“The house is finished, and now I want an extra socket next to the bed without chasing the wall.” “I've just rented a shop and the landlord won't let me cut into the walls.” For jobs like these, the fast, clean and easy-to-repair method is surface wiring in PVC trunking.
Trunking looks simple, but whether it looks neat or messy, lasts or peels off, is safe or not comes down to details: a trunking size that suits the number of cables, a straight route, tight corners, screws in the right places, no joints in the middle of the trunking run, and testing before switching the power on.
This lesson belongs to the “Installing lighting circuits, switches & sockets” step. By the end of this lesson, you will be able to plan the job yourself, work out the materials and install a trunking run in 7 steps.
Safety first: Any work that touches wiring must be done with the circuit breaker (MCB) switched off, a warning tag hung, and a test confirming the circuit is dead. Review the 5 mandatory safety rules before touching any electrical wire before you start.
When to use surface trunking, and when not to
Surface wiring in trunking is suitable when:
The house is already finished and the client wants extra sockets, switches or lights without chasing, re-plastering and repainting.
Rented homes, shops or offices need a quick installation that can be removed when the premises are handed back.
Old concealed wiring is damaged and cannot be pulled out, so a replacement route is needed.
Do not use ordinary PVC trunking, or switch to another solution, when:
The area is wet or often splashed (shower areas, around sinks, uncovered drying yards): trunking is not watertight. You need boxes and devices with a suitable water-protection rating (check the IP rating), sealed conduit and 30 mA residual current protection.
Outdoors in direct sunlight: indoor trunking plastic easily becomes brittle and cracks. Use conduit and fittings clearly marked for outdoor use and UV-resistant.
Close to heat sources: next to a gas hob, behind an oven.
Large loads (induction hobs, water heaters, air conditioners): surface wiring is still possible, but you must run a dedicated circuit with cable sized for the load, not “conveniently” branch off the nearest socket.
PVC trunking: construction, types and fittings
Electrical trunking (square trunking, plastic cable duct) consists of a U-shaped base fixed to the wall and a cover that clips onto both edges of the base, hiding the cables and protecting them from knocks.

Figure 1. Construction of cable trunking: number 1 is the cover, number 2 is the U-shaped base fixed to the wall. (Image: Leotard, Wikimedia Commons, Public domain)
Common types of trunking
Square (rectangular) trunking: the most common type, used on walls and ceilings. Sizes are usually named by outside dimensions (for example “14 trunking”, “24x14 trunking”), and each brand has its own table; for calculations you must measure the actual internal dimensions with a caliper.
Compartmented trunking: separates power cables from network, TV antenna and camera cables.
Half-round (floor) trunking: a curved profile that covers cables running across the floor where there is little foot traffic; it does not replace wall trunking for long fixed runs.
When buying, prefer trunking clearly marked as flame-retardant / self-extinguishing PVC with stated dimensions. Thin, brittle trunking cracks easily when screwed.
Fittings: angles, tees and end caps
Manufacturers usually offer fittings for each trunking size: flat angles (turning on the same wall surface), internal angles, external angles (going around a projecting wall corner), tees (branching), straight couplers and end caps. Fittings make joints tight and tidy. If there are no fittings of the right size, electricians cut 45° mitres on the trunking itself (see Step 3).

Figure 2. A trunking run using tee and angle fittings at branches and changes of direction. (Image: Leotard, Wikimedia Commons, Public domain)
Tools and materials
Tools:
Voltage tester pen and multimeter (see how to use a multimeter to measure voltage, test continuity and find the live wire); a detector for concealed cables and metal, if available.
A drill with hammer mode, masonry bits matching the wall plug size.
Tape measure, spirit level or laser level, pencil, masking tape.
Fine-toothed hacksaw, 45° mitre box, utility knife, file or sandpaper.
Insulated screwdrivers, wire strippers, side cutters, crimping pliers.
A sturdy A-frame ladder, safety glasses for drilling.

Figure 3. Wire strippers with a size-adjusting screw (left) and side cutters with a stripping notch (right). (Photo: Petar43, Wikimedia Commons, CC BY-SA 4.0)
Materials:
Trunking and fittings of the right size; buy about one extra length to allow for cutting mistakes.
Plastic wall plugs and matching screws. Double-sided tape is only an aid and does not replace screws on long runs.
Cable of the correct cross-section, colour-coded for live, neutral and earth (green-yellow). Colour conventions may differ between jobs; what matters is that they are consistent throughout the house and recorded.
