A client calls: "We've just bought a double induction cooktop and were going to plug it into the socket next to the kitchen cabinet where the rice cooker is plugged in. Could you check whether we need a separate cable?" The answer is almost always yes. Induction and infrared cooktops are among the biggest loads in the home and run continuously for tens of minutes; wire them wrongly and the socket melts, the breaker trips in the middle of cooking, or worse, a fire starts inside the kitchen cabinet.
By the end of this lesson, you will be able to work step by step from reading the rating plate and calculating the current, through choosing the cable and circuit breaker, wiring and earthing, to the test run and advising the client.
The manufacturer's installation manual is the highest authority; the figures in this lesson are for reference only, and where they differ, follow the manual and current regulations. Before touching any wire, switch off the circuit breaker and check that the circuit is dead according to the 5 mandatory safety rules. Never open the cooktop casing to repair the circuit board yourself: inside there are capacitors that may still hold a charge after the power is disconnected, and opening the casing usually voids the warranty.
How do induction and infrared cooktops differ electrically?
Induction cooktops
An induction cooktop drives a high-frequency current through a copper coil under the glass; the magnetic field makes the base of a magnetic pan heat up by itself. The cooktop has a power circuit board, so it has a cooling fan and needs ventilation gaps. Electricians should remember:
When the voltage is low, many induction cooktops still try to maintain the selected power, so the current increases; some cooktops reduce power automatically or show a voltage error.
The cooktop has power electronics, so any leakage current may not be a pure sine wave. That is why many manufacturers state a specific type of residual current protection (see Step 2).
Infrared cooktops
An infrared (radiant) cooktop uses heating elements (resistance wire or halogen lamps) under the glass. It is an almost purely resistive load, switched on and off in cycles to hold the heat setting. The glass gets very hot and stays hot long after switching off. If the supply is weak, the lights in the house may flicker slightly in time with the switching.
On cooktop sizes: a single countertop unit is usually around 2,000 W, a double unit around 3,000–4,400 W, and a built-in 3–4 zone hob can exceed 6,000 W (all for reference; always read the rating plate). Many European models have terminal blocks for several configurations (single-phase, two-phase, three-phase) and must be wired exactly as the manual says.
Step 1: Read the rating plate and manual before buying materials
The rating plate is usually on the underside of the cooktop body and reprinted in the manual. Record in your survey notebook:
Total power (W, kW), the most important figure for choosing cable and breaker. Don't add up the individual zones yourself when the plate gives a total.
Voltage and number of phases, or the permitted wiring configurations.
Supply connection method: comes with a plug (and what amp rating the plug has) or only a flying lead or terminal block for hard-wiring.
Protection requirements: breaker rating, type of residual current protection, cable size recommended by the manufacturer.
Countertop cut-out dimensions, ventilation gaps and minimum clearances from the manual.

Figure 1. The supply terminal block of a European electric cooker: the bridges (wires in white sleeving) select single-phase or multi-phase configuration, and the label below shows each diagram. Cooktops with this kind of terminal block must be wired to the single-phase diagram in the manual. Photo taken during installation, with no power. (Photo: Dmitry G, Wikimedia Commons, CC BY-SA 3.0)
Real example: a European cooktop leaves the factory with its bridges set for two-phase; if the electrician connects it to a single-phase supply without moving the bridges as the manual says, half the cooking zones may not heat. Conversely, connecting two phases to a cooktop set up for single-phase can damage it. Always compare the bridges with the diagram in the manual before wiring; if unsure, ask the manufacturer.
Step 2: Calculate the current, choose the cable and a dedicated circuit breaker
Approximate current calculation
Single-phase supply: I = P / U. A 3,800 W double induction cooktop at 220 V: 3,800 / 220 ≈ 17.3 A. If the voltage drops to 200 V and the cooktop maintains its power, the current rises to about 19 A. So allow a margin for low-voltage conditions; the lesson how to choose cable size and circuit breakers for each circuit in the home also rounds a 3,800 W cooktop to about 19 A.
Reference table: cable and circuit breaker for the cooktop circuit
Cooktop type (total power on the rating plate) | Estimated current at 220 V | Copper cable for the dedicated circuit (L, N, PE) | Branch circuit breaker | Common connection method |
|---|---|---|---|---|
Single cooktop 1,800–2,200 W | 8–10 A | 2.5 mm² | 16 A | Plug into a dedicated earthed socket |
Double cooktop 3,000–3,500 W | 14–16 A | 4 mm² | 20–25 A | Adequately rated socket or hard-wired |
Double cooktop 3,800–4,400 W | 17–20 A | 4 mm² (6 mm² for long runs or shared conduit) | 25 A | Hard-wired or high-current socket |
3–4 zone hob 6,000–7,400 W, single-phase | 27–34 A | Per the manual, usually 6 mm² | Per the manual, usually 32 A | Hard-wired to the cooktop's terminal block |
The table is for reference only, for PVC-insulated copper cable in conduit at normal temperatures. Long runs, several circuits in one conduit, cables in insulated walls or hot locations require a larger cross-section. Where the cooktop manual says otherwise, follow the manual.
