"Help, a water pipe in my house has just burst, water is spraying all over the floor, what do I do now?" This is the kind of emergency call every plumber gets. Sometimes it's a PPR pipe that has been drilled through, sometimes an outdoor uPVC pipe that has become brittle and cracked, sometimes an old galvanised pipe that has rusted through. Faced with a burst pipe, inexperienced people often do things the wrong way round: rushing to wrap tape around it while water is still spraying. The right way is to shut off the water supply first and repair second.
By the end of this lesson, you will be able to close the right valve in the first few minutes, identify the pipe type and type of damage, choose between a temporary and a permanent repair, rejoin PPR, uPVC, HDPE and galvanised pipes using the correct jointing method for each, then leak-test and hand over clearly to the homeowner.
This lesson is for damage that is already visible (surface-run pipes, pipes in service ducts, concealed pipes where the tiles have already been opened up). If you only see a damp wall and don't yet know where the leak is, follow the lesson on detecting concealed leaks in walls first; don't start chiselling at random.
Safety before you start
Water and electricity are the most dangerous combination. If water is flowing near sockets, the distribution board, a water heater or a pump: switch off that area's circuit breaker (or the main breaker) from a dry place to stand. If the distribution board is already wet or you would have to wade through water to reach it: don't touch it; call an electrician or the power company.
Hot water pipes can cause burns. If a hot water line from the water heater has burst, switch off the heater, close the cold supply valve to the heater and wait for the water to cool down before working.
Wear safety glasses and gloves when cutting pipe, chiselling tiles or using pipe cement (it contains solvents, is flammable, needs ventilation and must be kept away from flames).
Don't drill or chisel any further until you know where the concealed electrical cables around the burst are.
Don't restore pressure until you are sure the joint has had enough time to cure or cool according to the manufacturer's instructions.
Step 1: Shut off the water at the right valve
The goal of the first few minutes: stop water coming out. To do that, you have to know where the water entering the burst section is coming from.
Homes supplied directly from the mains (no roof tank)
Close the nearest branch valve upstream of the burst (the angle valve under the basin, the bathroom isolating valve, etc.). This is the best option because the other rooms still have water.
If there is no branch valve or it is faulty: close the main valve after the water meter.
If the home has a booster pump: unplug it or switch off its breaker, otherwise the pump will keep pushing water out of the burst.
Homes with a gravity-fed roof tank
This is the most common mistake new plumbers make: they close the valve at the water meter and stand waiting, but water keeps spraying. The reason is that the valve after the meter only stops water going up to the tank, while the water already in the roof tank still flows down to the floors by gravity.
Close the roof tank outlet valve (usually right at the base of the tank or on the downpipe).
Switch off the pump that fills the tank so the tank doesn't keep being pumped full.
If the burst is on the line from the pump up to the roof: switch off the pump and close the valve on the delivery line.
Release the pressure after shutting off
Once shut off, open the lowest tap on that branch (the yard tap, a ground-floor tap) to drain the remaining water. If the pipe is still full of water, you can't weld or glue it.

Figure 1. A flush-mounted service box with its cover open: grey plastic pipes, red lever shut-off valves, a brass Y-strainer and two water meters. Knowing where valves like these are in advance means the water can be shut off in seconds when a pipe bursts. (Photo: Vyacheslav Argenberg, Wikimedia Commons, CC BY 4.0)
Real example
A three-storey townhouse where a PPR pipe on the second floor had been drilled through. The owner had closed the valve at the water meter but water was still spraying. The plumber went up to the roof, closed the tank outlet valve, unplugged the pump and opened the ground-floor yard tap: after a while the drill hole was only dripping, and then it stopped. Only then were the tiles opened up and the pipe repaired.
Trade tip: the first time you visit a client's home, ask about and show the owner where the main valve, the roof tank valve and the pump breaker are. It's a small thing, but clients remember it for a long time.
Step 2: Identify the pipe type and the type of damage
Once the water has stopped, dry the area and look closely at the damage. You need to answer two questions: what pipe is it and what kind of damage is it.
Identifying the pipe type
PPR: plastic pipe usually green, white or grey, with thick walls; the joints are heat-fusion welds (with a bead of plastic around the mouth of the fitting). Widely used for hot and cold water supply inside homes.
uPVC: rigid plastic pipe, usually grey or white, with solvent-cemented joints (you can see traces of cement at the mouth of the fitting) or rubber-ring joints. Common on surface-run cold supply lines, the line from the pump to the roof, and drainage.
HDPE: black plastic pipe (often with a blue stripe), fairly flexible and bendable. In homes it is often found on the section from the water meter into the house, joined with compression fittings.
Galvanised steel pipe: grey metal pipe with threaded joints. Still common in older houses, it often corrodes at the base of the threads and where the pipe touches damp walls.
Common types of damage
Type of damage | Signs | Common causes |
|---|---|---|
Small hole | A small jet of water spraying straight out | Drilled or nailed through the pipe; galvanised pipe rusted through |
Longitudinal crack along the pipe | A long crack along the pipe, water seeping out in a line | Impact; outdoor uPVC pipe becoming brittle over time; hot water in a pipe not rated for heat; sudden pressure surges |
Broken through, fully separated | Strong flow, the two pipe ends pulled apart | Heavy impact, ground settlement, pipe without support clips |
Leak at a joint | Water seeping right at the mouth of the fitting | PPR weld under-heated or misaligned; not enough cement; PTFE tape wound incorrectly on threads; compression fitting not tightened enough |
Whole section corroded | Rust, thin pipe walls, feels weak when squeezed or tapped | Old galvanised pipe, damp environment |
The type of damage tells you the cause, and the cause determines the repair: if a uPVC pipe cracked from sun exposure, the neighbouring section is also already brittle.

