“The bedroom light is switched off but it's still glowing faintly, and in the middle of the night it even flashes.” Since homes switched to LED lighting, electricians get this kind of call more and more often. The old incandescent bulbs almost never did this. LED bulbs are different: the driver inside needs only a tiny current to make the LED chips glow dimly, or it slowly charges a capacitor and then flashes periodically.
A light that glows dimly when switched off is sometimes just an annoyance, and sometimes a sign of danger: the switch is breaking the neutral wire, so the lamp holder is still live even though the switch is off. Someone changing the bulb who believes “it's off, so it's safe” can get an electric shock.
This lesson belongs to the “Troubleshooting common electrical faults” step. By the end of this lesson, you will be able to tell normal behavior from a fault, determine whether the switch breaks the phase (live) or the neutral, recognize “ghost” voltage when measuring, choose the right fix, and know when to call a more experienced electrician.
Safety before you start
Every job that involves removing a switch, opening a junction box or reconnecting wires is done with the power off:
Switch off the circuit breaker (MCB) for the lighting circuit (if unsure, switch off the main breaker) and hang a “Work in progress, do not switch on” sign.
Test your measuring instrument on a known live source before and after measuring, to make sure it still works.
Only touch anything once you have measured and confirmed that every wire in the box is dead, because other circuits may pass through the switch box.
Never make connections while the circuit is live. Some measurements in this lesson must be made with power on: use only insulated test probes, keep your hands dry, stand on a dry surface, do not touch metal parts, and only do it once you have been trained; if you are not confident, let the lead electrician take the measurement.
Normal or faulty?
Fades over a few seconds and then goes completely dark: the capacitor in the LED driver is discharging. This is usually normal.
Steady dim glow: a small current is still flowing through the lamp even though the switch is open.
Periodic flashing (once every few seconds or few tens of seconds): a small current gradually charges the capacitor in the driver; when it reaches the threshold the circuit starts up, the lamp flashes, the capacitor discharges completely and then charges again.
The last two mean the lighting circuit is not truly isolated when switched off. Your job is to find which path that small current is taking.
Seven common causes
1. The switch is on the neutral wire
A switch must break the phase (live) wire. If it is wrongly wired on the neutral, the light still goes off because the circuit is open, but the phase goes straight to the lamp, so the driver and lamp holder are always live. Through the capacitance of the wire run from the lamp back to the switch, between the driver and the lamp housing or ceiling, or through damp insulation, a very small current can still complete a circuit, enough to make a sensitive LED bulb glow faintly. This fault must be dealt with first because it is dangerous when changing bulbs.
2. Induced voltage from long parallel wire runs
Two wires lying close together in the same conduit or cable act like the two plates of a small capacitor (capacitive coupling). When the switch is off, the switched wire to the lamp is no longer connected to the phase but still runs alongside a live phase wire. The longer the shared run, the larger the coupled current: an incandescent bulb does not react, but a low-power LED driver may. This is common with garden lights, gate lights and two-way stair lighting.
3. Switches with indicator lights or glow-in-the-dark markers
The small indicator light on a switch (LED or neon) is usually connected in parallel across the two switch terminals. When the switch is off, current flows through the indicator, then through the bulb to neutral: an incandescent bulb is unaffected, but an LED bulb may glow faintly. Signs: the switch shows a glowing dot when off, and the problem started after changing to LED.

Figure 1. A switch with an indicator light: the rocker glows blue thanks to the light inside, making it easy to find in the dark. Indicators like this usually draw power by passing a small current through the bulb, which can make an LED lamp glow dimly. (Photo: Mikewarbz at en.wikipedia, Wikimedia Commons, CC BY-SA 3.0)
4. Touch switches and smart switches without a neutral wire
Touch and smart switches of the “single-wire” type (only a phase in and a switched wire out to the lamp) need power for their electronics. When the light is off, they get it by passing a small current through the bulb itself, so manufacturers usually state a minimum load. A small LED bulb below that level will glow, flash, or make the switch behave erratically. The same happens with two-wire dimmers used with incompatible LED bulbs.
5. An over-sensitive LED driver
Cheap LED bulbs often use simple drivers whose start-up circuit needs very little energy. On the same circuit, one bulb goes completely dark while another glows faintly. The bulb is not the root cause, but changing it is sometimes enough to stop the problem.

Figure 2. An LED driver with its casing removed: a small circuit board with a capacitor, a yellow coil and semiconductor components. A circuit with a filter capacitor like this can slowly accumulate leakage or induced current and then make the lamp flash. (Photo: Dmitry G, Wikimedia Commons, CC BY-SA 3.0)
6. Leakage due to damp or poor insulation
A switch box with water ingress, an outdoor light that is not sealed, peeling tape on joints, or old wires with cracked insulation create a small leakage path from the phase to the switched wire to the lamp. Signs: worse after rain or in the humid season; stains or rust in the box. This is also a short-circuit, fire and shock hazard, and must be fixed at the source.
