A client calls: “Could you come and wire up my new air conditioner? The refrigeration technician is coming to install it this afternoon.” Or: “Every time I switch on my air conditioner, the breaker trips.” In the hot season, electricians get calls like these all the time. A wall-mounted split air conditioner is a large load that runs continuously for many hours, so sloppy electrical work shows up very quickly: hot cables, burnt terminals, tripping breakers.
This lesson covers only the electrical part: running a dedicated circuit, reading the rating label to choose the cable and circuit breaker, identifying which unit receives the supply, connecting the power cable and the interconnecting cable, earthing, protecting outdoor cables, testing before energizing, and dealing with a few common faults. Copper piping, refrigerant and vacuuming are the refrigeration technician’s job; the electrician does not touch them. By the end of this lesson, you will be able to plan and wire the supply for a single-phase split air conditioner according to the manufacturer’s diagram, test it properly before switching on, and narrow down the most common electrical faults.
Rule number 1: Every brand and every model has its own wiring diagram. The diagram on the unit and the manufacturer’s installation manual are the highest authority, above the habit of “every unit is wired this way”. Before touching any wire, switch off the circuit breaker and verify that it is dead according to the 5 mandatory safety rules.
What cables does a wall-mounted air conditioner have?
Power cable: from the circuit breaker to the unit that receives the supply, consisting of line (L), neutral (N) and protective earth (PE).
Indoor–outdoor interconnecting cable: connects the terminal blocks of the two units, both carrying power to the other unit and carrying control signals between the two circuit boards. It is usually a multi-core cable with one earth core.
Earthing: connects the metal casings of both units to the building’s earthing system.
Refrigeration technicians usually bundle the interconnecting cable with the copper pipes; the two trades should agree beforehand on who runs which cable and who connects which terminals.
Step 1: Read the rating label and the manual before buying cable
Do not choose cable and breakers by “it’s a 1 HP unit”: two units with the same cooling capacity but different brands or generations can list different currents. Look at the rating label (usually on the side of the outdoor unit, or under the front cover of the indoor unit) and in the installation manual for:
Voltage and number of phases. Most domestic wall-mounted units are single-phase 220–240 V. Three-phase units have their own diagrams; the wiring method in this lesson does not apply to them.
Rated current and maximum current (some labels say “Max current” or similar), and electrical power input (different from cooling capacity).
Manufacturer’s recommendations: breaker or fuse rating, power cable cross-section, interconnecting cable cross-section and number of cores, type of residual current device.
Which unit receives the supply and the terminal block diagram.
Photograph the label and the diagram page; if the client has lost the manual, look it up by model number on the manufacturer’s support website.
Step 2: A dedicated circuit and dedicated MCB for each unit
Each air conditioner should have its own circuit from the distribution board with its own circuit breaker. Do not branch off the nearest socket, do not plug it into an extension lead, and do not share a circuit with a water heater or cooker. A shared circuit adds up the current of several loads, so cables and terminals gradually heat up, and it can easily end up like the cases in the lesson on sockets and plugs that overheat and melt.
How to choose breakers and cable cross-sections by load current, length and installation method is covered in the lesson on how to choose cable cross-sections and circuit breakers for each circuit in the home. For air conditioners in particular, also remember:
Give priority to the manufacturer’s recommended values. If the manual specifies a breaker rating in amps, use exactly that rating, not a larger one; the cable must be able to carry the current of the chosen breaker.
For long cable runs, calculate the voltage drop. A large voltage drop makes it hard for the compressor to start and the unit often shows error codes.
An isolating device near the unit. Many installation manuals require fixed wiring to include a device that disconnects all poles. In Vietnam, a common solution is a 2-pole breaker box mounted next to the indoor unit, within easy reach and not below any spot where condensate could drip.
Residual current protection: the air conditioner circuit needs a suitable RCBO or RCD according to current standards and the manufacturer’s requirements (some manufacturers specify the RCD type for inverter units). For the layout in the board, see the lesson on installing a home distribution board: arranging MCBs, RCBOs and safe earthing.
Step 3: Does the supply go to the indoor or the outdoor unit?
There is no general rule that “power always goes to the outdoor unit” or “always to the indoor unit”:
Supply to the indoor unit: the power cable (or plug) goes to the indoor unit, which feeds the outdoor unit through the interconnecting cable. Common on smaller units.
Supply to the outdoor unit: the power cable goes straight to the outdoor unit’s terminal block, and the outdoor unit feeds back to the indoor unit.
Separate supplies to each unit on some models.
