“It’s just joining two wires.” Many people say that, then quickly twist two copper ends together, wrap them in black tape and push them into the ceiling. A few months later that very spot heats up, the tape turns soft and gooey, the lights flicker and the socket works one minute and not the next.
The joint is the weakest point of a wiring run: continuous cable rarely fails in the middle, and faults are usually at joints and screw terminals. Joining wires correctly is a foundation skill for every electrician.
This lesson belongs to the “Installing lighting circuits, switches & sockets” step. By the end of this lesson, you will be able to choose between a twisted joint, a twist-on connector, a terminal block (in Vietnam called a “domino”) or a crimp butt splice, follow a 7-step procedure for joining wires in a junction box, and check your work before switching the power back on.
Safety first: Only join wires after you have switched off the circuit breaker (MCB), hung a warning sign and verified by measurement that the circuit is dead using a voltage tester or multimeter (test the instrument on a live source before and after measuring). Never join “live” wires. Review the 5 mandatory safety rules before touching any electrical wire before you start.
Why do joints overheat and burn?
Where two copper cores touch, current only flows through the points that are truly in contact. If a joint is loose, dirty or oxidised, the contact area shrinks and the contact resistance rises. The heat produced there is proportional to the square of the current times the resistance (P = I² × R), so the larger the current, the hotter the joint gets.
This is a vicious circle: heat makes the metal expand and contract every time the load is switched on and off, so the joint gradually loosens, the copper surface oxidises faster, the resistance rises and it heats up even more, until the cable insulation and tape char and cause a short circuit or fire. The circuit breaker usually does not trip in this case, because the current does not exceed its rating — there is just one small spot getting hot.
Common culprits: loosely hand-twisted joints, stripping that nicks the core, stranded flexible wire clamped directly under a screw so strands break, wrong-size connectors, copper joined directly to aluminium (two different metals corrode at the point of contact), and joints buried inside walls or conduit. The lesson Sockets and plugs that get hot, scorched or melted describes this phenomenon at sockets; here we deal with the root cause.
5 criteria of a good joint
Mechanically secure: gently pulling each wire does not pull it out or turn it.
Good electrical contact: clean cores, pressed tightly; under load the joint is not noticeably hotter than the wire on either side.
Insulation at least as good as the cable sheath: no exposed core or copper strands.
Located in a junction box or a device back box with a cover that can be opened for inspection.
Correct type and size: suited to the cable type, cross-section, number of wires, and the current and voltage marked on the accessory.
Common joining methods and when to use them
Twisted joints wrapped with insulating tape
The “traditional” method: strip both ends, twist them tightly, fold down the sharp end and wrap with tape. The figure below shows the classic diagram for an inline joint between two solid wires (the Western Union splice): cross the wires, hook them together, then wrap each end in many tight turns around the other wire.

Figure 1. Diagram of an inline twisted joint between two solid wires (A–D) and two longer-wrap variants (E, F), from the 1915 book “Practical Electric Wiring”. (Image: John MacLaren Sharp, Wikimedia Commons, Public domain)
A properly made twisted joint is strong, but its weak point is the insulation: over time tape loses its adhesion, and when heated it softens and peels off. Therefore:
Only use it when no suitable accessory is available, and it must still be placed inside a junction box.
Wrap insulating tape with moderate tension, overlapping by about half the tape width, extending over the cable insulation on both sides (for reference: a few cm). Do not use office tape or paper masking tape.
Twisted joints with twist-on connectors (wire nuts)
A twist-on connector is a plastic cap with a tapered metal spring inside. Place it over wire ends laid side by side and turn it clockwise: the spring bites into the cores, twists and holds the wires tightly, and the plastic shell covers the copper completely.

Figure 2. Twist-on connectors come in many sizes, usually distinguished by colour; inside is a tapered spring. Which colour matches which wire size must be checked in each manufacturer’s chart. (Photo: Junkyardsparkle, Wikimedia Commons, CC0)
Points to note:
Colour is not a universal standard. Each manufacturer has its own chart showing how many wires and which sizes each connector can take; read the packaging before use.
Best suited to solid single-core wire; join flexible wire with it only if the manufacturer allows.
Turn until tight and the wires below begin to twist together; pull-test each wire; no copper should be visible below the edge of the connector.
Lever connectors (push-in connectors)
This type has a clear plastic body with a lever for each entry: open the lever, insert the wire stripped to the correct length all the way in, close the lever and you are done. Some other types have no lever and are simply push-in (push the wire in and it is held). The cover photo of this lesson shows two junction boxes in progress using connectors with orange levers.