Two principles that must never be broken:
The breaker's rated current must not exceed the current-carrying capacity of the cable under the actual installation conditions. Never "upsize the breaker so it stops tripping" while keeping the same cable.
The earth wire has the same cross-section as the live wire. A 4 mm² live with a 1.5 mm² PE is a common mistake.
A dedicated circuit breaker with residual current protection
The cooktop circuit must be a dedicated circuit from the distribution board with its own breaker, not branched from another socket and not shared with the microwave or electric kettle. The kitchen has water, so the cooktop circuit needs 30 mA residual current protection (a dedicated RCBO, or downstream of an RCD depending on the board layout; see the lesson installing a home distribution board: arranging MCBs, RCBOs and safe earthing).
On type: Type AC residual current devices are designed only for sinusoidal AC leakage; Type A also detects pulsating DC leakage, which is common with equipment containing electronics. Many induction cooktop manufacturers recommend Type A or state the required type. The type is printed on the device body as letters or a waveform symbol; for new installations, choose the type the manual requires.
Check the main supply cable and the main breaker too
A 3,800 W cooktop adds nearly 20 A at evening cooking time, when the air conditioner and water heater may also be running. If the main breaker already trips at peak times or the cable after the meter is undersized, advise an upgrade; for the section from the grid to the meter, contact the power company (EVN).
Step 3: Choose between a socket and hard-wiring
Using a socket
Read the rated current printed on the plug and on the socket. Common flush wall sockets are usually rated 10 A or 16 A, which is not enough for a double cooktop drawing nearly 20 A, even if the plug fits. When using a socket:
The socket's rating is no lower than the plug's rating and the cooktop's current; the socket has an earth contact and that contact is actually connected to a PE wire.
One socket for the cooktop only; no extension leads, adaptors or multi-sockets; never replace the manufacturer's plug with a different type.
Hard-wiring
For high-power double cooktops and 3–4 zone hobs, the most durable method is hard-wiring: the cooktop's supply lead is connected to the dedicated circuit cable via a covered junction box or the cooktop's terminal block. When hard-wiring, there must be a separate, easily operated means of isolation for the cooktop: a dedicated breaker in the board labelled "COOKTOP", or an additional double-pole breaker or switch near the cooktop that doesn't require reaching over the hob. If the manual doesn't allow cutting off the plug or the client is worried about the warranty, ask the manufacturer first.
Location of the socket or junction box
Place it in the cabinet compartment next to the cooktop, within easy reach; not directly under the cooktop body where hot air is blown out, not behind an oven, and well away from the sink and water pipes.
Step 4: Run the cable and prepare the installation position
Run a dedicated circuit from the board to the cooktop in conduit, with all three conductors L, N and PE (green-yellow). For surface wiring, see the lesson surface wiring with plastic trunking.
Avoid joints along the run if possible; if a joint is unavoidable, make it inside a covered box as in the lesson how to join electrical wires correctly, never twisted and wrapped with tape inside the kitchen cabinet.
Check the countertop cut-out and ventilation gaps against the manual: if the cabinet compartment is sealed, the circuit board overheats and the cooktop reduces power or shows an overheat error.
If there is a built-in oven below, only stack them when both manuals allow it.
The cooktop supply lead should have just enough slack to lift the hob out for maintenance, without being trapped between the cooktop and the stone, or touching the underside of the cooktop or the oven body.

Figure 2. Inside a four-zone built-in induction hob with the glass removed: the copper coils that create the magnetic field, insulating plates and control boards; top left is the supply connection point, with the green-yellow wire connecting the metal frame to earth. The photo is only for understanding the construction; electricians should not open cooktops themselves. The brand label on the board has been blurred. (Photo: Twostaricebox, Wikimedia Commons, public domain)
Step 5: Safe wiring, step by step
Isolate: switch off the cooktop circuit breaker, or the main breaker when working inside the board. Lock off or hang a "Work in progress – do not switch on" tag and inform the household.
Prove dead: test your instrument on a known live source, measure at the wire ends to be connected (L–N, L–PE, N–PE), then test the instrument again on the live source. See the lesson using a multimeter for electricians.
