Sand in the shower head, a brown film in the toilet cistern, an RO purifier that clogs its first cartridge in a few weeks: these are signs that particles are travelling through the house pipework. A whole-house sediment pre-filter on the main line catches most of that dirt in one place, before it reaches tanks, valves, mixers and appliances.
This guide explains when a sediment pre-filter is worth installing, how to choose between a spin-down screen and a cartridge housing, how to choose the micron rating and port size, where to put the filter in a typical Vietnamese house with a cistern, booster pump or rooftop tank, and how to install it on PPR or uPVC pipe with a three-valve bypass, followed by flushing, maintenance and troubleshooting. It is written for trainee plumbers.
Scope and safety. A sediment filter only removes particles (sand, silt, rust flakes, scale debris). It does not disinfect water or remove dissolved iron, hardness, chemicals or bacteria. Before cutting into a supply line, close the main stop valve, release the pressure and, if a pump is involved, switch off and isolate the 230 V, 50 Hz pump at its breaker so it cannot start while the line is open. Keep water away from pump controllers and sockets. All sizes, times and pressure figures in this article are for reference only; the filter manufacturer's instructions, the pump data and local requirements always take priority.
Why and when to install a sediment pre-filter
Sediment can enter the house water from several sources:
Mains water after pipe repairs or a supply interruption, when rust and sand come through in bursts.
Underground cisterns (bể ngầm), where silt settles and is drawn up when the level is low.
Rooftop tanks (bồn nước mái), which collect dust and debris, especially if rarely cleaned.
Well water, which often carries fine sand.
Old galvanised steel pipes, which shed rust flakes.
Recommend a pre-filter when the customer sees particles or brown deposits, when aerators clog repeatedly, when float valves keep failing because grit holds them open, or when a water heater or RO purifier should be protected.
Be clear about what it will not do. Water that is clear at the tap but turns yellow after standing usually contains dissolved iron, which passes through a sediment filter; that needs testing and an iron removal system. White scale is hardness (a softener), and bad taste calls for activated carbon. The sediment filter is the first stage that protects such systems, not a replacement for them.
Types of whole-house sediment filter
Spin-down (screen) filters
A spin-down filter has a transparent bowl containing a washable stainless steel or nylon mesh screen. Water enters at an angle and spins, so heavier particles are thrown outwards and fall to the bottom of the bowl. A flush valve at the bottom lets you dump the collected sediment into a bucket or drain without opening the housing.
Spin-down filters suit sand and coarse grit. They have a low pressure drop and no cartridges to buy, but they are a coarse stage and will not stop fine silt. A Y-strainer works similarly, with a mesh screen inside a brass or plastic body that is removed by unscrewing a cap.

Figure 1. Small threaded mesh strainers: two brass Y-strainers (the right-hand one has a flush valve on the screen chamber) and a nickel-plated strainer. The cast arrow on each body shows the flow direction. A strainer or spin-down filter is a coarse stage; finer silt needs a cartridge. (Photo: Луносвет, Wikimedia Commons, CC BY-SA 3.0)
Cartridge housings
A cartridge housing has a head with inlet and outlet ports, a bowl that unscrews from the head, an O-ring seal and a replaceable cartridge. Besides the slim 10-inch housing used under sinks, there are larger "big" housings (about 4.5 inches in diameter, 10 or 20 inches long) for whole-house duty. A bigger housing holds more dirt and gives a lower pressure drop at the same flow.
Typical cartridges for sediment are:
Melt-blown polypropylene (PP), the common white cartridge that turns brown as it loads.
Pleated cartridges, with a large surface area; some can be rinsed and reused a few times.
String-wound cartridges for coarse to medium sediment.
A clear bowl shows when the cartridge is dirty, but must be kept out of sunlight, which encourages algae and degrades the plastic. Clear bowls may also have a lower pressure rating, so check the label.

Figure 2. A large-diameter cartridge filter housing with an opaque blue bowl, hung from a bracket screwed to the wall, with the inlet and outlet pipes entering the head from each side. The bracket carries the weight, so the pipework is not twisted when the bowl is unscrewed. (Photo: Vaniacornejo, Wikimedia Commons, CC BY-SA 3.0)
Backwashable and self-cleaning filters
Some filters can be backwashed: reversing the flow flushes trapped dirt from a screen or media bed to a drain. They suit wells with heavy sediment but need a drain and more space. For most houses the choice is a spin-down screen, a cartridge housing, or both in series.
