"Every time I turn off the kitchen tap there's a 'clunk' inside the wall, and the same when the washing machine finishes filling." Plumbers get this call quite often, especially from lower-floor apartments in apartment buildings and from houses with booster pumps. Each bang is a pressure surge running along the pipework; over time it can loosen threaded joints, cause leaks at flexible connector hoses, damage float valves and solenoid valves, and make pipes knock against and crack the plaster.
By the end of this lesson, you will be able to distinguish water hammer from other pipe noises, measure the pressure to find the root cause, secure loose pipes, install pressure-reducing valves and water hammer arrestors in the right places, and deal with check valves slamming shut on pump lines.
Every device has its own pressure limits and installation method: the manufacturer's instructions and the building's design documents always take priority over this lesson.
Safety before you start
Shut off the water and relieve the pressure: close the branch valve or main valve and open the lowest tap to release the pressure. Only undo connections once the gauge reads 0. Have a bucket and rags ready.
Isolate the pump's power at its own circuit breaker (or unplug it) before removing the check valve, pressure switch or discharge line; hang a "Under repair, do not switch on" sign.
Hot water: switch off the water heater's circuit breaker and run the water until it is cool before working on the hot line, to avoid scalding.
Never chisel into a wall until you know where the pipes and cables run.
Never adjust or remove the building's shared pressure-reducing valve, or the water utility's valves and meters. If the supply pressure is too high, report it to the building management and note it on the job sheet.
Never remove or plug the water heater's safety valve, even if it drips after you change the pipework.
What water hammer is and why pipes "bang"
When a tap is open, the whole column of water in the pipe moves toward the tap. If the valve closes suddenly, the mass of water is stopped almost instantly; its kinetic energy turns into a pressure wave that spikes at the valve and then bounces back and forth along the pipework several times until it dies out. The wave makes the pipe jerk and knock against the wall, producing a "clunk" or "thud". That is water hammer.
Hydraulics textbooks describe the pressure rise when flow stops instantly with the Joukowsky equation: ΔP ≈ ρ × a × Δv (ρ: density of water, a: wave speed in the pipe, which depends on the material and wall thickness, Δv: change in flow velocity). On site, you only need to remember three points:
The faster the water flows, the harder the bang. High supply pressure means higher velocity, so reducing the pressure is very effective.
The faster the valve closes, the harder the bang. Lever taps, quarter-turn ball valves, and the solenoid valves in washing machines, dishwashers and water purifiers are the usual culprits.
Loosely supported pipes turn pressure surges into movement and banging.
So there are three ways to tackle it: reduce the velocity (lower the pressure), slow down or absorb the surge (close valves slowly, fit water hammer arrestors), and secure the pipes. Usually you need to combine two or three of these.

Figure 1. A recessed washing machine valve box in a house abroad: each valve is fitted with a small stainless-steel tube-type water hammer arrestor, with braided stainless-steel hoses running to the washing machine. The arrestors are placed right next to the valves to absorb the surge when the washing machine's solenoid valve closes. (Photo: Tony Webster, Wikimedia Commons, CC BY 2.0; product labels blurred)
Not every noise is water hammer
Do not fit a water hammer arrestor the moment you hear a pipe make a noise. Typical water hammer is one or a few "clunks" or "thuds" right as a valve closes. Other noises have other causes: loose pipes knocking against the wall, whistling when water flows through a restriction, air in the pipes after a supply cut, hot pipes expanding, a check valve slamming shut when a pump stops, a cistern float valve vibrating. The reference table at the end of the lesson helps you tell them apart quickly.
Tools and materials to prepare
A water pressure gauge with a threaded fitting that attaches to a tap or the washing machine valve outlet. Check the units on the gauge face (bar, kPa, MPa or psi) before reading.
Spanners, an adjustable wrench, PTFE tape, a pipe cutter; a flashlight; a mechanic's stethoscope or a long screwdriver to listen to the pipes; a phone to record video of the noise.
Rubber-lined pipe clips, wall plugs and screws, sleeves or padding for sections passing through walls.
Depending on the cause: a pressure-reducing valve, water hammer arrestors, a spring check valve, a float valve, tap washers.
Rags, a bucket, gloves.
A 7-step procedure for finding the cause and fixing it
Step 1. Ask the customer and reproduce the noise
Ask the customer:
When does it bang: when closing which tap, when the washing machine or dishwasher finishes filling, after flushing the toilet when the cistern is full, when the pump cuts out?