Figure 2. A blue surface-run outdoor plastic pipe leaking right below a T-joint: water sprays onto the wall and runs in streaks across the ground. Look closely to see whether the leak is in the pipe body or at the joint before choosing how to repair it. (Photo: Nokalfirstimeokaynaman, Wikimedia Commons, CC BY-SA 4.0)
Two more things to check
Is the pipe on either side of the burst still in good condition? Press it, tap it lightly and look at its colour; mark where it is still sound so you know where to cut back to.
Is there enough working space? Especially for PPR (you need room for the welding machine) and for concealed pipes (the tiles must be opened up wide enough). It's better to open it wide enough once than to chisel again and again.
Step 3: Temporary or permanent repair?
Sometimes it's late at night and fittings can't be bought, or the client needs water urgently. In those cases a temporary repair is reasonable, as long as you tell the client clearly that it is temporary.
Common temporary repair methods
Pipe repair clamp (a clamp with a rubber gasket lining, tightened with bolts): wraps tightly around a hole or short crack on a surface-run pipe. Choose the correct size for the pipe's outside diameter, position the rubber gasket so it covers the damage with some overlap on both sides, and tighten the bolts evenly.
Self-fusing silicone tape (stretched and wound in overlapping layers, it fuses into a single layer): wind it tightly, overlapping the edges, covering well beyond the damage. Suitable for small holes at low pressure.
Epoxy putty stick (two-part, kneaded together): fills small holes in metal pipes after the water has been shut off and the area cleaned and dried. Choose a product clearly labelled as suitable for water pipes and read the curing time on the packaging carefully.
Limits of temporary repairs
Never plaster or tile over a temporary repair. Every temporary repair must be left exposed so it can be monitored and replaced later.
Don't use them on hot water pipes unless the product clearly states it can withstand that temperature.
Electrical tape, ordinary tape, plastic bags tied with wire and so on are not repairs; they just hide the damage.

Figure 3. A temporary repair you should not do: the T-joint on a copper pipe is wrapped thickly in tape and sealant, while just above it the pipe has developed a new hole. (Photo: Syced, Wikimedia Commons, CC0)
The old damage was wrapped thickly, hiding the joint, and right next to it the pipe has developed a new hole. When you see this, propose replacing the whole section of pipe rather than wrapping more around it.
Step 4: Permanent repair for each pipe type
The general principle for every pipe type: cut out the damaged section completely back to sound pipe, then rejoin using the correct jointing method for that pipe type. Don't mix jointing methods: don't apply uPVC cement to PPR pipe, and don't heat-weld uPVC pipe.
PPR pipe: cut out the damaged section and weld in a coupling
Drain the pipe dry. PPR can't be welded with water still in the pipe: water meeting the hot welding die stops the weld melting evenly and makes it prone to leaks. Drain all the water and let the pipe dry; if the pipe slopes, keep the low end pointing down.
Cut square through the damaged section with plastic pipe cutters, back to sound pipe.
Measure the gap between the two pipe ends. For a small gap, use a single coupling. For a longer gap, use two couplings with a new piece of pipe inserted between them.
Mark the weld depth on the pipe end according to the depth of the fitting socket.
Weld at the correct temperature and time for the pipe diameter (see the PPR welding lesson on NAMBIN and the pipe manufacturer's table). Push in straight along the axis, and don't twist after insertion.
Where it's too tight to get the welder onto both ends at once: weld one end first, then the other, or use a weld-on union so it can be assembled in parts. Never bend the pipe to make room.
For a small hole from a drill, some manufacturers offer a pipe repair welding kit (ream the hole wider and weld in a repair plug). Only use it if you have the manufacturer's own kit and the hole is within the size the manufacturer allows. If unsure, cut out the section and weld in a coupling.