Identify it from the diagram inside the terminal box cover and the installation manual. Do not guess from the wire colours or from how the previous installer wired it, because the previous installer may have got it wrong. Usually switching off one breaker de-energizes both units; with separate supplies, you must switch off both.

Figure 1. The outdoor unit of a split air conditioner on a bracket: at the top right is the plastic cover over the terminal box, and the cables and insulated copper pipes come out of the side. The position of the terminal box varies by model. (Photo: Smial, Wikimedia Commons, CC BY-SA 2.0 DE)
Step 4: Reading the terminal block and making the connections
Terminal markings differ by manufacturer
When you open the terminal box, you may find: terminals numbered 1, 2, 3 plus an earth symbol; terminals marked L, N plus a signal terminal (some units mark it S, others use a number); or a combination of numbers and letters. Never assume that terminal “3” on one unit is the same as terminal “3” on another. Follow the marking table for that specific model.
Warning: On many air conditioners, the “signal” core in the interconnecting cable carries a dangerous voltage relative to earth; it is not a safe low-voltage signal. Treat every core in the interconnecting cable as a live 220 V conductor.
Wiring principles
Mark both ends. Use number labels or numbered ferrule sleeves on each core. Terminal 1 on one side connects to terminal 1 on the other, 2 to 2, 3 to 3.
The right type of cable and the right number of cores according to the manual. Do not use telephone cable, network cable or undersized cable as the interconnecting cable.
Minimize joints along the way. Many manufacturers require the interconnecting cable to be one continuous length. If a joint is unavoidable, make it inside a sealed box, using the correct technique as in the lesson on how to join electrical wires correctly and as the manufacturer requires. Do not wrap it in tape and tuck it into the pipe insulation.
Neat wire ends. Strip just enough so the copper sits fully inside the terminal with no copper showing outside. Stranded wire should be crimped with a ferrule or lug suited to the terminal type. Do not solder-tin stranded wire ends and clamp them under a screw: the solder creeps over time and the connection gradually loosens.
Tighten firmly with the correct size of screwdriver, then tug each wire gently to test it; if the manual specifies a tightening torque, follow it.
Use the cable clamp provided in the unit, clamping onto the outer sheath of the cable so any pulling force does not fall on the terminal screws.
Refit the terminal box cover with all its screws to keep out rain and dust.
Earthing both units
Connect the earth core to the earth terminal (⏚) on both the indoor and outdoor units; the power cable must carry the earth from the distribution board. Do not use water pipes, steel frames or the outdoor unit bracket instead of an earth conductor, and do not connect earth to neutral. If the house has no earthing or the earthing is faulty, inform the homeowner in a written message and propose doing the work; do not quietly ignore it.
Step 5: Outdoor cables and waterproofing
Sun (UV) protection: ordinary cable sheaths left exposed to the sun for a long time become brittle and crack. Use cable with a sheath suitable for outdoor use as recommended by the manufacturer, or run it in conduit or trunking. Usually the interconnecting cable is bundled with the copper pipes and wrapped in tape; agree this with the refrigeration technician.
Drip loop: before the cable enters the outdoor unit’s terminal box or the hole through the wall, let it sag lower than the entry point so rainwater drips off at the lowest point instead of running inside.
The hole through the wall is drilled sloping slightly downwards to the outside; once the pipes and cables have been passed through, seal it.
Secure the cable so it does not rub against sharp metal edges; for indoor surface sections, run it in trunking as in the lesson on surface wiring in plastic trunking.
Real-life example: An outdoor unit is mounted on a west-facing wall, with the interconnecting cable left bare in the sun. After a while the sheath cracks, rain gets in and the RCBO trips. The electrician replaces that section of cable, bundles it with the copper pipes and remakes the drip loop before the terminal box; the RCBO stops tripping.
Step 6: Testing before energizing
Once the wiring is done, do not switch on straight away. Keep the breaker off and test in order.
Dead tests (no power)
Visual check: wired to the diagram, terminal numbers at both ends match, no exposed copper, no copper strand touching an adjacent terminal.
Continuity of each interconnecting core: disconnect the cable from the terminals at both ends, temporarily short two cores together at one end, and measure at the other end on the Ω or continuity range, pair by pair. For how to use the meter, see the lesson on using a multimeter as an electrician. Remove the temporary short after measuring.
Earth continuity from the earth terminals of both units back to the earth bar in the distribution board.
Short-circuit check: with the cores free at both ends, measure between each pair of cores and between each core and earth. There must be no continuity.
