?
Not advisable. Charging needs gauges, a scale, a vacuum pump, leak-finding skills and safe handling of high-pressure and flammable R32 refrigerant. Homeowners can wash the filters and keep the outdoor unit well ventilated; leave the refrigerant to a trained technician.
Practice exercises and self-assessment
- Read the labels on 3 different air conditioners and note the refrigerant type, factory charge, standard pipe length and extra grams per metre.
- With a lead technician supervising, connect gauges to a unit that works well and record standing pressure, suction pressure in test-run mode, current and outdoor temperature.
- Calculate the charge for a 9,000 BTU R32 unit: factory charge 0.50 kg for pipes up to 7.5 m, extra 15 g/m, actual pipe 12 m; write a quote using the table above as a template.
Self-assessment criteria
- Pass: you read the refrigerant type on the label correctly and can explain why a different refrigerant must not be used.
- Pass: suction readings are recorded with outdoor temperature and test-run mode and compared with the reference table.
- Pass: your charge works out as 500 + 4.5 × 15 = 567.5 g (rounded to 570 g) and the quote adds up.
- Not yet: charging before finding the leak, skipping the vacuum, or charging R410A as vapour.
Once you can charge correctly, move on to the next step of the roadmap: Cleaning and servicing air conditioners and refrigerators, where you learn to keep coils clean so the unit runs at the right pressure and current without needing extra refrigerant. To see how long it takes to reach the point of charging units for customers, read How long to learn air conditioner repair? Fees, path and 2026 pay.
Keep learning the trade: after vacuuming and charging come cleaning and servicing, diagnosing error codes and inverter boards, a full-apartment installation project and trade certification. See the 8-step roadmap for refrigeration and air-conditioning technicians.