Load calculator → circuit breaker & wire size

Add up appliance power to get the current, the circuit breaker and the minimum copper wire. Single phase 220 V, PVC-insulated copper wire in conduit inside the wall.

1. What are you sizing?

2. Appliances

Power is on the rating plate (W or kW). Defaults are typical values; change them to match the real label.

No appliances yet. Pick one above and press Add.

3. Existing wire and breaker (if known)

The mm² size is printed on the cable sheath, e.g. "2 × 2.5" means 2.5 mm². Switch the breaker off before checking the wire.

Result

Add at least one appliance to see the result.

Golden rule: the breaker protects the wire, not the appliance. If a breaker keeps tripping, find the cause (overload, short circuit, earth leakage) — never fit a bigger breaker before checking the wire. Results are a guide; a qualified electrician must check the real installation.

Learn more

Want to do this job yourself?Start the Residential electrician roadmap: safety, testing, choosing wire and breakers, fitting a distribution board.

Method: I = P ÷ (220 V × cos φ); 25% margin for long-running loads and the main breaker; wire per IEC 60364-5-52 / TCVN 9207 (method B1, 40 °C), voltage drop ≤ 3%.