Identify the wires correctly: green-yellow is used only for earth. In older installations with mixed-up colours, re-mark L and N with coloured tape after measuring.
Strip to the correct length, with no bare copper sticking out of the terminal and no strands cut off. Flexible stranded wire must have a pin ferrule crimped on before screwing down.
Connect PE first to the terminal marked with the earth symbol, then N, then L. For cooktops with multi-terminal blocks: compare each terminal and bridge with the single-phase diagram in the manual.
Tighten each screw, then tug each wire gently. Loose connections are the most common cause of overheating in high-current circuits.
Clamp the cable so pulling forces aren't transferred to the terminal screws; fit all terminal block covers and junction box lids.
At the board, connect to the dedicated breaker and label it "COOKTOP".

Figure 3. The supply connection box of an electric cooker (oven) with one group of screw terminals scorched; according to the photographer, poor contact caused the connection to heat up gradually. When you find a burnt junction box or socket like this: isolate, replace it, and cut off any section of wire that has hardened or discoloured before reconnecting. (Photo: Sumpfchiller, Wikimedia Commons, CC BY-SA 3.0)
Real example: a double induction cooktop was plugged into a 16 A socket shared with the rice cooker; a few months later the socket face had yellowed and the plug smelled burnt. The cooktop's nearly 20 A plus the rice cooker exceeded the socket rating, and the contacts gradually overheated. The fix: run a dedicated 4 mm² circuit from the board with a 25 A breaker with residual current protection, hard-wire the cooktop through a covered junction box, and keep the old socket for small kitchen appliances only. See also the lesson sockets and plugs that overheat, scorch or melt.
Step 6: Checks before and after switching on
Dead tests
Earth continuity: measure from the cooktop's metal frame (or the PE pin of the plug) to the PE bar in the board; the result must be very small, around less than 1 Ω for runs inside the home (reference).
No short circuit: measure L–N, L–PE and N–PE on the circuit cable before connecting the cooktop; there must be no continuity.
Insulation test (if you have a tester): only test the circuit cable with the cooktop disconnected, because the test voltage can damage the circuit board. A commonly quoted minimum is around 1 MΩ (reference); new cable is usually much higher.
Switching on and measuring voltage
Switch on the cooktop breaker and measure at the socket or junction box: L–N around 220 V, N–PE close to 0 V. If L–PE is close to 0 V and N–PE is close to 220 V, live and neutral are swapped; isolate and correct it immediately.

Figure 4. A clamp meter on the voltage function, displaying 220.0 V AC. When test-running the cooktop, switch to the current range and clamp the jaws around one live wire. The socket in the photo is a type used outside Vietnam. The brand name has been blurred. (Photo: Benjaminpvera, Wikimedia Commons, CC BY-SA 4.0)
Load test and current measurement
Place pans of water on all cooking zones and set them to the highest level or boost mode as per the manual.
Clamp the meter around one live wire, not around the whole cable containing L and N (the two opposing currents cancel out and the reading is close to 0). Record the current and the L–N voltage under load.
Compare with P / U. A much higher current, or a sharp voltage drop when the cooktop is switched on, indicates undersized cable, a long run or poor connections.
Run for about 20–30 minutes, isolate, then check the temperature of the plug, socket, junction box and the wire ends at the breaker using the back of your hand or an infrared thermometer. Slightly warm is normal; too hot to touch for long, discoloured or smelling means you must find the loose connection.
Press the test button (T) on the RCBO/RCD: it must trip immediately; reset it and run another test.
Measurement table for handover
Item | How to measure | Expected result (reference) | If it fails |
|---|---|---|---|
Dead before wiring | Tester pen, meter on L–N, L–PE, N–PE | 0 V on all three pairs | Don't touch yet; find the right breaker to switch off |
Earth continuity | Ω range, cooktop frame to PE bar | Very small, around less than 1 Ω | Check the PE wire, terminals and PE bar |
No-load voltage | L–N at the socket or junction box | Around 220 V | Weak supply: check the main cable, notify the power company if needed |
Voltage at full power | L–N under load | Drops by only a few volts | Large drop: undersized cable, long run, poor connections |
Current under load | Clamp meter around one live wire | Close to the cooktop's P / U | Abnormally high: check the cooktop and cable |
Connection temperature after 20–30 minutes | Isolate, then check plug, socket, junction box, breaker | Only slightly warm | Retighten or replace the connection or socket |
Residual current protection | Press the T button | Trips immediately | Replace the device |
Common faults after installation
The breaker trips when several zones are on high: the current exceeds the breaker rating. Only upsize the breaker within the limit of the cable; if the cable is too small, replace it. Some cooktops allow you to set a total power limit.
