Water heater sizing: tank, breaker, cable
Know how many people shower back to back in the evening and how cold the winter water gets, and you can pick a tank that is just right — no waiting for hot water, no power wasted heating a tank that is too big.
1. Peak hot water use
~40 L warm water each
~120 L each
2. Where is the cold water from?
3. Heater and cable
m
Measured along the cable route, one way
Result
- Tank to buy
- 75 L
- Needs ~65 L of 70 °C water
- Full heat-up
- ~121 min
- Switch on before showers
- Circuit breaker
- 16 A
- 30 mA RCBO (shock protection)
- Copper cable
- ≥ 2.5 mm²
- Current ~12.6 A
Needs 120 L of 40 °C warm water. An instant water heater for one shower (4 L/min) would need ~7 kW.
Cold water at 15 °C: a 4.5 kW instant heater will not keep a full shower warm. In a northern winter use a storage tank.
Must do: the heater must be earthed and have its own 30 mA RCBO/ELCB. Let the safety valve drain; never block it. Switch the heater off while showering if it has no shock protection.
Learn more
- Installing the water pump, rooftop tank and water heater in a townhouse the right wayRead
- Water heater leaking, safety valve dripping or no hot water: 7 steps to checkRead
- Installing hot and cold water supply pipes and pressure testing before plasteringRead
- How to choose wire size and circuit breakers for every circuit in a houseRead
Method: 70 °C water needed for 40 °C mixed water = V × (40 − t cold) ÷ (70 − t cold), plus 20% mixing losses; heat-up time = V × 4.186 kJ × ΔT ÷ (P × 95%); breaker and cable as in the Load calculator (IEC 60364-5-52).