Advantages: fast, consistent, easy to undo for inspection; many models take both solid and flexible wire. Disadvantages: higher price, and poor-quality products have weak springs and plastic that deforms easily.
Read the body of the connector: cross-section range, wire type, rated current and voltage; many types have a strip-length gauge printed right on the body.
Lever-less push-in types are usually for solid wire only; flexible wire pushed in easily splays its strands and makes poor contact.
Insert the wire until the copper end touches the end of the entry (the clear body lets you see it), close the lever and pull-test.
Choose products with a known origin and clear specifications.
Terminal blocks (“domino” screw connectors)
A terminal block is a strip of paired entries with brass tubes and clamping screws inside, encased in plastic. Each pair of entries joins two wires facing each other.

Figure 3. A four-way terminal block strip (screw connector): each way has a brass tube and clamping screw, with a plastic casing. (Photo: VSchagow, Wikimedia Commons, CC BY-SA 4.0)
Terminal blocks are cheap and common, but often used incorrectly:
Stranded flexible wire clamped directly under a screw easily breaks strands; crimp on a bootlace ferrule before clamping.
Do not solder-tin the end of flexible wire and then clamp it under a screw: solder is soft and over time it creeps under pressure, so the screw gradually loosens.
The copper core must sit fully inside the brass tube, with no copper protruding beyond the plastic edge, and the screw must not clamp onto the insulation.
Tighten firmly with a screwdriver of the right size (overtightening strips the thread and cracks the plastic), then pull-test each wire.
Screw connections can loosen over time, so terminal blocks must be located where they can be opened for inspection.
Crimp butt splices and heat-shrink tubing
A crimp butt splice is a metal sleeve for joining two wires inline: insert both wire ends and crimp with a crimping tool of the correct type and die, then cover with heat-shrink tubing (slipped on before crimping). The sleeve, the tool die and the wire cross-section must all match; crimping with ordinary pliers or a hammer gives a joint that looks tight but has poor contact. If you do not have the correct crimping tool, choose another method.
Soldering
Rarely used for household wiring: it is time-consuming, easily burns the insulation, and solder-tinned wire ends do not suit screw clamps. If you solder, the joint must still be twisted securely first (solder only improves contact), then covered with heat-shrink tubing.
Reference table: choosing a joining method for the situation
Method | Solid single-core wire | Stranded flexible wire | Advantages | Disadvantages | Notes |
|---|---|---|---|---|---|
Twist + tape | Yes | Yes | No accessories needed | Tape ages; depends on skill | Only when no accessory is available; must still be in a box |
Twist-on connector | Best suited | Depends on manufacturer | Cheap, covers copper completely | Easy to choose the wrong size | Check the manufacturer’s wire-size chart |
Lever connector | Yes | Yes (types clearly marked) | Fast, removable, wire visible | Higher price; poor-quality ones loosen | Strip to the gauge on the body |
Push-in connector | Yes | Usually not | Very fast | Usually for solid wire only | Read the connector body |
Terminal block | Yes | Use ferrules | Cheap, common | Screws may loosen over time | Must be accessible for inspection |
Crimp butt splice + heat shrink | Yes | Yes | Strong, compact, inline joint | Needs the correct crimping tool | Sleeve, die and wire must match |
Reference table: preparing wire ends and checking
The figures below are for reference only; always give priority to the instructions printed on the accessory you are using.
Item | Method / reference value | How to check |
|---|---|---|
Strip length for lever connectors | According to the gauge printed on the connector body (usually about 1 cm, for reference) | Copper touches the end of the entry, no copper exposed outside the body |
Strip length for terminal blocks | Equal to the depth of the brass tube | No copper protruding from the plastic edge, screw not clamping the insulation |
Strip length for twist-on connectors | According to the manufacturer’s chart on the packaging | After twisting, no copper visible below the connector edge |
Spare wire left in the box | Long enough to pull out and redo the joint once (for reference: about 10–15 cm) | The cover closes without squashing the wires |
Continuity | Multimeter on the Ω or continuity range, with the circuit de-energised | Joint is continuous and does not touch other wires |
Insulation resistance | Insulation resistance tester (megger), used by a qualified electrician; reference minimum 1 MΩ at 500 V DC for a 230 V circuit (per IEC 60364-6) | Between line – neutral – earth, with electronic devices disconnected |
Temperature under load | Run the load for a while, then measure with an infrared thermometer, or switch off and open the box to check | The joint is not noticeably hotter than the wire on either side |
Tools and materials
Testing: voltage tester, multimeter (see how to use a multimeter as an electrician); an insulation resistance tester if available.