Insulation resistance test (if you have a tester): only test the cable after it has been disconnected from both units and from the breaker. Never apply the insulation tester’s test voltage to the air conditioner’s circuit boards, because it can damage components. If the unit itself needs an insulation test, follow the manufacturer’s instructions or leave it to the refrigeration technician.

Figure 2. An insulation resistance tester with a rotary knob for selecting a test voltage of 50–1000 V. The tester in the photo is set to 1000 V and the display shows more than 11.0 GΩ; 220 V household circuits are usually tested on the 500 V range (reference). (Photo: wdwd, Wikimedia Commons, CC BY-SA 4.0)
Ask the refrigeration technician before running the unit
Do not energize the unit so the compressor runs while the pipework has not been vacuumed and the valves have not been opened. Before the test run, ask the refrigeration technician: “Is the pipework finished, are the valves open, can we run it?”
Energize and do live tests
Switch on the breaker and measure at the supply terminals: L–N, L–PE, N–PE. L–N and L–PE should be close to mains voltage; N–PE is usually very small. If N–PE is unusually high or L–PE is zero, check the earthing and whether L and N have been swapped.
Measure the voltage between the supply terminals on the other unit (per the diagram) to be sure power has passed through the interconnecting cable.
Switch the unit on. Many units have a protective time delay before the compressor starts; wait as specified in the manual before concluding that “the outdoor unit isn’t running”.
Once the unit is running steadily, use a clamp meter around a single core (the line core). If you clamp the whole multi-core cable, the outgoing and return currents cancel and the meter reads close to zero. Compare the measured current with the rated current on the label.
After it has run for a while, check whether the breaker and terminals are unusually hot (with an infrared thermometer if available).

Figure 3. Measuring AC voltage with the meter function of a clamp meter: the two probes are inserted into a socket and the display shows 220.0 V AC. The photo was taken in Chile, so the socket is a foreign standard. (Photo: Benjaminpvera, Wikimedia Commons, CC BY-SA 4.0)
Record the readings on the handover sheet so you have figures to compare with if the client calls for warranty service.

Figure 4. A clamp meter: when measuring current (ACA range), open the jaw on the left and clamp it around exactly one core. (Photo: Redecke, Wikimedia Commons, Public domain)
Reference table: what to look up and how to use it
The figures in the table are for reference only; always follow the rating label, the manufacturer’s manual and current Vietnamese standards.
Item | Where to find it | How to use it (reference) |
|---|---|---|
Voltage, number of phases | Rating label | The wiring method in this lesson only applies to single-phase 220–240 V units; three-phase units follow their own diagrams |
Rated current, maximum current | Rating label, manual | Basis for choosing the breaker and cable; compare with the current measured by clamp meter during the test run |
Recommended breaker or fuse | Installation manual | Use exactly the rating the manufacturer specifies, never a larger one |
Cross-section and number of cores of the power and interconnecting cables | Installation manual | No smaller than the manufacturer specifies; for long runs, also calculate voltage drop |
Supply entry point, terminal markings | Diagram inside the terminal box cover, manual | Match terminal numbers at both ends; do not assume from another unit |
Residual current device | Manual, current standards | Choose the type and tripping current as required; 30 mA is the level commonly used for personal protection (reference) |
Insulation test voltage | Tester instructions, current standards | 220 V circuits are usually tested at 500 V DC (reference); only test cable disconnected from the units |
Common faults and how to narrow them down
The breaker trips when the air conditioner is switched on
Note when it trips and which device trips (MCB or RCBO/RCD).
Trips as soon as the breaker is switched on: suspect a short circuit in the cable or inside the unit. Disconnect the cable from the unit and test the cable for shorts and insulation. If the cable is fine but it trips again when the unit is reconnected, the fault is inside the unit; hand it over to the refrigeration technician.
Trips a few minutes after switching on, when the compressor starts: the breaker is smaller than the manufacturer recommends, the circuit is shared with other loads, a loose terminal is overheating, or there is a compressor problem. Check that the circuit is dedicated, check the breaker rating, and measure the current with a clamp meter.
RCBO/RCD trips, especially after rain: suspect water in the outdoor unit’s terminal box, a cracked outdoor cable sheath, or a damp joint in the interconnecting cable.
For the full procedure, see the lesson on breakers that keep tripping: a 6-step procedure. Never fit a larger breaker to “stop it tripping”: the breaker protects the cable, and upsizing the breaker while keeping the old cable just lets the cable burn.
The indoor unit runs, but the outdoor unit does not
Have you waited long enough for the protective time delay? Is the indoor unit flashing a light or showing an error code? Look the code up in the manual; many codes are communication errors between the two units.
