A client calls: “After a shower my bathroom mirror stays fogged for an hour and the ceiling corner is growing black mould. Could you install an extractor fan and wire it to the light switch for convenience?” It sounds simple, but electricians often get called back because the fan hums loudly, water drips from the fan grille, air blows back in when it rains, or the RCD trips every time someone showers. By the end of this lesson, you will be able to choose the right fan and size, pick a mounting position with proper airflow and the correct IP rating, wire it with a shared light switch, a separate switch or an overrun timer, install the ducting and backdraft shutter to prevent condensation, and test-run the fan before handing it over.
The manufacturer’s wiring diagram and installation manual are the highest authority; the figures in this lesson are for reference only, and where they differ, follow the manual and current regulations. Before touching any wire, switch off the circuit breaker (MCB) and verify the circuit is dead according to the 5 mandatory safety rules. Bathrooms are damp and people stand barefoot on wet floors, so electrical mistakes here are more dangerous.
What types of bathroom extractor fan are there?
By mounting method
Wall- or window-mounted: blows straight outside without ducting; suits bathrooms with an outside wall.
Ceiling-recessed with ducting: the fan body sits in the plasterboard ceiling and moist air travels through a duct to an outside wall or light well; common in Vietnamese townhouses and apartments.
Inline: installed in the middle of the duct run; quieter because the motor is far from the room, but needs a ceiling access hatch for maintenance.
By control method
Two-wire fan (L, N): runs whenever it has power; controlled by the light switch or a separate switch.
Fan with an overrun timer: when the light is switched on the fan runs, and when the light is switched off the fan keeps running for a while and then switches itself off. This type usually has three supply terminals; see Step 4.
Fan with a humidity or motion sensor: runs automatically when humidity exceeds a threshold or someone is present, and usually also needs a permanent supply.
Step 1: Choose a fan that fits the need
Read the specifications on the box and rating label
Airflow (m³/h): usually measured without ducting; with long ducts and many bends, the actual airflow is lower.
Static pressure (Pa): high-pressure fans (usually centrifugal) cope with long ducts better than thin-bladed axial fans.
Duct spigot diameter: must match the duct to be used; never reduce the duct size.
IP rating and permitted mounting locations (see Step 2).
Insulation class: many plastic-bodied fans are double insulated (symbol of two nested squares) and have no earth terminal. Metal-bodied fans must be earthed.
Calculate the required airflow
The usual method: room volume × number of air changes per hour. For bathrooms, the figure usually quoted is about 6–10 air changes per hour (for reference); use the higher figure if there is a lot of hot showering.
Example: a 2 m × 2 m bathroom with a 2.7 m ceiling → volume ≈ 10.8 m³. At 8 changes per hour → about 86 m³/h needed. With about 3 m of duct and one bend, choose a fan rated at about 110–150 m³/h.
Reference table for sizing a fan by room
Room type (ceiling about 2.7 m) | Floor area | Estimated airflow needed | Rated airflow to choose | Notes |
|---|---|---|---|---|
Small toilet, no shower | up to 2 m² | 30–50 m³/h | 60–90 m³/h | A wall-mounted fan is usually enough |
Small bathroom with shower | 3–4 m² | 50–110 m³/h | 90–150 m³/h | For long ducts, choose a high-pressure fan |
Medium bathroom | 5–6 m² | 80–160 m³/h | 150–220 m³/h | An overrun timer is recommended |
Large bathroom with bathtub | 7–9 m² | 110–240 m³/h | 200–300 m³/h | Consider an inline fan or two extract grilles |
Reference table only, based on 6–10 air changes per hour with an allowance for duct losses. For high ceilings, long ducts and many bends, choose a higher value; if the design or fan manual says otherwise, follow that.
Step 2: Choose the mounting position and understand bathroom “zones”
The airflow path
An extractor fan only works well when there is make-up air coming in, usually through the gap under the door or a louvred panel in the door. Layout principles:
Place the fan away from the entrance door, ideally on the opposite side, so the air travels from the door across the shower area before reaching the fan. A fan next to the door just pulls in outside air and blows it away, leaving the shower corner damp.
Mount it high, near the ceiling, because hot steam rises.
Near the shower and toilet, but not directly above the shower unless the IP rating and manual allow it.
Locate beams, water pipes and existing cables before drilling or cutting.