How long has it been banging: since moving in, or since replacing a tap, installing a water purifier, installing a pump or repairing the pipework?
At what time of day: if it is louder at night, the supply pressure may be higher when fewer people are using water; measure the pressure at both peak and off-peak times.
Are there any leaks, swollen flexible hoses, or an unusually dripping water heater safety valve?
Then reproduce it yourself: open each tap fully and snap it shut, let the washing machine fill, flush the toilet, switch the pump on and off; listen, record video and note which action causes the noise.
Step 2. Measure the static pressure and watch the gauge on quick closure
Attach the gauge to a tap near the main valve or to the washing machine valve outlet, close all the other taps and read the static pressure. Open another tap fully and read the dynamic pressure. Snap that tap shut and watch the needle: if it jumps and then oscillates, there is a water hammer surge. An ordinary dial gauge cannot capture the true peak of the surge because the surge is very short; it only tells you there is a surge, not how big it is.
How high is too high for static pressure? There is no single figure; compare it with the pressure limits on the appliance labels and in the manuals and with the design documents. For reference, plumbing codes in some countries (for example the USA) require a pressure-reducing valve when static pressure exceeds about 80 psi (about 5.5 bar); this is a reference figure, not a regulation in Vietnam.
Quick conversions: 1 bar ≈ 100 kPa ≈ 0.1 MPa ≈ 14.5 psi, and a water column about 10 m high produces about 1 bar. So in apartment buildings fed from a roof tank, lower-floor apartments are under much higher pressure than upper-floor ones unless there are pressure-reducing valves per floor or per zone.
Step 3. Locate where the noise comes from
The noise is usually loudest where the pipe hits the structure, not necessarily at the valve that causes the surge.
Close one branch valve at a time (bathroom valve, kitchen valve, washing machine valve) and repeat the action that causes the noise. If closing a branch stops the noise, the source of the surge or the knocking point is on that branch.
Walk along the exposed pipe runs (service ceiling, service shaft, under the sink, rooftop) while someone else opens and closes the taps. Put your hand on the pipe: the section that jerks the hardest is the prime suspect.
Listen with a stethoscope or screwdriver pressed against the pipe at several points, and mark the loudest point.
For pipes concealed in walls, tap lightly and listen along the wall, using as-built drawings to work out the route. Do not chisel until you have tried all the external measures.
Step 4. Re-secure loose pipes and pipes passing through walls
If pipes rattle or there are knock marks on the wall, secure them first, because it is cheap and often noticeably reduces the noise.
Add rubber-lined clips on long sections lacking support, on both sides of elbows and tees, and close to valves and taps. Follow the pipe manufacturer's clip spacing; plastic pipes need closer support than metal pipes, especially hot lines.
Tap and washing machine connection points must be solid. If the wall elbow turns when you tighten the tap, reinforce the connection point rather than just adding more PTFE tape.
Pipes passing through walls and floors should have sleeves or soft padding and not touch brick or concrete directly.
Hot lines need room to expand: do not clamp every point rigidly on long runs; leave some clips that let the pipe slide, as the manufacturer recommends.

Figure 2. Several types of pipe clips: on the left a white plastic clip on a long threaded screw, the others metal clips lined with black rubber, some with screws locking the two halves and some mounted on threaded rod. The rubber lining helps reduce vibration transmitted from the pipe to the wall. (Photo: Ersetzbar, Wikimedia Commons, CC BY-SA 4.0)
Step 5. Reduce the pressure if the static pressure is too high
If the static pressure is high relative to the appliance limits, along with signs such as water spraying hard, swollen hoses or taps wearing out quickly, installing a pressure-reducing valve fixes the root cause.
Location: after the apartment's main shut-off valve, within the customer's own part of the system. In houses with a booster pump, decide whether the whole house or one branch needs reducing; never install a pressure-reducing valve before the pump's suction inlet.
Install in the direction of the arrow on the valve body; fit isolating valves on both sides and a Y-strainer upstream (if the valve has no built-in strainer) for maintenance.
Adjust the pressure with no taps open, a little at a time; then open the farthest and highest tap to check that the dynamic pressure is still enough for the shower, water heater and washing machine. Record the setting.
Keep an eye on the water heater: some pressure-reducing valves do not allow water to flow back into the supply. When the heater heats up, the expanding water cannot "back off" into the mains, so the pressure in the house rises and the heater safety valve may drip more. Observe over several heating cycles; if needed, ask the manufacturer about solutions such as an expansion vessel on the hot line. Never plug the safety valve.