Switch off the power and open both terminal boxes: does the interconnecting cable have loose screws, mismatched numbers (2 to 3), or a hidden break from being crushed by a clamp or chewed by rats? Measure the continuity of each core again.
If the cable, connections and voltages are all good and the outdoor unit still does not run, hand it over to the refrigeration technician.
Dividing the work with the refrigeration technician and the homeowner
Task | Electrician | Refrigeration technician | Homeowner |
|---|---|---|---|
Dedicated circuit, breaker, residual current protection | Does it | Reports requirements from the manufacturer’s manual | Approves the plan and cost |
Earthing | Does it, tests it | Connects to the unit terminal if agreed | Agrees to the work if the house has none |
Interconnecting cable between the two units | Connects it or checks the connections, tests it | Usually runs it together with the copper pipes | |
Copper pipes, vacuuming, refrigerant charging | Does not do it | Does it | |
Test run | Measures voltage and current | Checks cooling and pressures | Accepts the work |
Before taking the job, ask the client for the unit model, whether they still have the manual, which refrigeration technician is installing it and who is buying the cable; your quote should state clearly what you will and will not do (see the lesson on quoting, taking on jobs and working with clients).
Real-life example: The refrigeration technician has already connected the interconnecting cable himself and messages the electrician that he “only needs to run the supply”. The electrician still opens the terminal boxes to check and finds that cores 2 and 3 are swapped at the outdoor unit. He corrects them and tests continuity before energizing, avoiding a communication error and an argument about who is responsible.
Safety checklist before handover
The breaker was switched off, a warning sign hung and the circuit verified dead before connecting.
A dedicated circuit and dedicated breaker at the manufacturer’s recommended rating; no extension leads.
Power and interconnecting cables of the correct type, cross-section and number of cores per the manual.
Wired to the model’s diagram; terminal numbers match at both ends; each core marked.
Earth connected to both units and continuity tested back to the earth bar; suitable residual current protection fitted.
No exposed copper, screws tight, the cable clamp gripping the sheath, terminal box covers closed.
Outdoor cables protected from the sun, with a drip loop.
Continuity, short-circuit and insulation tests (with the cable disconnected from the units) done before energizing.
Test run only after the refrigeration technician confirms the pipework is finished.
Voltage and running current measured and recorded on the handover sheet.
The homeowner has been shown the air conditioner’s breaker and told to switch it off before cleaning the unit.
Frequently asked questions
If the air conditioner comes with a plug, can it go into an ordinary socket?
Some small units come with a plug. In that case, still provide a dedicated earthed socket on a dedicated circuit, with the socket and plug rated for the unit’s current; no extension leads. If the manual requires fixed wiring through a breaker, follow the manual.
If L and N are swapped at the indoor unit, will it still run?
Some units still run; others show an error. Even if it runs, the fuse and switching circuits inside the unit are then on the neutral, and parts of the circuit you think are safe are still live. If the wiring is also swapped at the board and the breaker only switches one pole, the unit stays live even with the breaker off. Always connect L and N correctly according to the diagram and check again.
If there is an RCBO, is earthing still needed?
Yes. Earthing provides a path for leakage current to earth and reduces the voltage on the casing if a live part touches it; the RCBO detects the leakage current and cuts the power. The two complement each other; one does not replace the other.
Practice exercises
Exercise 1: Reading labels. Photograph the rating labels of two air conditioners from different brands. Record the voltage, rated current, maximum current and power input; look up the manual by model to find the recommended breaker, cable cross-section, which unit receives the supply and the terminal markings.
Exercise 2: Continuity of an interconnecting cable. Take a length of multi-core cable and number both ends. One trainee secretly shorts two cores at one end; the other uses a multimeter to find which pair is shorted.
Exercise 3: Wiring on a practice board. The board has a breaker, two numbered terminal blocks simulating the two units, and earth terminals. Wire according to the diagram the instructor provides (changing the diagram each time), make a drip loop and use the cable clamps. Do the dead tests, have the instructor check, and only then energize and measure voltage. Use a clamp meter to measure the current of a small load: clamp one core, then clamp the whole two-core cable, and explain the result.
Pass criteria:
Read the label correctly and find the wiring diagram for the model.
Match terminal numbers at both ends, earth both units, neat wire ends, tight screws.
Complete all dead-test steps before energizing.
Distinguish cable faults from faults that must go to the refrigeration technician, and do not do the refrigerant work yourself.
Related lessons to study next: how to choose cable cross-sections and circuit breakers for each circuit in the home and installing a home distribution board: arranging MCBs, RCBOs and safe earthing.