Insulated tools: wire strippers of the right size, cutters, needle-nose pliers, screwdrivers that fit the screws; a crimping tool if you use ferrules or crimp splices.
Materials: junction boxes with covers (waterproof types for damp locations), connectors or terminal blocks of the right size, ferrules, heat-shrink tubing, insulating tape, and cable of the same type and cross-section.
Protective equipment: safety glasses, a torch and a sturdy ladder.
Procedure for joining wires in a junction box: 7 steps
Step 1. Switch off, lock out and verify
Switch off the circuit breaker for the circuit (or the main breaker if you are not sure), hang a “Work in progress, do not switch on” sign and tell the people in the house. Test all the wires in the box: line – neutral, line – earth, neutral – earth. One junction box may contain wires from two different circuits, so test everything before touching.
Step 2. Identify the wires and choose a joining method
Photograph the wire positions before disconnecting, and identify the line, neutral and earth wires and the wires going to lights and sockets. The common IEC colour code is brown (or black, grey) for line, blue for neutral, and green-yellow for earth, but many older houses in Vietnam use red for line, blue or black for neutral, and sometimes only one colour. Do not trust the colours — measure. Then choose the joining method from the table above.
Step 3. Trim and strip to the correct length
Cut off old wire ends that are blackened, green with corrosion or hard and brittle, until you see bright copper and soft insulation. Strip with wire strippers on the hole matching the wire size; do not score around the wire with a knife, as this easily nicks the core.
Check: the core has no nicks and flexible wire has not lost any strands. If you nick it, cut off that section and strip again.
Step 4. Prepare the ends of stranded flexible wire
Gently twist the strands in one direction to keep them neat. For terminal blocks and screw clamps, crimp on a ferrule of the correct size; for lever connectors rated for flexible wire, insert directly, as long as the strands do not splay.
Step 5. Make the joint
Lever connector: open the lever, insert the wire to the end of the entry, close the lever; one wire per entry.
Twist-on connector: lay the wire ends side by side and level, put on the connector and turn clockwise until tight.
Terminal block: core fully into the brass tube, tighten firmly; the two wires to be joined must be at the two ends of the same brass tube.
Crimp butt splice: slip on the heat-shrink tubing first, crimp with the correct die, then shrink it with a heat gun.
Twisted joint (when unavoidable): twist tightly with pliers, trim neatly, fold down the sharp end and wrap tape fully over the insulation on both sides.
Always join line to line, neutral to neutral and earth to earth; the earth conductor must be continuous.
Step 6. Pull-test and check the insulation
Pull moderately on each wire; any wire that comes out or turns must be redone. Inspect closely: no copper strands sticking out, and no copper exposed outside the connector, terminal block or tape. Test continuity and check that there is no cross-contact between wires.
Step 7. Arrange the wires, close the cover and test under load
Fold the wires in gentle bends into the box so that the joints are not squashed when the cover is closed; fix the box in place. Remove the sign, switch the breaker on and test the devices. For heavy-load circuits (kitchen sockets, water heaters, air conditioners), run the load for a while, then switch off and open the box to see whether any joint is abnormally warm.

Figure 4. Example junction box: the wires are joined in groups by function (brown with brown, blue with blue, green-yellow with green-yellow), each group with one twist-on connector. After checking, the joints must be folded neatly into the box and the cover closed. (Photo: Dmitry G, Wikimedia Commons, CC BY-SA 3.0)
Real-life example 1: extending the wire for a balcony light
The client wants to move the balcony light about one metre further, and the old wire is not long enough. The wrong way: twist the wires, tape them and run them into the trunking. The right way: install a waterproof junction box with a cover at the joint, use new cable of the same type and cross-section, join with lever connectors or a terminal block, and also join the earth wire if the light has a metal body; then switch it on and off several times to test.
Real-life example 2: a kitchen socket that keeps cutting out
When an electric kettle is plugged into the kitchen socket, it runs and then cuts out. Switch off, verify the circuit is dead, and open the junction box above: the taped twisted joint has become brittle, the copper is blackened and the insulation next to it is scorched. The section of wire behind it turns out to be old aluminium wire joined directly to new copper wire.