7. Wiring errors: two-way switches, shared neutrals, a lamp in series with another load
Two-way switches wired incorrectly. The correct circuit: phase to the common terminal of the first switch, the common terminal of the second switch up to the lamp, and two strapping (traveler) wires connecting the remaining terminals. Running the neutral through the switches means that in some positions the lamp is off but still has phase present. Even when wired correctly, when the light is off one strapper is always live and runs next to the other, so long strappers easily cause induction.
Borrowing a neutral from another circuit. This makes the current path hard to trace and can cause an RCD/RCBO to trip for no apparent reason; separate them so that each circuit has its own phase–neutral pair.
A lamp in series with another load. In a junction box, the neutral end of lamp A has been mistakenly connected to the switched wire of lamp B. With A on and B off, current flows through A, then through B to neutral: both glow dimly. Sign: the lamp only glows dimly when another switch is turned on.
Measuring correctly: when the meter says “live” but it is not
Tools: a test screwdriver (voltage tester); a multimeter for AC voltage, ideally with a low-impedance (LoZ) mode; a loaded test lamp (a holder with an incandescent bulb, leads with insulated clips); insulated screwdrivers and colored tape for marking wires.

Figure 3. A screwdriver-type voltage tester: the clear body contains a small neon bulb that lights up when the tip touches a live wire. It can also glow faintly on a wire that only carries induced voltage, so never use the tester alone to draw a conclusion. (Photo: August Geyler, Wikimedia Commons, CC BY-SA 4.0)
An ordinary digital multimeter has a very high input impedance, so it draws almost no current from the circuit. When you measure an open-circuit wire lying next to a live phase wire, the tiny coupled current is still enough for the meter to show a significant figure, sometimes several tens of volts or more (guideline, depending on wire length). This is ghost voltage: it appears on the screen but cannot supply current, and drops to almost 0 as soon as a small load is connected. Neon testers and non-contact testers also need very little current, so they can light up on such a wire too.
How to confirm:
LoZ mode (if the meter has it): the meter places an internal load across the input, so ghost voltage drops sharply while real voltage stays the same. According to manufacturers' instructions, this mode draws current from the circuit, so measuring between phase and earth may trip an RCD/RCBO, and it should not be used on sensitive electronic circuits.
Without LoZ: measure again with the test lamp connected across the same two points. Real voltage makes the incandescent bulb light normally; ghost voltage does not.
Conclusion: large reading in normal mode, near 0 with a load → induction; both close to mains voltage → real voltage.
Conversely, when you need to confirm that a wire is dead before touching it, do not rely on a single check where the tester does not light. Measure with a meter between every pair of wires and from each wire to earth.

Figure 4. A typical general-purpose digital multimeter. This type usually has no LoZ mode, so it easily shows ghost voltage on open-circuit wires; to be sure, measure again with a load. (Photo: K.Venkataramana, Wikimedia Commons, CC0; the brand logo on the front has been blurred)
A 6-step procedure for finding the cause
Step 1. Ask and observe
When did it start (after fitting LED bulbs, installing a new switch, after rain)? One light or several? Is it related to turning on another light? Note the switch type, bulb type and the distance from the switch to the lamp.
Step 2. Try a different bulb
Switch off the MCB and temporarily fit an incandescent or halogen bulb (if the fitting allows) or a different type of LED bulb. Switch the MCB on, turn the light switch off and watch in the dark:
The incandescent bulb stays dark but the original LED glows → a small current is flowing through the lamp; go to step 3.
The incandescent bulb also glows clearly → the current is fairly large; think immediately of a lamp in series with another load or serious leakage; switch off and inspect the junction box.
Step 3. Check which wire the switch breaks
The simplest way: turn the switch on (light on) and measure each switch terminal against earth or against a neutral wire you have positively identified. If the switch is on the phase, both terminals show mains voltage; if it is on the neutral, both terminals read close to 0 V. If the house has no earth wire, use a voltage tester as an extra reference: with the switch on, the terminal connected to phase makes the tester light brightly, while neither terminal lighting is a sign that the switch is on the neutral. You can cross-check at the lamp with the switch off: if one of the lamp wires still has real mains voltage (which stays when measured in LoZ mode or with a load) → phase is present at the lamp, so the switch breaks the neutral or the two-way circuit is miswired. If one end is ≈ 0 V and the other has only ghost voltage → the switch correctly breaks the phase; the cause is induction, an indicator light, a single-wire switch or the driver.
Removing the switch plate to get the probes in while the circuit is live is risky; if you have not been trained, leave it to the lead electrician.
