After a thunderstorm, a client calls: “Lightning struck near the house last night, and this morning the wifi modem, the camera recorder and the air-conditioner control board are all dead, but not a single breaker tripped. Can you install lightning protection for me?” Calls like this are common in the rainy season, especially for houses next to open fields, tall stand-alone houses, and areas still served by overhead lines.
What the client is asking for is a surge protective device on the power supply, known as an SPD, installed in the distribution board. By the end of this lesson, you will be able to choose the right type, read the label, choose its position relative to the main breaker and the RCD, wire it with short leads, test it after installation and after storms, and advise the client correctly.
The manufacturer's instructions and the building's design are the highest authority; the figures in this lesson are for reference only, and where they differ, follow the instructions and current regulations. Before touching any wire, switch off the breaker and confirm the circuit is dead according to the 5 mandatory safety rules. Never work in the distribution board, on the roof or on earthing conductors while a thunderstorm is in progress.
What are lightning surges, and what can and can't an SPD do?
Where overvoltage surges come from
Lightning does not need to hit the house directly to damage equipment. A strike near the power lines or on the ground nearby can travel along power cables, antenna cables and network cables into the house, or be induced as a voltage on long cable runs. Switching large loads or faults on the grid also create surges. Surges are very high but extremely short (in the order of microseconds); breakers and fuses are not designed to cut them, which is why “no breaker tripped but the equipment is still broken”.
How an SPD works
Inside a household SPD there is usually a metal oxide varistor (MOV), sometimes combined with a spark gap or gas discharge tube. At normal voltage they are practically an open circuit. When a surge exceeds the threshold, they conduct very quickly, diverting most of the energy to earth and clamping the remaining voltage to a low level, then return to open once the surge has passed.

Figure 1. A plug-in Type 2 SPD module for DIN rail (label reads Uc 275 V, In 20 kA, Imax 40 kA, Up 1.35 kV) and a blue varistor, the main component inside the module. The brand name has been blurred. (Photo: WagnerTh, Wikimedia Commons, CC BY-SA 4.0)
Each time it diverts a surge, the varistor ages a little. That is why a good SPD has a thermal disconnector that separates the module from the circuit when it fails, along with a status indicator window (usually green means good, red means replace). An SPD is not something you install once and forget forever.
What an SPD cannot do
It does not protect against direct lightning strikes. That is the job of the air terminal (lightning rod), down conductors and lightning earthing system installed by specialists.
It does not protect people against electric shock. Shock protection is the job of the RCD/RCBO (residual current breaker) and earthing.
It cannot replace a voltage stabiliser. An SPD only handles very short surges; sustained overvoltage (for example a lost neutral on a three-phase main line) can overheat the SPD and make it disconnect itself.
It does not protect signal lines. Antenna cables, network cables and outdoor camera cables need their own signal SPDs.
It is not a 100% guarantee. Do not promise the client that “once this is installed, lightning won't damage anything again”.
Step 1: Survey before installing
Survey the following 6 points and record them on the job sheet before choosing equipment:
Is there an earth, and does it meet requirements? Without a good earth, an SPD is almost useless. See the lesson installing a home distribution board: arranging MCBs and RCBOs and earthing safely.
Main board: is there space on the rail, a separate PE bar, what type of main breaker, a main RCD or branch RCBOs?
Is there a lightning rod? If there is, or if overhead lines cross open ground, a Type 1 SPD may be needed at the supply origin, which should be selected by a designer.
The service line into the house: overhead or underground.
Sensitive equipment far from the board (top floor, gate, garage) may need an additional layer of protection close to the equipment.
Signal lines: antenna cables, network cables, outdoor camera cables.
Example. A three-storey townhouse with an overhead service line; the main board on the ground floor has a main breaker and a main RCD, and there is an earth rod. After a storm, the modem, the camera recorder on the third floor and the roller shutter board failed. Recommendation: a Type 2 SPD at the main board, upstream of the RCD; an additional Type 3 surge protector for the network cabinet on the third floor; ask a network technician to install surge protection for the outdoor camera cables.
Step 2: Choose the SPD type and read the label
Three SPD types by installation position
Type | Tested with | Usual installation position | When to use |
|---|---|---|---|
Type 1 (T1) | Current impulses simulating direct lightning current (10/350 µs waveform, Iimp rating) | Supply origin, main board | Buildings with a lightning rod, or as designed where lightning risk is high |
Type 2 (T2) | Current impulses with an 8/20 µs waveform (In, Imax ratings) | Main board, floor boards | The most common choice for houses and apartments |
Type 3 (T3) | Combination wave, low energy | Sockets, close to equipment | An additional layer for sensitive equipment, only used when a Type 2 is already installed upstream |
For a house without a lightning rod: usually choose a Type 2 SPD at the main board. With a lightning rod, workshops, or farms in open areas: follow the design.