Choosing the micron rating
The micron (µm) rating describes how fine a particle the filter is designed to catch. One micron is a thousandth of a millimetre; a human hair is very roughly 50–100 µm. Ratings are usually nominal, which means the filter catches most, not all, particles of that size. Absolute ratings are stricter and more expensive. Ratings are not standardised between brands, so treat the numbers below as a guide.
Rating (for reference) | What it mainly catches | Typical use |
|---|---|---|
Screen, roughly 100 µm and coarser | Sand, grit, rust flakes, pipe debris | Spin-down or Y-strainer as the first stage on well or cistern water |
50 µm | Coarse sediment and fine sand | Whole-house cartridge when water is dirty, or first of two cartridge stages |
20–25 µm | Most visible sediment and fine silt | A common general-purpose whole-house choice |
5 µm | Fine silt, some turbidity | Second stage, or ahead of a water heater or carbon filter on cleaner water |
1 µm | Very fine particles | Usually at the point of use (under-sink RO pre-filter), not whole-house |
Finer is not automatically better: a finer rating clogs faster and costs more pressure. On dirty water a single 5 µm cartridge may block in days. Use staged filtration: a coarse stage first (spin-down or 50 µm), then 20 µm or 5 µm.
Practical example. A house fed by a ground tank with sand after every mains interruption: fit a spin-down screen followed by a big 20-inch housing with a 20 µm PP cartridge.
Flow, pressure drop and port size
Every filter causes a pressure drop that increases with flow and with the amount of dirt in the cartridge. Manufacturers publish a maximum flow rate and pressure drop curves for each housing and cartridge combination; use those, not guesses.
Guidelines for sizing:
Match the port size to the pipe, never smaller. If the house main is PPR 25 mm (roughly 3/4 inch) and the housing has 1/2 inch ports, the filter becomes a bottleneck. For a whole house, 3/4 inch or 1 inch ports are common.
Estimate peak flow: two showers, a washing machine and a kitchen tap together is a realistic morning peak. Choose a housing whose rated flow comfortably exceeds it.
Check the pressure rating of the housing against the highest pressure it will see, including the cut-out pressure of a booster pump and pressure surges. Most plastic housings are for cold water only.
Low-pressure systems need extra margin. Water from a rooftop tank by gravity has very little pressure, roughly 0.1 bar for every metre of height between the water level in the tank and the outlet. Even a modest drop is noticeable, so choose a larger housing and a coarser rating.
Choosing the location
The general rule is: after the main stop valve and water meter, before anything you want to protect (tanks, water heater, purifier, mixers). In Vietnamese houses the supply layout varies, so consider the options below.
Mains direct to the house
Install the filter after the meter and the main stop valve, at the point where the supply enters the house, before any branch. This protects everything downstream.
Mains to an underground cistern, then a pump to the rooftop tank
There are three possible positions, each with trade-offs:
On the mains inlet, before the cistern float valve. Keeps the cistern cleaner, but low mains pressure means slower filling. Use a large housing and coarse rating.
On the pump discharge, before the rooftop tank. The pump pushes water through and the rooftop tank stays clean. The housing must be rated above the pump's maximum (shut-off) pressure, and a clogged cartridge reduces delivered flow.
Never on the pump suction. A filter between cistern and pump restricts suction, causing cavitation, noise and loss of prime. For grit from the cistern floor, use a foot valve with a strainer, keep the intake above the sediment and clean the cistern.
Rooftop tank feeding the house by gravity, with or without a booster pump
A filter on the tank outlet catches debris from the tank, but at gravity pressure the flow suffers. With a booster pump, place it after the pump (on its discharge), never on its suction. Without one, use a large housing with a coarse rating, or filter before the tank instead.

Figure 3. A rooftop installation in which a treatment vessel (here a water softener) sits in the pipe that fills the overhead tank, so water is treated before it is stored. A sediment pre-filter can be placed on a fill line in the same way, but a filter housing outdoors should be shaded and protected from direct sun. (Photo: రవిచంద్ర, Wikimedia Commons, CC BY-SA 4.0)
Before the water heater and RO purifier
Whatever the layout, the pre-filter should be upstream of the water heater and the RO purifier, whose own filters remain necessary.
Planning the installation
Tools and materials
Housing with bracket, cartridge(s) and housing wrench
Three ball valves of the pipe's nominal size, plus two unions
PPR fittings with threaded brass inserts, or uPVC threaded adaptors and cement
PTFE tape, PPR welding machine or uPVC cutter
Wall anchors, pipe clips, spirit level, drill
Two pressure gauges (optional but very useful), bucket, towels
The three-valve bypass
A bypass lets the household keep water while the cartridge is changed. It uses three valves:
Valve 1 (inlet) on the pipe going into the filter.
