A client rings: "the bedroom sockets have stopped working". Has the breaker tripped? No, every switch in the board is still up. The lights and the fridge work, but the charger, the fan and the bedside lamp in one room are dead.
This is one of the most common call-outs in residential work, and it is different from a breaker that keeps tripping or a socket that gets hot. Somewhere between the board and the dead socket a conductor has simply stopped making contact: an open circuit. This guide gives trainee electricians in Vietnam (single-phase, nominally 220–230 V, 50 Hz) a step-by-step procedure to find exactly where, without guessing, without pulling every socket off the wall, and without getting hurt.
Scope and safety. This article covers fault-finding on an existing socket circuit where sockets have no power but no protective device has visibly tripped. It does not cover the supply side of the meter, work inside the distribution board beyond operating its switches, or new circuits. Mains voltage can kill. Learners should take readings and open sockets only under the supervision of a qualified electrician, and must isolate and prove dead every terminal before touching it. Voltages here are for reference only; your tester's instructions, the manufacturer's instructions and local rules come first.
Why a socket can be dead while the breaker stays on
A miniature circuit breaker (MCB) responds to too much current: overload or short circuit. A residual current device (RCD, RCCB or RCBO, often called "aptomat chống giật" in Vietnam) responds to current leaking to earth. An open circuit causes neither: current simply stops flowing beyond the break, so the protective devices see less load, not more, and have no reason to trip.
The line (L) conductor is open
Nothing beyond the break has any voltage, and testers show nothing at either hole. This is the easiest fault to read.
The neutral (N) conductor is open
Line still reaches the socket, so a voltage indicator lights on the line hole, but current has no way back, so nothing works. Worse, if an appliance on the dead section is switched on, the neutral hole becomes live through the appliance, and a neon tester may light on both holes. A broken neutral turns a conductor you expect to be safe into one that can shock you. Treat every conductor on such a circuit as live until proved dead.
A connection is failing but not yet fully open
A loose screw or weak push-in terminal can work intermittently, cutting in and out when someone bumps the plug or the wall. A poor connection carrying load can also overheat; if you find discolouration or a burning smell, treat it as a heat fault too (covered in a separate nambin.com article on hot sockets).
Tools and preparation
Minimum kit
A two-pole voltage tester or a digital multimeter with suitable test leads (shrouded probes, finger guards). Check that the meter and leads are rated for mains work; the measurement category and voltage are printed on them (many electricians use CAT III 600 V or higher for building wiring; treat this as a reference, not a rule).
A proving unit or a socket you know is live, to check your tester before and after every dead test.
A plug-in socket tester (useful, but see its limits below).
A non-contact voltage tester (NCV pen) for quick tracing only, never for proving dead.
A known-good small load, such as a lamp.
Insulated screwdrivers, a torch, a lock-off device or tape and a "Do not switch on" tag, plus spare sockets and connectors.
Questions to ask the client first
A two-minute conversation often saves an hour of testing:
Exactly which sockets are dead? Are any lights affected?
What happened just before: a storm, a burning smell, a crackle, a plug that sparked?
Any recent work: drilling for a shelf or TV, a new air conditioner, ceiling or plaster repairs?
Does it come and go, or is it completely dead?
Are there other boards, for example a small board on each floor, as in many Vietnamese tube houses?
Recent drilling, an intermittent fault or a burning smell point towards a damaged or failing connection.
The 8-step procedure
Work in order; each step rules out a group of causes before you open anything.
Step 1: Prove the appliance, not the socket
Plug a known-good small load into the "dead" socket. Then plug the client's appliance into a socket you know is working. You are checking for:
A faulty appliance or plug, or a blown fuse in a plug or adaptor (where fitted).
A power strip with its own switch off, its overload button tripped, or a broken internal connection.
An adaptor or worn socket whose contacts are not touching the plug pins.
If the known-good load works, the socket is not dead; the fault is in the appliance or the lead.
Step 2: Check for switches that control the socket
Many sockets in Vietnamese homes have a switch on the same plate, and some, for example for a water heater or air conditioner, are fed through a separate wall switch or double-pole isolator. Check the switch on the plate (and which way is ON), any unlabelled switch nearby and any appliance isolator. A socket whose switch someone turned off is a common "fault".

Figure 1. A combined switch plate with fan regulators, rocker switches and a socket. On plates like this, a switch next to the socket may control it, so check every switch before you condemn the socket. (Photo: Swethasakthivel, Wikimedia Commons, CC0)
Step 3: Look properly at the distribution board
"The breaker hasn't tripped" usually means "the MCBs are all up". Look again, carefully:
The RCD or RCCB. One RCD often protects several MCBs. If it has tripped, every circuit after it is dead although each MCB still shows ON. (An RCBO combines both functions for a single circuit.)