Reading the 5 ratings on the label

Figure 2. A two-pole DIN-rail SPD: the L terminal at the top, the earth terminal (earth symbol) at the bottom. The module label reads Uc 385 V, Imax 40 kA, In 20 kA, Up ≤ 1.8 kV; the window is green. The module on the left has been pulled out and opened to show its construction; never do this with a module in use. The brand name has been blurred. (Photo: JoanTheSpark, Wikimedia Commons, CC0)
Uc – maximum continuous operating voltage. For 220/230 V networks, 275 V is common (reference). Some types are rated higher (320 V, 385 V…). A higher Uc copes better with fluctuations but usually comes with a higher Up; choose according to the actual network and the manufacturer's recommendation.
In – nominal discharge current (8/20 µs), which it can withstand many times; Type 2 units for homes are often 20 kA (reference).
Imax – maximum discharge current (8/20 µs), which it can withstand once; often 40 kA (reference).
Up – voltage protection level: the residual voltage while the SPD is discharging. The lower, the better; it must be lower than the impulse withstand of the equipment.
Maximum backup protection, for example “125 A gL” means a gL-type fuse of maximum 125 A.
Also look for the T2/Type 2 marking, the product standard (for example IEC 61643-11), a plug-in module and a status indicator window. Avoid products whose labels do not list all the ratings.
Choosing the pole configuration for a single-phase house
Two common arrangements for single-phase houses:
“1+1” configuration: one varistor module between L and N, and one spark-gap module between N and PE. Normally there is almost no leakage current to PE, so it suits installation upstream of an RCD. The three-phase equivalent is “3+1”.
L–PE and N–PE configuration: one module from each conductor to earth; check whether the manufacturer allows it for the house's earthing system.
Choose a product the manufacturer clearly states is suitable for the house's earthing system (a local earth at the house or PE supplied from the network); if you are unsure, ask someone experienced.
Step 3: Choose the position in the board, coordinating with the breaker and RCD
Where the SPD goes in the diagram
Meter (belongs to the utility; do not interfere) → the house's main breaker.
Immediately after the main breaker, take a branch: the breaker (or fuse) protecting the SPD, sized exactly as the manufacturer requires → SPD → a short lead to the PE bar.
Only after that branch point come the main RCD or the branch RCBOs, and then the circuits.
Why does the SPD go upstream of the RCD? Surge current is discharged to PE; if the SPD is downstream of the RCD, the RCD sees it as leakage current and may trip or be damaged. If it has to be installed downstream, choose a surge-resistant RCD (for example a time-delayed S type) according to the manufacturer's instructions.
Does the SPD need its own breaker?
When an SPD fails short-circuit, there must be a device to disconnect it from the supply. If the main breaker is not larger than the maximum backup rating marked on the SPD, many manufacturers allow you to omit an extra one. A dedicated breaker of the size the manufacturer recommends lets you replace the module without cutting power to the whole house, but if it trips, the SPD is disconnected without the client knowing. Label it “SURGE PROTECTION BREAKER – ALWAYS ON”. Do not pick an arbitrarily small breaker yourself: one that is too small may trip as soon as a surge arrives, disconnecting the SPD exactly when it is needed.
Distance to equipment
Equipment far from the main board (many references mention a benchmark of about 10 m of cable, reference) may see voltages higher than Up because of reflections on the line. For network cabinets and camera recorders on distant floors, add a Type 3 surge protector close to the equipment.
Step 4: Wiring the SPD correctly – short, straight, secure
The short-lead rule
This is the most common mistake. When a surge is discharged, the current changes extremely fast and every length of wire generates an induced voltage that adds to Up. An often-quoted estimate is about 1 kV per metre of wire during a large surge (reference, for illustration only). Therefore:
The total length of the wire from the L/N connection point to the SPD plus the wire from the SPD to the PE bar should be as short as possible. Many installation guides based on IEC 60364-5-53 recommend no more than about 0.5 m (reference).
Run the wires straight, without loops and without coiling the excess to make it look “tidy”.
Place the SPD right next to the PE bar; do not put the SPD at one end of the board and the PE bar at the other.