Valve 2 (outlet) on the pipe leaving the filter.
Valve 3 (bypass) on a pipe that connects the main line before valve 1 to the main line after valve 2.
Normally valves 1 and 2 are open and valve 3 is closed. For maintenance, open valve 3, then close valves 1 and 2. While the bypass is open the house receives unfiltered water, so close it again when the work is done. Label the valves ("IN", "OUT", "BYPASS – normally closed").
Put a union between the housing and each of valves 1 and 2, so the housing can be removed without cutting pipe. If fitting gauges, put one on the housing inlet and one on its outlet (inside the two valves), so their difference shows the pressure drop across the cartridge.
Step-by-step installation
Step 1: Mark out and check clearance
Hold the housing and bracket against the wall and mark the holes. Check:
The flow direction (IN/OUT or an arrow on the head).
Clearance below the bowl: enough to lower the bowl clear of the cartridge and swing the wrench (for reference, at least about 10 cm below a big 20-inch bowl).
Room for a bucket, ideally a floor drain nearby.
No direct sunlight, no risk of knocks, no electrical equipment below.
Step 2: Fix the bracket
Fix the bracket with suitable wall anchors and level it. A full 20-inch housing is heavy and is twisted every time the bowl is unscrewed, so the bracket must carry the weight and torque, not the pipes.
Step 3: Isolate and drain
Close the main stop valve, isolate the pump at its breaker if relevant, and open a tap downstream to release pressure and drain the section.
Step 4: Build the bypass and connections
On PPR, weld the bypass tees, valves and threaded adaptors with correct depth, time and alignment, and let joints cool before loading them. On uPVC, cut square, deburr, dry-fit, cement, and respect the cement maker's curing time before pressurising. Most housing heads have female ports, so you will use male adaptors or nipples; make up the threaded joints without stressing the welded or cemented ones.
Step 5: Make the threaded joints
Wrap PTFE tape on the male thread in the direction of tightening, keeping it flat and not overhanging the end, where it could shred into the water. Take care with plastic ports:
Do not over-tighten into a plastic female port. Tapered threads act as a wedge and can split the head, sometimes days later. Follow the maker's guidance.
Use only sealants approved for that plastic; some liquid sealants cause cracking.
Hold the head while tightening so it does not twist on the bracket.
Step 6: Support the pipework
Clip the pipes on both sides of the filter and bypass, close to the valves, so no load passes through the plastic threads and turning a valve does not flex the joints.
Step 7: Install the cartridge and bowl
Make sure the cartridge sits centred on the locating rings top and bottom, otherwise water flows around it. Check that the O-ring is clean, undamaged and seated in its groove; a thin film of food-grade silicone grease helps it seal. Avoid petroleum jelly, which can make some rubber seals swell. Screw the bowl on by hand and never force a misaligned bowl.
Flushing and leak testing
Filling and flushing
Close valve 3, open valve 2 and open a downstream tap that is easy to drain.
Open the main valve, then valve 1 slowly to avoid a pressure shock.
Press the vent button on the head, if fitted, until water comes out.
Run the tap until the water is clear and free of air, then restore pump power.
Leak test
Wipe every joint and the bowl seal with a dry tissue, which shows a weep the eye may miss. Check again after about 30 minutes and the next day, after the pump has cycled several times.
When pressure testing new supply pipework, do not exceed the housing's rated pressure. If the test pressure is higher, test with valves 1 and 2 closed and the bypass open, or with a spool piece in place of the housing.
Record the inlet and outlet pressures with the cartridge new and water flowing. This is the clean baseline for deciding when to change the cartridge.
Maintenance: changing the cartridge and cleaning the housing
How often?
There is no fixed interval. Change the cartridge when:
The pressure drop across the filter has risen clearly above the clean baseline (a common rule of thumb is around 0.5–1 bar of extra drop, for reference; follow the maker's figure), or
Flow at the taps falls noticeably, or
The maker's maximum interval has passed, even if it looks clean, to limit bacterial growth.