Surface back boxes, sockets, switches, lidded surface junction boxes; crimp lugs, connectors or terminal blocks.
Choosing cable size and trunking size
Cable: sized by load and breaker, not by trunking size
The cable cross-section is chosen according to the load current, the length of the run and the circuit breaker protecting that circuit. The detailed method is in the lesson how to choose cable cross-section and circuit breakers for each circuit in the home. One principle to remember with surface wiring: a new branch must not be smaller than what that circuit's breaker can protect. Do not branch off with thin cable just because “the new socket is only for a charger”: later the client may still plug an iron or a heater into it.
On cable type: double-insulated (sheathed) cable withstands knocks and scratches better. Single-insulated wires should only be laid in closed trunking with a firmly clipped cover; in low positions prone to knocks, or where children might pry the cover off, prefer sheathed cable.
Trunking: calculate the fill, do not overstuff
Overstuffed cables dissipate heat poorly, the cover pops off easily, and pulling in extra cables later easily scratches the old ones. A quick calculation:
Measure the outside diameter of one cable with a caliper (including the sheath); call it d (mm).
Area of one cable ≈ 0.785 × d × d (mm²).
Measure the inside of the trunking (internal width × internal height) and multiply to get the internal area.
The total area of all cables should not exceed about 40–45% of the internal trunking area (reference, as recommended by many installation guides; also read the trunking manufacturer's instructions).
Example: 3 wires (live, neutral, earth), assuming d = 4 mm (an assumed figure for practice; measure the real cable). One wire ≈ 0.785 × 4 × 4 ≈ 12.6 mm²; three wires ≈ 38 mm². An internal trunking size of 16 × 8 mm = 128 mm²; 40% is about 51 mm². 38 < 51, so it fits. If another circuit is added later (total ≈ 76 mm²), it will not be enough, so choose a larger size from the start.
Surface wiring with trunking: the 7-step procedure
Step 1. Survey, plan and isolate the power
Ask the client: what they want to add, where, and which appliances they will use (to work out the load). Take photos of the existing condition.
Decide on the supply point: from the distribution board (a new circuit with its own breaker, best for large loads) or a branch from an existing socket or junction box (only if that circuit still has enough capacity and the old wiring is in good condition).
Sketch the route: start point, end point, turns and length; from that, draw up the materials list.
Before making any connections: switch off the breaker for the relevant circuit, hang a warning tag and test to confirm it is dead; check your tester on a live source before and after testing.
Step 2. Mark out a straight, tidy route that avoids obstacles
A neat trunking run is vertical or horizontal, parallel to the ceiling line, door frames and skirting boards. Do not run diagonally to “save cable”: it looks bad and the next person cannot guess where the cable is when drilling.
Prefer running along the ceiling corner, just above the skirting board or around the door frame so the trunking blends into existing outlines.
Use a spirit level or laser to draw a faint pencil line along the edge of the trunking.
Mark the positions of socket and switch back boxes, turns and junction boxes.
Scan for concealed cables and pipes before marking drilling points: avoid drilling directly above or below existing sockets and switches and around areas with water pipes (behind washbasins, toilets, water heaters). In many houses concealed wiring does not run in straight lines; a detector only reduces the risk and gives no absolute guarantee.
Keep power trunking apart from network and antenna trunking, or use compartmented trunking.

Figure 4. A white PVC trunking run going straight across the ceiling, carrying the supply cable to a light fitting. (Photo: Dmitry G, Wikimedia Commons, CC BY-SA 3.0)
Step 3. Measure, cut the trunking and make the corners
Measure directly on the wall, adding the length that fits into the fittings if you use them.
Cut the base and cover separately. Stagger the cover joints relative to the base joints so the cover is less likely to pop off.
For corners without fittings: place the trunking in a mitre box and saw along the 45° slot so the two ends join into a tight right angle. For internal and external corners: cut away part of the base wall at the bend so the cables pass through without being pinched, then cut the cover at a 45° angle.
Use a file or sandpaper to remove burrs from every cut. Sharp plastic edges can easily slice cable insulation.

Figure 5. A wooden mitre box with 45° and 90° slots, helping you saw trunking straight and at the right angle. (Photo: Rasbak, Wikimedia Commons, CC BY-SA 3.0)
Step 4. Drill and fix the trunking base
Hold the trunking base on the marked line and mark the screw holes. Space the screws about 30–50 cm apart, with extra screws near both ends of each length and on both sides of every corner (reference; for large trunking, heavy cables or ceilings, fix more closely).