The middle position. Some breakers stop in a middle position when they trip, which can pass for ON. Push the handle fully OFF, then ON.
Other boards. A sub-board on another floor, a breaker beside the air conditioner or a water heater's own RCD may be what tripped.
Wrong labels. Board labels may be missing or wrong; do not assume which breaker feeds the dead socket.
If you find a tripped device, reset it once. If it holds, you still need to find out why it tripped. If it trips again, do not keep resetting it: there is a real fault, and you should switch to the procedure for tripping breakers.

Figure 2. A two-pole residual current device (RCD) marked 16 A, 0.03 A (30 mA) and 230 V. In many homes one RCD feeds several MCBs, so when it trips, every circuit after it goes dead even though their own breakers still show ON. (Photo: Diermaier, Wikimedia Commons, CC0)
Step 4: Map the dead area
Go round the room and the rooms next to it with your known-good load, and mark every working and dead socket on a quick sketch.
In most homes, sockets on one circuit are connected one after another (loop-through or "daisy-chain" wiring): from the board to the first socket, then from that socket's terminals to the next, sometimes via a junction box in the ceiling or wall. This means:
If the fault is a single dead socket in the middle of a run with working sockets on either side, the fault is most likely at that socket, or at its own branch.
If several sockets are dead in a row, the break is usually at the last working socket or the first dead socket, because that is where the conductors to the dead section are connected.
If the dead sockets are not next to each other, suspect a junction box that feeds both, or a different circuit layout from what you assumed.
Your aim is to name two places: the last good point and the first dead point.

Figure 3. The back of a double socket with its cover removed. According to the photographer, the feed cable enters at the top and a second set of conductors leaves at the bottom to supply the next sockets. With loop-through wiring like this, one poorly clamped terminal can kill every socket further along the run. (Photo: Maasaak, Wikimedia Commons, CC BY-SA 4.0)
Step 5: Test the dead socket from the front
Take readings at the first dead socket from the front, without removing it. The circuit may be live, so use proper equipment, keep your fingers behind the probe guards and work under supervision.
Prove your tester first on a known live socket or proving unit.
Measure L–N, L–PE (earth) and N–PE. On a two-pin socket you can only measure L–N, unless your supervisor shows you a known earth point.
Prove your tester again. If it failed in between, your readings mean nothing.
Use the reference table below to interpret the readings. Two limits:
Ghost voltages. A high-impedance digital meter can show a few volts, even tens of volts, on a disconnected conductor running next to a live one (capacitive coupling). A two-pole tester or a meter's low-impedance (LoZ) mode usually shows this as close to zero. Confirm before calling a conductor live or dead.
Plug-in socket testers show a pattern of lights, not voltages. Some faults, such as an open neutral with a load connected, can fool them, and many are of little use on a two-pin socket. Read your tester's legend and confirm anything odd with a two-pole tester or meter.
A non-contact tester is handy for tracing roughly where a live conductor stops along a wall, but it says nothing about the neutral and can give false readings either way. Never use it to prove a circuit dead.
Step 6: Isolate, lock off and prove dead
From here on you will touch terminals, so the circuit must be dead.
Switch off the circuit's MCB or RCBO (or the main switch if unsure).
Lock it off, or tape and tag it "Do not switch on – work in progress", and tell everyone in the house.
Prove your tester on a known live source.
At the socket you will open, test L–N, L–PE and N–PE. All must read zero (allowing for a small ghost reading on a high-impedance meter, which you confirm with a two-pole tester).
Prove your tester again.
Remember the open-neutral warning: unplug everything on the dead section, and test every conductor in the box, not just the ones you expect to be live. If a box contains more than one circuit, isolate them all.
Step 7: Open and inspect the last good and first dead points
Pull the socket forward gently, so you see the connections as they were. Look for:
Loose screw terminals. A conductor that pulls out with a light tug, a screw that turns easily, or a conductor clamped on its insulation instead of bare copper.
Push-in (back-stab or spring) terminals. They work when used as the manufacturer intends (correct conductor type, size and strip length), but a conductor that is too thin, stranded without a required ferrule, or bent back and forth over the years can lose contact.
Two conductors under one terminal. In loop-through wiring the incoming and outgoing conductors often share a terminal. If one is poorly clamped, the socket may work while everything after it is dead.
Broken conductors. Copper nicked by a stripping tool or bent sharply can crack just behind the terminal while the insulation looks perfect. Flex each conductor gently and watch.
Signs of heat: discoloured plastic, dark marks, darkened copper, melted insulation. A connection that burned open is the end of a heat fault.