Task | Suggested interval (for reference) | Notes |
|---|---|---|
Visual check of bowl and joints | Monthly | Look for weeps, cracks, colour of the cartridge |
Flush spin-down or strainer screen | Weekly to monthly, or when sediment is visible | More often after mains repairs or heavy rain on well water |
Replace PP sediment cartridge | Roughly every 1–6 months | Shorter on cistern or well water; longer on clean mains |
Clean pleated cartridge | When pressure drop rises; replace after a few cleanings | Hose dirt off the outer surface; replace if damaged |
Clean and sanitise bowl, replace O-ring if worn | At each cartridge change; O-ring as needed | Check the seal for cuts, flattening or cracks |
Replace housing | When cracked, discoloured or past the maker's service life | Plastic housings age; do not wait for a burst |

Figure 4. Cartridges from a multi-stage household filter after about a year in use. The sediment cartridge on the left, originally white, has turned brown with trapped rust and silt; the other two are later stages of the same filter. A cartridge this discoloured is overdue for replacement, and the customer should be told that a whole-house sediment cartridge usually needs changing much more often than this. (Photo: Monoklon, Wikimedia Commons, CC BY-SA 4.0)
Changing a cartridge
Open valve 3, then close valves 1 and 2.
Press the vent button; never unscrew a bowl under pressure.
With a bucket below, unscrew the bowl and remove the old cartridge.
Wash the bowl with a soft brush (no abrasives) and, if the maker allows, sanitise with diluted chlorine and rinse well.
Clean, inspect and grease the O-ring.
Fit the new cartridge and bowl, open valve 1 slowly, vent, open valve 2, then close valve 3.
Run a tap until clear, check for leaks and write the date on the housing.
Troubleshooting
Low pressure or flow after installation
Clogged cartridge: compare the drop with the baseline and replace.
Rating too fine: if a new cartridge blocks within days, add a coarser first stage.
Undersized housing or ports: upsize.
Partly closed valve: check valves 1 and 2.
Collapsed cartridge from a high pressure drop: replace it.
Leak at the bowl O-ring
O-ring missing, twisted or out of its groove, or sand on the sealing face.
O-ring cut or flattened: replace with the correct part.
Bowl cross-threaded, under- or over-tightened.
A crack in the bowl or head: replace the housing, never repair it.
Leak at the ports
Usually an over-tightened or poorly sealed thread, or unsupported pipework stressing the head. Remake the joint and add clips.
Cloudy or dirty water after a cartridge change
Milky water that clears from the bottom of the glass upwards is air. Vent the housing and run the taps.
Fine black particles come from a carbon cartridge that was not flushed.
Brown water may be disturbed sediment, or water bypassing an unseated cartridge. Check its position and seals.
Safety and quality checklist
Main valve closed, pressure released, pump isolated at its breaker before cutting the pipe
Filter located after the stop valve and meter, never on a pump suction line
Housing rated above the highest system pressure, including pump cut-out pressure; cold water only, out of the sun
Flow direction correct; bracket carries the weight; pipes clipped
Clearance to remove the bowl
Bypass and unions installed and labelled; plastic threads not over-tightened
Flushed, vented, leak-checked after 30 minutes and next day
Pressure baseline and change date recorded; customer shown the bypass
Frequently Asked Questions
What micron rating should I use for a whole-house sediment filter?
For many houses a 20–25 µm cartridge is a good general choice. On dirty well or cistern water, start with a spin-down screen or 50 µm cartridge, then a finer stage. Fine 1–5 µm ratings are usually better at the point of use, such as an RO purifier. These values are for reference; test the water and follow the filter maker's advice.
Will a sediment filter remove yellow water or iron?
Only if the iron is already in particle form, such as rust flakes. Dissolved iron passes through and turns yellow or brown later when it oxidises. That requires water testing and a suitable iron removal system.
Can I install the filter before the pump?
Not on the pump's suction line. A filter there restricts suction and can cause cavitation and loss of prime. Install it on the pump discharge (checking the housing pressure rating) or on the mains inlet before the cistern.
Does a whole-house filter reduce water pressure?
Yes, a little when clean, and more as it clogs. Correct port size, a large housing, staged ratings and changing the cartridge on time keep the drop small. On gravity-fed systems the effect is more noticeable.
Practice Exercises
Exercise 1: Choose the location. A house has mains water into an underground cistern, a 230 V pump to a rooftop tank and gravity feed to the bathrooms. Sketch it, mark two acceptable pre-filter positions and one you would reject, and explain why.
Exercise 2: Plan the bypass. Draw a three-valve bypass with unions for a 20-inch housing on PPR 25 mm pipe, with each valve's normal position and the cartridge change sequence.
Exercise 3: Read the gauges. With a new cartridge, the inlet gauge reads 2.5 bar and the outlet gauge 2.4 bar while a shower runs. Three months later the readings are 2.6 bar and 1.7 bar. What has changed, what will the customer notice, and what action do you take?
Exercise 4: Diagnose the fault. A day after a cartridge change, the housing drips and the kitchen water is cloudy. List likely causes and your checks, in order.