Pre-drill the trunking base with a small bit first; do not drill straight through the trunking with a large bit, as the plastic cracks easily.
Drill the wall to the wall plug size, slightly deeper than the plug, blow out the dust and tap the plug in flush with the wall surface.
Tighten the screws just enough: the screw head should press the base flat, not so tight that the base dents or cracks. Screw heads must not stick up and foul the cover or cut into the cables.
Double-sided tape only helps hold the line straight while screwing; tape alone will peel off over time.
Step 5. Lay the cables in the trunking
Pull the cables according to the plan, leaving enough spare at each end for connecting and for re-cutting once if needed.
Cables lie flat inside the trunking, not twisted and not repeatedly crossing over each other.
At corners, bend cables in a smooth curve, never a sharp fold.
Never join cables in the middle of a trunking run. Every joint must be inside a socket back box, switch back box or lidded junction box with enough space that can be opened for inspection.
Power cables and signal cables (network, antenna, camera) go in separate compartments or separate trunking.
Step 6. Fit the surface boxes, connect and close the cover
Fix the surface box firmly to the wall and butt the trunking end tightly against, or into, the knockout of the box, leaving no exposed cable.
Strip just enough insulation for the terminal; crimp lugs onto stranded wire. Connect live, neutral and earth correctly; if the socket has an earth terminal, the green-yellow wire must be connected. For switches, switch the live wire, never the neutral.
Branching from an existing socket: connect at the socket terminals or with a connector or terminal block in a box; each terminal only takes the number of wires the manufacturer allows. Tug-test each wire.
Fit the cover starting from one end, pressing evenly until you hear it click. A section that will not clip on is usually caused by a protruding cable or a high screw head: open it and fix it, do not force it.
Step 7. Test, energise and hand over
Before switching the power on:
With the power off, use the multimeter on the continuity range to check: no short between live and neutral or live and earth; the earth wire is continuous from the new socket back to the earthing point.
If you have an insulation resistance tester (megger), disconnect all electronic devices, LED lights and power supplies from the circuit before testing, as the test voltage can damage them. For 220 V circuits, many references use a minimum of about 1 MΩ when testing at 500 V DC (reference; check against the current standard).
After switching the power on:
Measure the voltage at the new socket between live and neutral and between live and earth; compare with other sockets in the house (Vietnam's supply is 220 V/50 Hz).
Use the tester pen: only the live slot should light. When the switch is off, the light goes completely off, not dimly lit.
If the circuit has a residual current device (RCD/RCBO), press the TEST button to make sure it trips.
Plug in a real load for a few minutes and check that the socket face and connections are not unusually warm.
Clean up the dust, photograph the trunking run, and note which breaker the circuit comes from and which cable was used. Tell the client not to hang things on, or nail into, the trunking.
Reference table: parameters and checks for trunking work
Item | Reference value / method | How to check |
|---|---|---|
Cable fill in trunking | Total cable area about 40–45% of the internal trunking area or less (reference) | Measure cable d and trunking interior with a caliper, calculate as in the example |
Screw spacing for the trunking base | About 30–50 cm, with extra screws near the ends of each length and on both sides of corners (reference) | Press along the trunking: no rocking, no sagging |
Cable joints | Only inside back boxes or lidded junction boxes; never mid-trunking | Open the trunking cover: only continuous cable along the whole length |
Continuity before energising | No short between live and neutral or live and earth | Multimeter on continuity range, power off |
Insulation resistance | Meets the applicable standard; many references use about ≥ 1 MΩ at 500 V DC for 220 V circuits (reference) | Insulation tester, with electronic devices disconnected |
Voltage after energising | Equivalent to other sockets in the house | Multimeter on AC V range |
Residual current protection | RCD/RCBO trips when TEST is pressed | Press the TEST button on the device |
Worked example: adding a bedside socket with trunking from an existing socket
Situation: a second-floor bedroom; the client wants a double socket at the head of the bed for chargers, a bedside lamp and a fan. The existing socket is in the corner of the room, about 3 m away along the wall, close to the floor. The walls are painted and the client does not want them chased.
Survey: switch off the breaker, test dead, open the existing socket: the wires in the back box are still flexible, not discoloured, and there is an earth wire. The room only has a TV, a fan and chargers; the distribution board has a breaker and residual current protection dedicated to the bedroom circuit. Conclusion: branching from this socket is acceptable.