Figure 3. A brass water pressure-reducing valve with female threads at both ends, a black adjusting knob on top and a bar-scale pressure gauge on the side for reading the downstream pressure while adjusting. (Photo: Lunosvet, Wikimedia Commons, CC BY-SA 3.0; drawing cropped out, markings on the valve body blurred)
Step 6. Absorb the surge at fast-closing valves
If the pressure is reasonable and the pipes are secure but there is still a "clunk" at an appliance that shuts off water quickly, deal with it right at the source of the surge.
A water hammer arrestor has an air chamber or spring separated from the water by a piston or diaphragm; when a surge occurs, the water pushes into the arrestor instead of hammering the pipe. Install it as close as possible to the valve causing the surge (washing machine, dishwasher, or purifier inlet with a solenoid valve, lever taps), following the orientation, size and thread specified by the manufacturer. Leak-test every threaded joint after installing.
Older houses sometimes have an air chamber: a capped vertical section of pipe behind the tap outlet that holds a pocket of air. Over time the air gradually dissolves in the water, the chamber fills with water and stops working; to restore it, shut off the water and drain the pipework so air can get back in. Sealed water hammer arrestors usually last longer.
Slowing down valve closure also reduces surges: close main ball valves and lever taps slowly; for fast-closing float valves in roof tanks and cisterns, replace them with a suitable type or adjust them to close smoothly.

Figure 4. A white plastic water inlet solenoid valve of the type commonly found in washing machines: the large threaded inlet on the left takes the supply hose, the spigot below lets the water out, and the coil and electrical connector are on top. Valves like this close very quickly and easily cause water hammer. (Photo: Lac 16, Wikimedia Commons, CC BY-SA 3.0)
Step 7. Deal with "thuds" on the pump line, air in the pipes and noisy float valves
Check valve slamming shut when the pump stops. In houses that pump from an underground tank to a roof tank, when the pump cuts out the water column in the pipe flows back and slams the check valve shut, giving a "thud" that shakes the whole riser. The usual fix: replace the swing check valve with a spring check valve (which closes early, before the backflow has time to build up speed), installed according to the pump manufacturer's instructions, and secure the riser firmly. Isolate the pump's power and relieve the pressure before removing anything.
Air in the pipes after a supply cut or pipe repair makes the water sputter and the pipes jerk. Open the taps one by one from the lowest to the highest until the water runs smoothly. If the pump keeps drawing in air, check the suction line, the foot valve and the water level in the underground tank.
Toilet cistern float valve vibrating or howling while filling (silent once the cistern is full): replace the washer or the float valve, and partly close the angle valve if the pressure is high.
Retest after the repair: repeat the actions from step 1, measure the static and dynamic pressure again, check the threaded joints with dry paper, and record the "before and after" results on the job sheet.
Reference table: identifying noises and how to fix them
Noise, symptom | Common cause | How to check | How to fix |
|---|---|---|---|
"Clunk" or "thud" right as a tap closes or the washing machine stops filling | Water hammer from a fast-closing valve, high pressure | Snap the tap shut and watch the gauge needle jump; measure static pressure | Reduce pressure, fit a water hammer arrestor, close valves slowly |
Rattling, knocking on the wall when opening or closing | Missing clips, loose connection points, pipes through walls without padding | Feel the pipe while someone opens and closes taps; look for knock marks | Add lined clips, reinforce connection points, fit sleeves |
Prolonged whistling or howling while a tap is open | Worn washer, valve not fully open, vibrating pressure-reducing valve, pressure too high | Close branch valves one at a time and listen for the source; measure the pressure | Replace the washer or valve cartridge, adjust or replace the pressure-reducing valve |
"Thud" in the riser when the pump stops | Check valve slamming shut | Listen at the valve when the pump switches off | Spring check valve, secure the riser |
Water sputtering, pipes jerking after a supply cut | Air in the pipes | Watch for air mixed in the water coming from the tap | Bleed air from the lowest to the highest point; check the pump suction line |
"Ticking" on the hot pipe when the heater switches on and off | Pipe expanding with heat and rubbing against clips or walls | Only on the hot line, when the temperature changes | Clips that let the pipe slide, not clamped rigidly, padding through walls |
Vibrating or howling in the toilet cistern while filling | Float valve vibrating, worn washer | Only noisy while the cistern is filling | Replace the washer or float valve, partly close the angle valve |
Table of parameters to measure and record on the job sheet
Parameter | How to measure or determine it | Notes |
|---|---|---|
Static pressure | Gauge on a tap near the main valve, all other taps closed | Measure at both peak and off-peak times if you suspect the pressure varies |
Dynamic pressure | Open the farthest or highest tap fully | After fitting a pressure-reducing valve, it must still be enough for the appliances |
Pressure-reducing valve setting | The valve's own gauge or a separate gauge | Record it for future comparison |
Action that causes the noise, loudest point | Note the appliance, mark it on the pipe route diagram | With video before and after the repair |
Readings differ from house to house; the table only helps you know what to measure and what to record, not standard values.