Solution: cut out the damaged section and never join aluminium directly to copper; ideally replace the aluminium section with copper wire of the correct cross-section, and if that cannot be done yet, only use accessories clearly marked as approved for joining aluminium to copper. Also check whether the wire cross-section matches the circuit breaker protecting the circuit (see how to choose cable cross-sections and circuit breakers for each circuit), and advise the client to replace the remaining aluminium sections.
Common wire-joining mistakes
Joining inside conduit, walls or ceilings without a box: it cannot be inspected, and repairs require breaking into the structure.
Joining on a smaller section of wire in a circuit protected by a large breaker: a breaker only protects the wiring when it matches the smallest wire in the circuit.
Joining extension-lead or appliance flex cables with tape: flexible cords are constantly pulled and bent; if damaged, replace the whole length.
Using a green-yellow wire as a line conductor, or leaving out the earth wire when extending a circuit.
Safety checklist
Correct breaker switched off, sign hung, people in the house informed; verified dead on all wires in the box with an instrument that has been tested on a live source.
Joining accessories suit the wire type, cross-section and number of wires, with clear specifications.
Cores not nicked, no strands lost; flexible wire fitted with ferrules when clamped under screws.
No exposed copper; every wire passes the pull test.
Line to line, neutral to neutral, earth continuous.
Joints are inside a box with a cover that can be inspected; waterproof boxes used in damp places.
No direct aluminium-to-copper joints; no wire smaller than the breaker protection allows.
The circuit should have residual-current protection (RCD, RCBO); if the house does not have one, advise the client to install it.
Heavy-load circuits: run a load test, then re-check the temperature of the joints.
Work inside the main distribution board and complete rewiring of a house should be done by qualified, properly licensed electricians; everything before the electricity meter is managed by the power utility (EVN) and must not be tampered with.
Working with the client when joining wires
Explain why junction boxes and connectors are needed: they cost a little more in materials, but the joints last and can be inspected.
Inform the client before tackling a bigger problem (old aluminium wiring, brittle cracked insulation, many scorched joints): take photos to show the client, and propose a solution and cost before doing any extra work.
Photograph and note the locations of new junction boxes and hand this over to the client.
Frequently asked questions
Can I join electrical wires with just black tape?
It is not recommended. Tape only insulates; it does not hold the joint securely and loses adhesion over time. If a twisted joint is unavoidable, it must be twisted very tightly, wrapped with insulating tape and placed in a junction box; it is better to use a connector or terminal block of the right size.
Can copper wire be joined to aluminium wire?
Not directly. Only use accessories clearly marked as approved for joining aluminium to copper; ideally, replace the aluminium section with copper wire of the correct cross-section.
How do I join solid single-core wire to stranded flexible wire?
Use a lever connector rated for both types of wire, or crimp a ferrule onto the flexible wire and clamp it in a terminal block. Use twist-on connectors only if the manufacturer allows.
Can wires be joined inside concealed conduit?
It is not recommended. Joints must be in a junction box or device back box with a cover; the cable in a conduit should run in one continuous length from one box to the next.
Is it a problem to join two wires of different cross-sections?
It is acceptable if the joining accessory suits both wire sizes. But you must make sure the breaker protecting the circuit matches the smaller wire; never join a smaller wire into a circuit protected by a large breaker.
Practice exercises
Work on a practice bench with no power; only energise for testing on a board with a circuit breaker, an RCD and an instructor supervising.
Exercise 1 – Stripping: strip 10 solid wire ends and 10 flexible wire ends to the gauge on a lever connector; no nicks and no lost strands.
Exercise 2 – Four joint types: a lever connector (3 wires), a twist-on connector (2 wires), a terminal block with ferruled flexible wire, and an inline twisted joint as in Figure 1 wrapped with tape. Pull-test each joint.
Exercise 3 – Complete junction box: connect the supply, the wire to the switch and the wire to the light (line, neutral, earth); test continuity, check for cross-contact, close the cover, and with an instructor present, energise for testing.
Exercise 4 – Fault finding: the instructor prepares 5 faulty joints; trainees identify each fault and how to fix it.
Pass criteria:
You do not touch any wire before switching off and verifying that it is dead.
Every joint is secure, with no exposed copper, correctly paired line – neutral – earth, and neatly inside the box.
You can choose a suitable joining method and explain why.
Related lessons to study next: installing two-way switches and earthed sockets correctly and surface wiring with plastic trunking.