Figure 1. A recessed ceiling extractor fan housing (black box with duct spigot) fixed firmly to the ceiling frame before boarding; on the left is the flexible duct. Photo taken in a timber-framed house in the USA during renovation. (Photo: Stilfehler, Wikimedia Commons, CC BY-SA 4.0)
Wet zones in a bathroom (as a concept)
Electrical installation standards for bathrooms usually divide the space around the bathtub or shower tray into zones according to the degree of exposure to water:
Inside the bathtub or shower tray: may be submerged; ordinary electrical equipment is almost never installed here.
Directly above the bathtub, tray or shower area: directly sprayed with water; only high-IP equipment approved by the manufacturer may be placed here.
The surrounding band: may be splashed.
Outside the zones: still damp but rarely splashed.
The dimensions of each zone are set by the installation standard applied to the building; this lesson does not give figures to avoid confusion. Practical principle: the closer equipment is to water, the higher its IP rating must be, and ordinary switches and sockets go outside the bathroom or in a location away from water as regulations require.
Reading the IP rating
An IP code has two digits: the first digit is protection against dust and solid objects; the second digit is protection against water; “X” means that item was not tested.
IPX4: protected against splashing water from any direction; often given as the minimum for equipment in zones near water (for reference — check against the standard and the fan manual).
IPX5: protected against water jets; needed where the area is often hosed down or the shower sprays directly.
Fans with no IP marking should only be placed in dry spots, away from showers and spray hoses.
The IP rating is only achieved when the fan is installed correctly: all gaskets fitted, correct orientation, cable entries sealed. Cutting extra holes in the fan casing voids the IP protection.
Step 3: Circuit protection and cable selection
Household extractor fans are usually a few tens of watts and often take their supply from the bathroom lighting circuit; 1.5 mm² copper cable is usually enough (see how to choose cable cross-sections and circuit breakers).
The circuit supplying the bathroom needs 30 mA residual-current protection: a dedicated RCBO for the circuit, or downstream of an RCD depending on the board layout (see installing a household distribution board with MCBs and RCBOs). If the house does not have one, propose that the client installs it first.
Some fan manuals also require an isolating switch that breaks both line and neutral located outside the bathroom, or a small dedicated fuse for the fan. If required, do it exactly as specified.
Run cables in conduit, with joints inside a junction box with a cover or in the fan’s terminal box; never leave taped joints in the ceiling. See the lesson on joining electrical wires properly.
Still run an earth conductor (PE) to the fan position. For metal-bodied fans, connect PE to the earth terminal; for double-insulated fans, insulate the end of the PE conductor in the junction box, ready for a future replacement.
Step 4: Choose the control wiring method
General principle: the switch must break the line conductor (L), not the neutral (N). If it breaks N, the fan still has voltage on it when switched off, and anyone removing it for cleaning could get a shock. To find the line conductor, see the lesson on using a multimeter.
Method A: Fan wired to the light switch
The switched line from the light switch goes to the light and also branches to the fan’s L terminal; N is shared.
The advantage is fewer wires and the fan is never forgotten. The disadvantage: switching the light off stops the fan immediately while moisture is still in the air. Acceptable for a small toilet; for a bathroom with a shower, use method C.
Method B: Separate switch for the fan
Use a double switch with a shared line feed: one gang for the light, one for the fan. From the switch to the light and fan you need two switched line conductors, plus N and PE.
The homeowner can run the fan whenever they like, but often forgets to switch it off or on. You can replace the fan gang with a timer switch mounted outside the bathroom.
Method C: Fan with an overrun timer
This is the method most often wired incorrectly. Many timer fans have three supply terminals, usually marked:
Terminal on the fan | Connect to | Function |
|---|---|---|
L (permanent line) | Line conductor taken before the switch, always live | Powers the timer circuit so the fan keeps running after the light is switched off |
S, SL or LS (switched line) | Line conductor after the light switch (the same wire that feeds the light) | Signal that “the light is on”, triggering the fan |
N | Shared neutral conductor | Return path |
PE (if present) | Earth conductor | Protects a metal casing |
Reference markings; each manufacturer labels them differently, so always wire according to the diagram on the fan or in the manual.
Points to remember:
You must run an additional permanent line conductor to the fan (L, S, N and PE in total).
The permanent L and the switched L must come from the same circuit and the same breaker, unless the manual allows otherwise. If they come from two circuits, switching off the lighting breaker still leaves the fan live, which is very dangerous during repairs.
The L terminal is always live, even when the switch is off. For maintenance, switch off the breaker or isolating switch and verify each terminal is dead before removing anything. Stick a warning label inside the fan’s terminal box.
If the permanent L is connected to both terminals, the fan runs forever. If the L terminal is left empty, depending on the circuit, the fan either does not run or has no overrun function.
The overrun time is set with a knob or DIP switch inside the fan; test at the shortest setting, then adjust to the client’s needs.