Step 4. Rule out the switch
Switch off, confirm the circuit is dead, take a photo and mark the wires, then remove the switch. For switches with indicators, touch switches or smart switches: temporarily replace with an ordinary mechanical switch with no indicator. Switch the power back on and turn the light switch off:
The glow is gone → the switch is the culprit.
Still glowing → the small current comes from the wiring: induction, leakage or a wiring mistake.
Step 5. Narrow it down to the wiring
Switch off, open the junction boxes and look for damp or rusty joints, peeling tape, or wires from two circuits joined together. Measuring insulation resistance requires a dedicated insulation tester (megger), and all lamps and electronic devices must be disconnected first; if you have not been trained, hand it over to an experienced electrician. If the insulation is good and there is no wiring mistake, but the switched wire to the lamp runs in a long conduit alongside a phase wire, or is a two-way strapper, induction is the most likely cause.
Step 6. Repair, re-check and write a report
Switch on, turn the light switch off and watch in the dark for a few minutes (periodic flashing may take a while to appear), then measure again in LoZ mode or with a load. Write down for the customer the cause, the repair and the result.
Quick reference table: symptom – likely cause – how to check – how to fix
Symptom | Likely cause | How to check | How to fix |
|---|---|---|---|
Fades for a few seconds after switching off, then goes completely dark | Capacitor in the driver discharging | Watch whether it goes fully dark | Usually normal |
Steady faint glow, ordinary switch, lamp holder live when off | Switch on the neutral | Switch on, both terminals ≈ 0 V to earth; or LoZ reading at the lamp still at mains voltage when off | Switch off, rewire so the switch breaks the phase |
Periodic flashing, lamp far from the switch, long shared conduit | Induced voltage | Large reading in normal mode, near 0 V in LoZ/with load | Anti-glow capacitor in parallel with the lamp; a less sensitive bulb; sensible wire routing in new installations |
Glowing since switching to LED, switch has a lit dot | Switch indicator passing current through the bulb | Temporarily fit an ordinary switch and the glow stops | Change to a switch without an indicator or one whose indicator uses the neutral; or the manufacturer's anti-glow capacitor |
Single-wire touch/smart switch, lamp flashing, switch erratic | Load below the minimum | Compare total lamp wattage with the manufacturer's instructions | Manufacturer's bypass capacitor, increase the load, or use a model with a neutral wire |
Worse after rain, outdoor light | Leakage due to damp | Open the box and look for damp and rust; insulation test (electrician with the right instrument) | Dry out, replace joints, boxes and fittings with a suitable waterproof rating; test the RCD |
Only glows when another light is switched on | Lamp in series with another load | Switch the other switches on and off one by one; inspect the junction box | Rewire: each lamp connected directly to the neutral of its own circuit |
Two-way circuit, glows only in certain switch combinations | Miswired two-way or long strapper wires | Try all 4 combinations, measure phase at the lamp in each one | Rewire to the standard diagram; if it still happens when correctly wired, treat as induction |
How to fix each cause
Rewire so the switch breaks the phase wire
Switch off the MCB, confirm the circuit is dead and mark the wires. Rewire so that: phase → switch → lamp; neutral goes straight to the lamp. Measure again: with the switch off, the lamp has no real voltage. If the whole house is affected, suspect reversed phase and neutral at the distribution board; it must be checked from the board.

Figure 5. The switch is pulled out of the wall opening to check the wires connected to the two brass screws. Only remove, mark and reconnect wires after switching off the MCB and confirming by measurement that the circuit is dead. (Photo: Kurtkaiser, Wikimedia Commons, CC0)
Fitting an anti-glow capacitor
For induced voltage, indicator lights or single-wire switches, the common fix is to connect a component in parallel with the lamp (between the switched wire and neutral, fitted at the lamp). The small current then bypasses through this component instead of charging the LED driver.
Prefer the switch manufacturer's own accessory (bypass or compensation capacitor). If you use a separate capacitor, it must be a class X2 safety capacitor designed for mains use, with a suitable voltage rating, placed in a sealed box or inside the light fitting, with insulated connectors. Use the capacitance value the manufacturer recommends; the figures commonly seen on the market (around a few tenths of a microfarad) are for reference only.
Do not use ordinary capacitors, electrolytic capacitors or capacitors salvaged from old equipment; do not improvise a resistor as a dummy load, because it can heat up continuously.
Never connect a capacitor in parallel with the switch: that passes more current through the lamp and makes the problem worse.
Replacing the switch, choosing the bulb
Switch with an indicator: change to an ordinary switch or one whose indicator is powered from the neutral wire (if the box has a neutral).