The residual current device trips when the cooktop is switched on or after cleaning it: water has got into the junction box or socket; the cable was crushed when fitting the hob; there is leakage inside the cooktop; or the wrong type of RCD is fitted. Narrow it down using the lesson circuit breaker keeps tripping: a 6-step procedure; faults inside the cooktop go to the warranty service.
The cooktop shows a voltage error or reduces heat by itself at peak times: measure the voltage when it happens. If the supply is low, the solution lies with the main cable, the power company or an adequately rated voltage stabiliser (see the lesson installing a voltage stabiliser for the home).
Overheat warning after cooking for a while: check the ventilation gaps and the cooktop fan.
Pan not detected: try a pan whose base strongly attracts a magnet; if the fault disappears, the pan was the cause.
When to stop and call a qualified specialist
The cooktop is rated only for two-phase or three-phase supply and the house is single-phase, or the manual has no clear single-phase diagram: ask the manufacturer or an electrical engineer.
The main breaker, main cable or meter is not adequate for the new load; the section from the grid to the meter belongs to the power company.
The house has no earthing or the earthing is inadequate: install earthing before fitting the cooktop.
Faults inside the cooktop (circuit board, coil, fan): refer to the warranty centre.
Advising the client
Clients often want to "just plug it in for now". Keep it short and use numbers: "Your cooktop is 3,800 W; on full power it draws nearly 20 A, and this socket is rated 16 A and is shared with the rice cooker. A dedicated circuit with an anti-shock breaker means you won't have to worry about the socket overheating or the power tripping."
State the scope of work clearly (metres of cable, breaker type, socket or hard-wired) before starting; pricing depends on the actual survey, see the lesson quoting, taking on jobs and working with clients. At handover, show the client the cooktop breaker and the RCD test button, and tell them that if they smell burning they should switch off the breaker and call an electrician.
Safety checklist before handover
Isolated, locked off or tagged, and proved dead before wiring.
Dedicated circuit from the board, dedicated breaker labelled "COOKTOP", 30 mA residual current protection of the type the manual requires.
Breaker rating not above the cable's current-carrying capacity; PE wire the same size as the live wire.
Socket (if used) adequately rated, for the cooktop only, earthed; or hard-wired through a covered junction box.
Bridges in the cooktop terminal block set to the single-phase diagram in the manual.
Stranded wires have pin ferrules, screws are tight, the cable is clamped and covers are closed.
Ventilation gaps as per the manual; the supply lead is not trapped or touching hot parts.
Measured PE continuity, no-load and on-load voltage, and current at full power.
After 20–30 minutes, connections are only slightly warm; the RCD test button trips immediately.
Frequently asked questions
Can a double induction cooktop be plugged into an ordinary socket?
Only if the socket and plug are rated no lower than the cooktop's current, the socket is dedicated to the cooktop, is earthed and is on a dedicated circuit with adequate cable. For a double cooktop of nearly 4,000 W, a common 10–16 A flush wall socket is not enough; hard-wire it or use a high-current socket.
Can 2.5 mm² cable be used for a double induction cooktop?
For a 3,500–4,400 W cooktop running continuously, 2.5 mm² is at the limit or inadequate. Use 4 mm²; for long runs or shared conduit, consider 6 mm².
Why does the anti-shock breaker keep tripping after the induction cooktop was installed?
It may be water in the socket or junction box, a crushed cable, leakage inside the cooktop, or a residual current device of a different type from the one the manufacturer requires. Disconnect the cooktop from the circuit to narrow it down: if the circuit no longer trips, the fault is in the cooktop.
Practical exercise
Exercise 1: Reading the rating plate and calculating. Take the rating plate or manual of a double cooktop and a single cooktop. Record the total power, voltage and supply connection method; calculate the current at 220 V and 200 V; choose the cable and breaker and explain your choice.
Exercise 2: Practice on a training board (with a supervisor): wire a covered junction box with 4 mm² cable, with pin ferrules on stranded wire; follow the full sequence of isolating, proving dead, measuring PE continuity, switching on and measuring L–N and N–PE; use a clamp meter to measure the current of a kettle and compare it with P / U.
Pass criteria:
Current calculated correctly; breaker rating not above the cable's current-carrying capacity.
Correct safety sequence before touching any wire.
L, N and PE correct; connections secure, with ferrules, cable clamped and covers fully closed.
Related lessons to study next: wiring a water heater safely with shock protection and wiring a wall-mounted air conditioner.