Do not bundle the SPD's PE lead together with the outgoing circuit cables.
Conductor cross-sections (reference)
Conductor | Typical copper cross-section (reference) | Notes |
|---|---|---|
Type 2 SPD → PE bar | Usually 6 mm² or more (some older references state a minimum of 4 mm²) | As short as possible, green-yellow wire |
Type 1 SPD → PE bar | Usually 16 mm² or more | As designed |
Board PE bar → earth rod | As per the earthing system design | The rod connection must be secure and corrosion-protected |
Always give priority to the figures in the instructions for the SPD you are installing.
Step-by-step installation
Switch off the main breaker, lock it or hang a “Do not switch on – work in progress” tag. Inform the people in the house.
Confirm the supply is dead at the main breaker output (L–N, L–PE, N–PE), proving your meter on a live source before and after; see the lesson using a multimeter for electricians. Note: the input of the main breaker is still live when the breaker is off. Do not touch it.
Mount the SPD breaker and the SPD on the rail next to each other, close to the PE bar, oriented as shown on the label.
Connect L and N from the load side of the main breaker through the SPD breaker to the SPD. With the “1+1” configuration, L and N must not be swapped (the spark-gap module sits only between N and PE).
Connect the PE lead from the SPD's earth terminal to the PE bar by the shortest route.
Tighten the screws to the torque stated by the manufacturer and tug-test each wire; stranded wires must have pin lugs crimped on.
Insert the module into its base (if it is a plug-in type) and check the indicator window.
Label it: device name, installation date, replacement module type.
Step 5: Testing after installation
Dead tests before energising
Check L, N and PE against the diagram; if the SPD leads are long, fix them straight away.
When testing insulation with a megger, remove the module or disconnect the SPD first, because the test voltage may make the SPD conduct, giving false readings or damaging the SPD. Reinstall it after testing.
Check continuity from the SPD earth terminal to the PE bar and from the PE bar to the earth rod.
Energise and observe
Switch on the main breaker, then the SPD breaker. The indicator window must show the good state (usually green); if it is red right after installation, switch off and check the connections and supply voltage.
Measure L–N, L–PE and N–PE at the board. An abnormally high N–PE voltage, or a low L–PE voltage when L–N is normal, indicates a problem with the earth or neutral that must be fixed first.
Press the RCD/RCBO test button and record the measurements on the handover sheet.
Checking after thunderstorms and replacing modules

Figure 3. A three-phase “3+1” SPD set in a distribution board in Austria: three phase modules (labelled Uc 280 V, In 20 kA, Imax 40 kA, T2) and one blue N–PE module. Two indicator windows are green and one is red: according to the photographer's description, that module has operated and needs replacing. Brand logos have been blurred. (Photo: Asurnipal, Wikimedia Commons, CC BY-SA 4.0)
After every major storm, open the board door (without removing the inner cover) and look at the SPD windows. Do not touch the terminals before switching off the power. Quick-reading table:
Sign | Usual meaning | What to do |
|---|---|---|
Window green, SPD breaker on | The SPD is in circuit | Note it |
Window red on one module | That module has disconnected itself and no longer protects | Switch off, replace the module with the same part number, record the replacement date |
SPD breaker tripped | The SPD may have failed short-circuit or experienced an excessive surge | Do not reset it repeatedly; inspect and replace the SPD if needed |
Cracked or scorched casing, burning smell | The SPD has been severely overloaded | Switch off, replace the whole unit, inspect the wiring and PE bar |
Window green but equipment still damaged | The surge came in via signal lines, or the equipment is far from the board | Consider a Type 3 SPD and signal SPDs |
Replacing a module: switch off the SPD breaker (or the main breaker), confirm it is dead, pull out the failed module, plug in a module with the same part number or one the manufacturer approves, switch on and check the window. Do not use a module from another brand or with a different Uc.
Common mistakes when installing SPDs
The house has no earth, or the SPD earth terminal is connected to the neutral: the SPD has no proper discharge path.
Long SPD leads, coiled to look neat: the induced voltage on the wire cancels most of the benefit.
Placing the SPD downstream of the main RCD without checking the instructions: the RCD trips frequently during storms.
No backup protection of the right size, or an SPD breaker that is too small.
Swapping L and N on a “1+1” SPD.
Not showing the client the indicator window: a red module goes unnoticed for a long time.