Real-life example: an electrician replaces an old two-wire fan with a timer fan, but only two wires run from the switch up to the ceiling. He connects the switched wire to the L terminal and leaves S empty: depending on the circuit, the fan either does not run or runs without the overrun function. The correct way is to run an extra permanent line conductor from a junction box on the same circuit up to the fan.
Note on electronic switches: touch switches, smart switches that need no neutral, and switches with locator lights usually let a small current through even when off. This current can make a timer fan “think” the light is still on so it runs forever, or make LED lights glow dimly (see the lesson on LED lights glowing dimly after being switched off). In that case, use a mechanical switch or a type the fan manufacturer approves.
Step 5: Ducting, backdraft shutters and preventing condensation
Ducting
Duct diameter equal to the fan spigot, as short as possible with as few bends as possible; every right-angle bend reduces airflow significantly.
Pull flexible duct taut, without sagging (sagging sections collect water and obstruct airflow). For long runs, use smooth rigid duct.
Connect the duct to the fan spigot with a hose clamp and aluminium tape.
The duct should slope slightly downwards towards the outside so condensation drains out rather than back to the fan.
Discharge to the outside or into a light well or ventilation shaft designed for this purpose. Do not discharge into a false-ceiling void or a closed roof space: the moisture condenses there, causing ceiling mould and rusting frames. In apartment buildings, ask the building management before drilling an outside wall.
Backdraft shutters (non-return valves)
Light flaps open by themselves when the fan blows and close when the fan stops, keeping out wind, rain, odours and insects. Many fans have a built-in flap at the spigot; the outlet on the outside wall is usually a self-closing louvred vent.
Install it in the direction of the arrow; if fitted backwards, the fan runs but no air comes out.
The flaps must open and close freely, not pressed by the duct, sealant or screws.
Do not stack several valves on a short run; each one adds resistance.
The outlet needs a rain cowl and insect mesh, with the opening facing down or sideways.

Figure 2. An outside-wall outlet vent with backdraft louvres: the louvres open when the fan blows and drop closed when the fan stops. (Photo: Antonio Mette, Wikimedia Commons, CC BY 3.0)
Condensation
Hot, humid air meeting a cold duct (a duct passing through the ceiling of an air-conditioned room, or an outside wall that is cold at night) condenses into water that drips from the fan grille. To reduce it: keep the duct short, sloping outwards and without sags; insulate sections of duct passing through cold spaces; let the fan overrun after showering so the duct dries; and make sure the backdraft shutter closes tightly.
Step 6: Step-by-step installation
Survey and agree the plan: fan type, position, control method and duct route; state the scope of work (see quoting and working with clients).
Isolate the power: switch off the bathroom circuit breaker, hang a sign and verify the circuit is dead right at the junction box.
Cut the opening using the fan’s template. Plasterboard ceilings: avoid the framing, and for heavy fans add a support batten or hanger rods. Brick walls: wear safety glasses and a dust mask, and avoid water pipes.
Run the cable in conduit to the fan, leaving just enough cable for the connections.
Mount the fan body and connect the duct before making electrical connections; tighten screws evenly so the casing is not twisted.
Connect the wires in the fan terminal box according to the diagram: strip just enough, crimp ferrules on stranded wire, tighten firmly, clamp the cable, seal the cable entry with the grommet and close the cover.
Waterproof: for wall-mounted fans, seal the gap between the duct and the wall opening on the outside. Do not block drain holes or vent slots if the manual specifies them.
Fit the front cover and filter, and clean up the area.
Step 7: Checking and test running
Before energising
Compare the wire order with the diagram (L, S if present, N, PE) and test PE continuity back to the board. Insulation testing (if you have a tester) should be done only on the circuit cables with the fan disconnected, because the test voltage can damage the timer and sensor circuits.
After energising
Item | How to check | Expected result (for reference) |
|---|---|---|
Switch breaks the line conductor | Switch off, measure the S terminal (or the L terminal on a two-wire fan) to PE | No voltage |
Permanent line (timer fan) | Switch off, measure the L terminal to N | Mains voltage still present, so it must be labelled |
Overrun function | Set the shortest time, switch the light off, time it | The fan keeps running and then switches off after the set time |
Suction | Close the door, hold a thin sheet of paper near the fan grille | The paper is sucked against the grille |
Backdraft shutter | Switch the fan off, watch the flap at the spigot or outlet | The flap closes by itself, with no air blowing back in |
Current | Clamp meter on the line conductor feeding the fan | Consistent with the power on the rating label, usually under 1 A for household fans |
Residual-current protection | Press the test button on the RCD/RCBO | Trips immediately |
Run the fan continuously for 10–15 minutes (for reference), listen for noise, and check the fan body is only slightly warm before handing over.