Aluminium conductors in older buildings, which need connectors approved for aluminium; ask your supervisor.
If the fault is not at a socket, it may be in a junction box: above a false ceiling, over a door, or plastered over during renovation. Follow the cable route from the last good point to the first dead point and look for boxes, cover plates or patches of new plaster. Ask the client for old photos taken before plastering, and check any recent drill holes near the route.

Figure 4. A junction box with three cables entering and the line (brown), neutral (blue) and earth (green-and-yellow) conductors joined by push-in connectors. If a box like this is hidden behind plaster or a false ceiling, an open connection in it can kill sockets in several places at once. (Photo: Dmitry G, Wikimedia Commons, CC BY-SA 3.0; cropped from a step-by-step series)
Step 8: Repair, test and explain
When you find the fault:
Cut back damaged or nicked conductors to clean copper. If heat has damaged the socket, replace it; never just re-tighten a burned terminal.
Re-terminate correctly: correct strip length, no bare copper outside the terminal, screws firmly tightened or conductors fully inserted (follow the manufacturer's instructions; some state a torque).
Where two conductors share a terminal not designed for two, consider joining them in a suitable connector with a single short tail ("pigtail") to the socket, so a loose socket terminal only affects that socket.
Tug each conductor to check it is held, and refit the socket without crushing the conductors.
Remove the lock and tag, warn everyone, and restore power.
Test every socket on the section (L–N, L–PE, N–PE and the known-good load). Where there is an RCD, press its test button, confirm it trips, and reset it.
Explain to the client in plain words what you found and did.
Reference table: readings at a dead socket
Values are for reference on a nominal 230 V supply; your actual supply may be anywhere roughly between 220 V and 230 V or a little above. "Ghost" means a small, unstable reading on a high-impedance meter that disappears on a two-pole tester or LoZ mode.
Symptom | Likely cause | Test | Expected reading |
|---|---|---|---|
Known-good load works in the socket, appliance does not | Faulty appliance, plug, lead or power strip | Try the appliance in a working socket | Socket reads normal (L–N ≈ 230 V) |
All sockets in a group dead, lights fine, all MCBs up | RCD/RCCB tripped, or breaker in middle position | Inspect board, every sub-board, appliance RCDs | 0 V at sockets until the device is reset |
No voltage anywhere at the socket | Open line conductor, or wrong breaker off | L–N, L–PE and N–PE at the socket | All about 0 V (or ghost only) |
Neon pen lights on the line hole, but nothing works | Open neutral | L–N, L–PE and N–PE with appliances unplugged | L–N ≈ 0 V or ghost; L–PE ≈ 230 V; N–PE ≈ 0 V or ghost |
Neon pen lights on both holes | Open neutral with an appliance still connected on the dead section | Same as above, then unplug everything and test again | N–PE can read close to 230 V while loads are connected; it drops when they are unplugged |
Socket works, but the tester reports "no earth" | Open or missing earth conductor (common where three-pin sockets were fitted to older wiring with no earth) | L–PE and N–PE | L–N ≈ 230 V; L–PE ≈ 0 V or ghost |
Socket works on and off, or when the plug is wiggled | Loose terminal, weak push-in terminal, worn socket contacts | Isolate, prove dead, inspect terminals; check for heat marks | Readings may vary between normal and zero while live; do not rely on them |
One socket dead in the middle of a working run | Fault at that socket or its own branch | Test it, then isolate and open it first | 0 V at that socket; normal at the sockets on either side |
Several sockets dead after drilling | Conductor damaged by the drill or a fixing | Trace the route from last good to first dead point | Normal at last good point, 0 V beyond the damage |
Worked examples
Example 1: Three bedroom sockets dead, loose loop-through terminal
Situation. Bedroom sockets A (door), B (desk) and C (bed). B and C are dead, A works, all breakers are on, no smell or heat. The route runs board → A → B → C, so A is the last good point and B the first dead point.
Testing. At B, with everything unplugged: L–N, L–PE and N–PE all about 0 V, so line is not reaching B. At A, L–N reads about 228 V.
Finding. After isolating, locking off and proving dead, the trainee removes A. The incoming and outgoing brown conductors share A's line terminal; the outgoing one comes out with a light pull, because it was clamped on the edge of its insulation.
Repair. Re-strip, join the two brown conductors with a short tail in a suitable connector, pull-test, refit and restore power. A, B and C now all read about 228 V L–N with normal earth readings.
Example 2: Kitchen socket where the tester lights on both holes
Situation. A kitchen socket is dead, but the client's neon screwdriver lights on both holes, so they think it is "full of power".