Figure 4. The surge protection unit of a solar power system that burned in a 2022 fire in Austria (according to the photographer's description). If you see an SPD that is cracked, scorched or smells of burning: switch off, replace the whole unit and inspect the surrounding wiring and PE bar. (Photo: Asurnipal, Wikimedia Commons, CC BY-SA 4.0)
When to stop and call a specialist
The building has a lightning rod and needs a Type 1 SPD or multi-stage protection: a designer is needed.
Work upstream of the main breaker, at the meter or on the service line into the house: this belongs to the power utility (EVN). Do not connect anything yourself or break any seals.
Apartments: floor boards and common risers belong to the building management. Only install in the apartment's own board, and ask management about an SPD at the building's main board.
Sustained abnormal voltage (suspected lost neutral): report it to the power company; do not install an SPD as a “quick fix”.
Signs of burning or melted plastic in the board, or a suspected direct lightning strike on the house: switch off, inspect everything, and call in a professional lightning protection company.
Advising the client
Clients usually want to hear “install this and you won't have to worry about lightning any more”. Tell them the truth:
“This device blocks most surges coming in through the power line and reduces the risk of damage to electronics, but it does not protect against direct strikes and does not replace the RCD for shock protection. After a big storm, check this window: green is good, red means call me to replace the cartridge. Antenna and network cables need their own surge protection.”
When quoting, list separately: the SPD and its protective breaker, wire and lugs, labour, earth testing or installation, and an optional Type 3 SPD. Do not give a price before surveying. See also the lesson quoting, taking on jobs and working with clients as a residential electrician.
Advise the client: before a big storm, they can unplug expensive, rarely used equipment. During lightning, do not go on the roof, and do not touch antenna cables or the distribution board.
Safety checklist before handover
There is an earth, and it has been measured and recorded.
Power was switched off, a tag was hung, and the circuit was confirmed dead with a meter before connecting.
The SPD is the correct type (T2 or as designed), Uc suits the network, and it has an indicator window.
The SPD is downstream of the main breaker and upstream of the RCD (or a surge-resistant RCD per the manufacturer's instructions); backup protection is correctly sized.
SPD leads are short, straight and of the correct cross-section; L and N on the correct terminals; screws tightened to the right torque.
For insulation testing (if done), the SPD was removed first and reinstalled afterwards.
After energising: the indicator window is good; L–N, L–PE and N–PE are normal; the RCD/RCBO test button operates.
The SPD is labelled, the client has been shown the indicator window and told to check after storms.
Frequently asked questions
Can I install an SPD in a house with no earth?
It can be connected, but it is almost useless, because the SPD needs a path to discharge surges to earth. Install an earth and measure it to confirm it meets requirements first. Never connect the SPD earth terminal to the neutral.
Can a power strip labelled “surge protected” replace an SPD in the distribution board?
No. It is only a layer of protection close to the equipment and handles small amounts of energy. The correct approach is a Type 2 SPD at the main board, plus surge protection near sensitive equipment if needed.
What should I do if the SPD window turns red after a storm?
That module has disconnected itself and no longer protects, even though the electricity in the house still works normally. Switch off, confirm it is dead, replace the module with the same part number, then switch back on.
Will installing an SPD make the RCD trip often?
If the SPD is installed upstream of the RCD and wired to the correct diagram, normally not; if it is downstream of the RCD, each surge discharge may trip the RCD. If it trips even in dry weather, see the lesson breaker keeps tripping: a 6-step procedure to find the real cause.
Practice exercises
Exercise 1: Reading labels. Take the labels of two SPDs from two brands and write down Uc, In, Imax, Up, type and maximum backup rating; explain which one suits a house with a frequently fluctuating supply.
Exercise 2: Draw a single-line diagram of a single-phase main board: main breaker, SPD breaker, “1+1” SPD, main RCD, four branch circuits, and a PE bar connected to the earth rod. Mark the conductors that must be the shortest.
Exercise 3: Install on a training board (with an instructor): connect the SPD with the shortest leads, carry out dead tests, remove the module for insulation testing, reinstall it, energise, read the indicator window, and measure L–N, L–PE and N–PE.
Pass criteria:
You read all 5 label ratings correctly and choose the right SPD type.
Correct position relative to the main breaker and RCD; correct L, N and PE terminals.
Short, straight, secure leads; you remember to remove the SPD for insulation testing.
You explain to the “client” what an SPD can and cannot do and how to read the indicator window.
Related lessons to study next: installing a home distribution board: arranging MCBs and RCBOs and earthing safely and installing a voltage stabiliser at home when the supply is weak or unstable.