Figure 3. A wall-mounted fan that has collected dust on its grille and blades over time: weaker suction and more noise. The power cable in the photo is surface-run; for new installations it should be run in conduit or trunking. The brand label has been blurred. (Photo: Antonio Mette, Wikimedia Commons, CC BY-SA 4.0)
Dealing with noise, vibration and common faults
Humming, vibration transmitted to the ceiling: loose screws, casing tightened unevenly, thin plasterboard resonating. Tighten evenly, add rubber pads, and separate the duct from where it touches the ceiling.
Rattling in windy weather: the backdraft flap is banging; check for bent flaps and use an outlet with a cowl.
Squealing, noise increasing over the years: dust on the blades, dry bearings. Clean the blades and grille; a failed bearing usually means replacing the fan.
Weak suction: long duct, many bends, crushed or sagging duct, backdraft valve fitted backwards or stuck, no make-up air, dirty grille.
Water dripping: condensation, or rain getting in because there is no cowl or the duct slopes back towards the fan.
Runs forever without switching off: permanent L connected to the S terminal by mistake, an electronic switch leaking current, or the humidity sensor threshold set too low.
Does not run: no voltage on a required terminal, wired to the wrong terminal, or jammed blades causing the thermal cut-out to trip. Measure the voltage at each terminal.
RCD trips during showers: water getting into the terminal box, or a fan without a sufficient IP rating for its position. Disconnect the fan to isolate the fault (see circuit breakers that keep tripping).
When to stop and advise the client
Stop and consult someone with expertise when: the bathroom circuit has no residual-current protection and the homeowner will not agree to install it; old cables are brittle or discoloured; you would have to drill through a beam, load-bearing wall or fire-separating wall, or connect to a shared building shaft; or the fan diagram is unclear (ask the supplier — do not guess).
At handover:
Show the client how to adjust the overrun time, where the bathroom circuit breaker is and how to use the RCD test button.
Advise them to clean the grille and front cover regularly, always switching off the breaker before removing them; with a timer fan, switching off the light switch is not enough.
If the fan makes unusual noises, smells of burning or leaks water, switch off the breaker and call an electrician.
Safety checklist before handover
Power isolated, sign hung and circuit verified dead before wiring.
The bathroom circuit has 30 mA residual-current protection, and the test button trips it immediately.
The fan’s IP rating suits its position; ordinary switches and sockets are outside the bathroom.
The switch breaks the line conductor; on timer fans, L and S are from the same circuit, with an “L terminal always live” label.
Joints are in a covered box, the terminal box is sealed with its grommet; metal-bodied fans are connected to PE.
Duct is the correct size, taut, sloping outwards and discharging outdoors; backdraft shutter fitted the right way round.
Test run completed, current measured, overrun function, suction and noise checked.
Frequently asked questions
Does a bathroom extractor fan need an earth connection?
Fans with a metal body or an earth terminal must be earthed. Double-insulated fans have no earth terminal; still run the PE conductor to the junction box and insulate its end, ready for future use.
Can I discharge the fan into the plasterboard ceiling void to avoid drilling the wall?
It is not recommended. Moisture condensing in the ceiling causes mould, staining and rusting frames. The duct must lead outdoors or into a shaft or light well intended for ventilation.
Why does my timer fan keep running after the light is switched off?
Usually because the permanent line has been connected to the S terminal by mistake, or an electronic switch is leaking current through the S terminal. Measure the voltage at the S terminal with the switch off, and try replacing it with a mechanical switch.
Practice exercises
Exercise 1: Calculate and choose a fan. A bathroom of 1.8 m × 2.4 m with a 2.6 m ceiling and a 3 m duct with one bend to the outside wall. Calculate the volume and the airflow required at 8 air changes per hour, choose the rated airflow and explain whether you would choose an axial or a centrifugal fan.
Exercise 2: Practice on a training board (with an instructor): wire a light and a timer fan (or a three-terminal L, S, N model) to one switch. Switch off and verify dead; energise, measure the voltage at each terminal with the switch on and off; time the overrun function; press the RCD test button.
Pass criteria:
The switch breaks the line conductor; L and S are on the same circuit.
You correctly record the voltage at each terminal with the switch on and off.
Joints are secure, with ferrules, the terminal box is sealed, and there is a warning label for the L terminal.
You can explain the fan position, make-up air and how to route the duct to prevent condensation.