Single-wire smart switch: with small loads, fit the manufacturer's bypass capacitor or choose the version with a neutral wire. In new installations, run a neutral to the switch box in advance.
Dimmers: use models the manufacturer states are LED-compatible, with bulbs marked “dimmable”.
Bulbs and drivers: test them on that actual circuit and note which types do not glow; choose drivers with the right wattage and a clear origin.
Sensible wire routing and dealing with leakage
In new installations: keep the phase and neutral of the same circuit together, avoid running the switched wire to a lamp in very long parallel runs with the phase of another circuit, and limit excessively long two-way strapper wires. When there is leakage: dry out, replace joints, boxes and wires with cracked insulation, use outdoor fittings with a suitable waterproof rating, then press the TEST button on the RCD/RCBO. For tracing leakage across the whole house, see the lesson “Electricity bill unusually high: checking the meter and tracing current leakage in the home”.
Three real-life cases
Bedroom, ceiling-mounted light. The homeowner replaced a compact fluorescent bulb with an LED, and since then the light has glowed faintly all night. With the switch on, both terminals measure close to 0 V to earth: the switch is on the neutral. The electrician switches off, rewires at the junction box in the ceiling, and measures again: no phase at the lamp when off. The glow is gone, and the homeowner can now change bulbs safely.
Gate light far from the house. The LED flashes every few tens of seconds. Measuring at the lamp: normal mode shows several tens of volts, LoZ near 0 V; the wire shares a conduit with the garden socket circuit. The electrician fits an X2 anti-glow capacitor, as recommended by the manufacturer, in the lamp's junction box, and the flashing stops.
Staircase, single-wire touch switch. A small LED bulb flashes when off; the switch instructions state a minimum load higher than the bulb's wattage. The electrician fits the manufacturer's bypass capacitor at the lamp.
Safety checklist
The correct MCB is switched off and a “Work in progress” sign is in place.
The measuring instrument was tested on a live source before and after measuring.
Every wire in the box was confirmed dead before touching.
Live measurements: insulated probes, dry hands, dry standing surface, no contact with metal parts.
No conclusions based on the voltage tester alone; cross-checked with a meter in LoZ mode or with a load.
The switch always breaks the phase wire; reconfirmed after the repair.
Anti-glow capacitor of the correct X2 type, as recommended by the manufacturer, with fully insulated connections.
No bare wire ends; all switch plates and junction box covers refitted; RCD/RCBO tested (if fitted).
Call a more experienced electrician when: you have not been trained in live measurement; the junction box is a tangle with several circuits sharing a neutral; an incandescent bulb also glows; there are signs of leakage, burning or a burning smell; you suspect reversed phase and neutral at the distribution board.
Frequently asked questions
Does an LED glowing dimly when off waste electricity?
The current that causes the glow is usually very small, so the energy used is negligible. What matters is the cause: a switch breaking the neutral or current leakage is a safety problem.
Does flashing when switched off make the bulb fail sooner?
There is no general figure; it depends on the type of bulb. Do not wait to see whether the bulb fails; find and fix the cause.
Can I fit an anti-glow capacitor myself?
Only if you have been trained in electrical connections, isolate the power following the correct procedure, and use the correct X2 safety capacitor as recommended by the manufacturer. Prefer genuine manufacturer accessories. Never connect the capacitor in parallel with the switch.
Can I switch to an incandescent bulb to stop the glow?
An incandescent bulb does not react to small currents, so the glow will stop, and this is a very good diagnostic test. But if the switch is breaking the neutral, the lamp holder is still live when off; changing the bulb only hides the fault and does not make the circuit any safer.
Practice exercises
On a practice board with an MCB, an RCD and an instructor supervising, wire an LED lighting circuit with the switch breaking the phase, then rewire it with the switch breaking the neutral. In both cases, measure the lamp holder with the light off using a voltage tester, a meter in normal mode and in loaded mode; record a comparison table.
Run two long wires through the same conduit: one connected to the phase, the other open at one end. Measure the open wire in normal mode and in LoZ mode (or with a test lamp), and record the difference.
Wire a two-way switch circuit to the correct diagram, try all 4 switch combinations and measure phase at the lamp in each one.
Write a one-page report for the gate-light case: symptoms, measurements, conclusion, repair, and re-check results.
Self-assessment criteria — you pass when:
You never touch any wire before switching off and confirming by measurement that it is dead.
You can distinguish real voltage from induced voltage using at least two measurement methods.
You correctly identify whether the switch breaks the phase or the neutral in every test.
You can explain why an anti-glow capacitor is connected in parallel with the lamp and not in parallel with the switch.
After this lesson, review one-way and two-way switch wiring in the “Installing lighting circuits, switches & sockets” step, and add questions about induced voltage and switches breaking the neutral to your revision for the “Safety checks & wiring exam” step.