Testing. With the kettle and microwave on that section unplugged, the neon screwdriver lights only on the line hole. A two-pole tester reads L–N about 0 V, L–PE about 230 V, N–PE about 0 V: a classic open neutral. With the kettle connected, line was reaching the neutral through the kettle element.
Finding. After isolating and proving dead (every conductor, because the neutral is suspect), the trainee finds the neutrals at this socket and at the previous, working socket tight. The cable runs up into a false ceiling, where a junction box behind an access panel has a blue conductor pulled out of its connector.
Repair. Re-terminate the neutral, check the other joints, leave the box accessible and retest every socket on the section.
Example 3: "The breaker didn't trip" was not the whole story
Situation. The living room sockets are dead; the client says every MCB is up.
Finding. In Step 3 the trainee sees that the RCD feeding four MCBs, including the living room sockets, is down. The client had not recognised it as a breaker. It resets and holds.
Next steps. An RCD trips for a reason. The trainee asks what was happening at the time (a storm, the washing machine running) and recommends checking the appliances and circuits behind it for leakage.
Safety checklist
Tester proved on a known live source before and after every dead test.
Meter and leads suitable for mains work, leads undamaged, probe guards in place.
Non-contact tester used for tracing only, never for proving dead.
Circuit isolated, locked off or taped and tagged; client and household informed.
All appliances unplugged from the dead section before opening anything (open-neutral risk).
Every conductor in the box tested L–N, L–PE, N–PE; no assumptions based on wire colour. In older Vietnamese installations colours are often inconsistent.
Boxes with conductors from more than one circuit: all circuits isolated.
Damaged parts replaced, every conductor pull-tested, every socket on the section retested after repair.
Any reset breaker that trips again is left off and the fault investigated, not reset repeatedly.
When to stop and call someone more senior
Stop work, make the area safe and call your supervisor or a qualified electrician if:
You suspect an open neutral and are not sure which conductors may be live.
The fault seems to be in the board itself, such as a breaker that is ON with no voltage at its output. Testing inside a board is not trainee work.
Finding the fault means opening plastered walls or ceilings.
Heat damage extends into the box or the cable.
Lights flicker or dim elsewhere, appliances behave strangely, or voltages are unusually high or low. A lost supply neutral, especially on a multi-phase supply, can damage appliances and is an emergency.
The whole house is dead with the main switch on. Do not touch the meter or incoming supply; the client should contact the power company.
You find aluminium conductors or wiring you cannot explain.
Stopping is a professional decision, not a failure.
Frequently Asked Questions
My neon screwdriver lights on both holes of the socket. What does it mean?
Usually an open neutral with an appliance still connected to the dead section, so line voltage is reaching the neutral through the appliance. Unplug everything on that section and retest with a two-pole tester or meter.
If the breaker did not trip, does that mean the circuit is safe?
No. Breakers detect neither an open circuit nor a poor connection that is heating up, and a circuit with an open neutral can have live conductors where you do not expect them. A breaker staying on only means there is no overload, short circuit or (for an RCD) earth leakage at that moment.
My multimeter shows 30–40 V on a conductor I disconnected. Is it live?
Not necessarily. A high-impedance digital meter can show a ghost voltage on a disconnected conductor that runs alongside a live one. Check with a two-pole tester or a meter in LoZ mode. If the reading stays high under a low-impedance test, treat it as live and find out where it comes from.
Can I use a plug-in socket tester to prove a socket dead before I work on it?
No. Plug-in testers indicate wiring patterns and some faults fool them. Prove dead with a two-pole tester or suitable meter, proved on a known live source before and after, testing every conductor.
Practice Exercises
Exercise 1: Read the readings. At a dead socket you measure L–N 0 V, L–PE 231 V, N–PE 0 V with nothing plugged in. What is the most likely fault? What would you expect a neon screwdriver to show on each hole if a kettle on that section were switched on?
Exercise 2: Mark the last good point. Draw a run of five sockets fed in the order 1–2–3–4–5 from the board. Sockets 1 and 2 work; 3, 4 and 5 are dead. Mark where you would open first and explain why. What would you suspect if only socket 3 were dead and 4 and 5 worked?
Exercise 3: Test, prove, test. On a training rig, under supervision, isolate a socket circuit, lock and tag it, and prove it dead using the "prove tester – test circuit – prove tester" sequence. Explain to your trainer why a non-contact tester alone is not enough.
Exercise 4: Ghost voltage. On a training rig, under supervision, measure a disconnected conductor running beside a live one, first with a high-impedance digital meter, then with a two-pole tester or LoZ mode. Explain the difference.
Exercise 5: Client explanation. A client says, "None of my breakers tripped, so the wiring must be fine." Write a short explanation in plain words of why a socket can be dead without a breaker tripping, and what you found at their house.