Plan: the trunking runs horizontally just above the skirting board; below the new position it turns upward with a flat angle to a surface box at the height the client chose (level with the top of the bedside table). Three wires of the same type and cross-section as the existing circuit. Materials: 2 lengths of trunking, 1 flat angle, 1 end cap, 1 surface box, 1 earthed double socket, about 4 m of wire in each colour, wall plugs and screws.
Installation and testing: mark the line with a laser, scan the wall around the old socket, fix the trunking base every 40 cm or so with extra screws on both sides of the angle. At the old socket, crimp each pair of same-colour wires into a shared lug and fix it in the terminal (following the socket manufacturer's instructions), and tug-test each wire. Fit the cover with joints staggered from the base joints. Test continuity, switch on, measure voltage, press TEST on the RCD, run the fan for 15 minutes, then feel both the old and new sockets to check they are not warm. Finally, note on the client's house diagram: “Bedside socket branched from the corner socket, second-floor bedroom circuit”.
Common mistakes with trunking
Joining cables mid-trunking and wrapping them in tape: they heat up easily and are very hard to find when they fail.
Only sticking with tape, no screws: a few months later the trunking peels off and the cables are exposed.
Over-tightening screws or stuffing in too many cables: the base cracks and the cover pops off.
Running diagonally or in curves: it looks bad, and someone drilling to hang a picture can easily hit the cable.
Safety checklist
I switched off the correct breaker, hung a tag and tested to confirm it is dead (tester checked on a live source before and after).
I scanned for concealed cables and pipes before drilling; I wore safety glasses while drilling.
The ladder is sturdy; I did not stand on swivel chairs or plastic chairs.
The new branch has a cable size suited to the breaker protecting the circuit; large loads have their own circuit.
There are no joints in the middle of the trunking.
Correct colours and polarity: switches break the live wire; sockets with earth have the green-yellow wire connected.
I tested continuity and insulation (if I have the tester) before energising.
I measured voltage after energising, pressed TEST on the residual current device, tested under load and checked for heat.
I did not use ordinary PVC trunking in wet areas, in direct sun or near heat sources.
Stop and call an experienced electrician when: the old wiring is brittle or discoloured; the house has no residual current protection; you need to run a new circuit from the distribution board and have never done it; or you are unsure at any step.
Frequently asked questions
Is surface wiring in trunking as safe as concealed wiring?
Done correctly, surface wiring in trunking is safe for homes: the cables are insulated, the trunking protects them, and the circuit has a breaker and residual current protection. The advantage is that it is easy to inspect and repair; the disadvantage is that it is more exposed to knocks and accidental nailing, so you must choose sensible positions and screw it firmly.
Can I use double-sided tape instead of screws?
On short runs on flat, clean walls, tape will hold for a while, but heat, humidity and paint dust gradually weaken it. Use screws; tape is only an aid.
Can I branch off an existing socket?
Yes, if that circuit still has enough capacity, the old wiring is in good condition, the new branch uses cable no smaller than the circuit's cable, and the joints are inside a lidded box. Do not branch for large loads such as water heaters, heaters or air conditioners: run a dedicated circuit from the distribution board.
Can power and network cables share the same trunking?
It is not recommended. Use compartmented trunking or two separate runs, for safety when someone else works on the network cables and to reduce signal interference.
Can I paint the trunking to match the wall?
Yes, using a paint that adheres to plastic once the cover is in place. Paint may stick the cover to the base, making it harder to open next time.
Practice exercises
Choose a room in your home and draw a trunking plan to add one socket: supply point, route, corners and length; draw up a materials list.
Measure the outside diameter of the cable you plan to use and the interior of two trunking sizes; calculate the fill for one 3-wire circuit and for two circuits sharing the trunking.
On a practice board (not connected to power): install a trunking run with one flat 45° mitred corner, one internal corner and one tee; screw it, lay the cables and close the cover tightly.
On a training board with a breaker and RCD, supervised by an instructor: connect an earthed surface socket at the end of the run, test continuity, energise, measure voltage and press TEST.
Self-assessment criteria — you pass when:
You never touch a wire before switching off the power and testing to confirm it is dead.
The trunking run is straight, corners are tight, no cable is exposed, and it does not rock when pressed along its length.
There are no joints mid-trunking; live, neutral and earth are correct; tugged wires do not come loose.
You can explain why large loads must not be branched from an existing socket.
Related lessons to study next: installing two-way switches and earthed sockets correctly and quoting, taking on jobs and working with clients as a residential electrician.