Real-life cases
Lower-floor apartment in a building fed from a roof tank. The washing machine "clunks" in the wall when it finishes filling, and the supply hose has already been replaced twice because it swelled. The plumber measures the static pressure at the washing machine valve and finds it clearly higher than the limit stated in the washing machine manual. The plumber reports this to the building management and, with the customer's agreement, installs a pressure-reducing valve after the apartment's main valve, sets it to a level the appliances accept, and fits a water hammer arrestor at the washing machine inlet. After the repair, the "clunk" is almost gone. The plumber asks the customer to keep an eye on the water heater safety valve for a few days.
Townhouse pumping from an underground tank to a roof tank. Every time the pump cuts out there is a "thud" in the stairwell, but closing the taps in the house makes no noise. The plumber isolates the pump's power, relieves the pressure and finds that the swing check valve next to the pump is worn and slamming shut. It is replaced with a spring check valve and extra clips are added to the riser; the "thud" is greatly reduced.
Safety and acceptance checklist
Water shut off and pressure relieved to 0 before dismantling; pump and water heater power isolated when working on those lines.
No interference with the water utility's valves or meters or the building's shared pressure-reducing valve.
Static and dynamic pressure recorded before and after the repair.
New threaded joints leak-tested with dry paper once pressure is restored.
Pressure-reducing valve installed in the direction of the arrow, with maintenance isolating valves; water hammer arrestors close to the appliance causing the surge.
Pipes secured firmly, with hot pipes still able to expand.
Water heater safety valve left intact.
All noise-causing actions reproduced; the noise has stopped or is clearly reduced.
Handover and advice for the customer
Let the customer listen to the noise-causing actions again after the repair and compare with the video from before. Explain briefly: "When running water is stopped suddenly, it slams into the pipe. I've reduced the pressure, fitted an absorber at the washing machine and clamped the pipes firmly."
Advise them to close the main valve and lever taps slowly, and not to adjust the pressure-reducing valve screw themselves.
Advise them to watch the water heater safety valve; if it drips more than before, call back and never plug it.
Frequently asked questions
Can water hammer burst pipes, or does it only cause noise?
Each bang is a pressure surge above the working pressure. A single one usually will not burst a pipe, but repeated every day it can loosen threaded joints, cause leaks at connections, swell hoses and damage valves.
What if it still bangs after fitting a water hammer arrestor?
Check again in this order: is the static pressure still high, is the arrestor placed right next to the appliance causing the surge, is it large enough for the branch, are there still loose pipe sections knocking against the wall, and is the noise really water hammer or a check valve, air in the pipes, or hot pipes expanding?
Should I set the pressure-reducing valve really low to be safe?
No. Pressure that is too low makes the shower weak, and washing machines and water purifiers may show error codes. Adjust a little at a time, check the dynamic pressure at the farthest tap and compare it with the minimum pressure in the appliance manuals.
Is the "ticking" from hot water pipes when the heater switches on water hammer?
Usually not. It is the sound of the pipe expanding or contracting as the temperature changes, rubbing against clips or the wall. Fix it with clips that let the pipe slide and padding where it passes through walls; no water hammer arrestor is needed.
Practice exercises
On a pipework model in the workshop, attach a gauge to a tap outlet, read the static and dynamic pressure, and convert them to bar, kPa and psi.
Snap a lever ball valve shut, then close it slowly, and record the difference in the gauge needle and the noise.
Remove two clips from a long section of pipe, try a quick closure, then refit lined clips and compare.
Prepare a survey sheet for a hypothetical "noisy pipes" job: the action causing the noise, static pressure, dynamic pressure, location, likely cause, proposed fix, and advice for the customer.
Self-assessment criteria — you pass when:
You can distinguish water hammer from loose pipes, air in the pipes, hot pipe expansion, a slamming check valve and a noisy float valve.
You always shut off the water, relieve the pressure and isolate the power to equipment before dismantling.
You measure and record the pressure before and after the repair, and can explain to the customer why you chose that fix.