Figure 4. Ratchet plastic pipe cutters: they cut small PPR, uPVC and HDPE pipes cleanly and squarely without producing much swarf like a saw. (Photo: M338, Wikimedia Commons, public domain)
uPVC pipe: cut out the section and cement in a coupling
The basic solvent-cementing technique (cut square, deburr, apply cement evenly to both surfaces, push straight in and hold still) is covered in the lesson on welding PPR and cementing uPVC. The particular difficulty with a repair is that the two existing pipe ends are fixed and can't be pulled apart.
Use a repair coupling (a type without a central stop, so it can slide completely onto one pipe end): apply cement, slide the coupling back onto one end, then push it across onto the other end so it is centred. Work quickly, because the cement sets fast.
For surface-run pipe with clips: you can loosen the clips to move one pipe end out slightly, fit an ordinary fitting, then clip it back. Don't bend rigid pipe excessively.
The surfaces must be dry. Pipe cement won't bond to a wet or greasy pipe surface.
Wait long enough for the cement before restoring pressure. This time depends on pipe size, temperature, humidity and the type of cement; read it on the cement tin, don't guess. Pressurised supply lines usually need longer than drainage lines.
If the uPVC pipe cracked because of long-term sun exposure, propose replacing the whole outdoor run and shielding it, painting it with protective paint or running it in a channel to avoid direct sunlight.
HDPE pipe: compression fittings
Cut out the damaged section squarely with cutters or a saw and deburr.
Choose a compression coupling of the correct size for the pipe's outside diameter.
Loosen the nut and insert the pipe end all the way (mark the insertion depth beforehand to check).
Tighten the nut as the fitting manufacturer instructs (usually hand-tight, then a further turn with a special spanner). Overtightening can crack the plastic nut.
HDPE pipe is flexible and tends to pull out if the ground settles or the pipe is under tension: check that the pipe isn't under strain after jointing.
Galvanised pipe: deal with threads, replace a section or switch to plastic pipe
Leak at a threaded joint: undo the joint, clean the threads, and rewrap PTFE tape in the direction the thread screws in (looking at the end of the thread, wind clockwise for a right-hand thread); wind it tightly with enough layers to fill the thread while still seeing the thread shape. Screw it in, and don't back it off after tightening, as that opens up the tape.
Pipe body rusted through: check the neighbouring section. Corroded galvanised pipe is usually corroded along a whole section, not just at one point. Replace the section with new pipe and a union, or use a threaded adaptor to connect to plastic pipe (PPR, HDPE) for the new section.
Pipe corroded in many places: tell the client the whole run should be replaced. Repairing one spot at a time will never end.

Figure 5. PTFE tape being wound onto a brass male thread: the tape is wound tightly, covering the thread completely while the thread shape is still visible underneath. (Photo: Tomwsulcer, Wikimedia Commons, CC0)
Pipes concealed in walls and floors
Open up the tiles wide enough to have room to cut and joint, not just over the leak itself.
After repairing, pressure-test before plastering and tiling again (step 5). Discovering a leak after plastering means chiselling a second time.
If the wall has a waterproofing layer (bathrooms), restore the waterproofing before tiling.
Step 5: Leak-test and turn the water back on
Turn the water on slowly
Close the taps that were opened for draining earlier, leaving only one tap open at the highest point to bleed air.
Open the valves (main valve, roof tank valve) slowly, not all at once. Opening suddenly can cause water hammer, which can jolt the joint you've just made.
When the bleed tap runs steadily without spluttering air, close it.
Switch the pump (if any) and the water heater breaker back on only after the hot water line is full of water.
Check for leaks
Wrap dry tissue paper around each new joint and wait a few minutes: if the paper stays dry, it has passed the first check.
Read the water meter: with all taps closed, the meter must stay still. Note the reading, wait a while, then read it again.
Concealed pipes: use a pressure test pump, raise the pressure to the test requirement for that pipe run and hold it for the specified time (see the lesson on installing water supply lines and pressure testing before plastering). If the gauge needle doesn't drop, it passes.
Step 6: Handover and working with the client
Repairing a burst pipe is an emergency job and the client is worried; the way you talk to them decides whether they call you again.
Take photos before, during and after the repair: the burst, the cut-out section of pipe, the new joint, the pressure gauge during the test.
Explain the cause in simple words: "the pipe was drilled through", "the plastic pipe was in the sun for a long time and became brittle", "the galvanised pipe corroded from the inside".
Say clearly whether the repair is temporary or permanent. If temporary: note the date you need to come back to replace it, and tell the client not to cover up the repair.
Quote separately: the emergency repair (shutting off the water, immediate action) and the complete repair (replacing a section or the whole run, opening up and restoring tiles). Don't give an all-in quote before you've examined the situation properly.
Advise the client: where the main valve and roof tank valve are; don't drill walls without knowing where the pipes run.
Reference table: repairs by pipe type
Pipe type | Correct jointing method | Possible temporary repair | Permanent repair | Conditions before restoring water |
|---|---|---|---|---|
PPR | Heat-fusion welding | Correctly sized pipe repair clamp (surface-run pipe) | Cut out the section, weld in a coupling or an insert piece; manufacturer's repair kit for small holes | Weld cooled for the time the manufacturer states (refer to the manufacturer's table) |
uPVC | Solvent cement or rubber ring | Pipe repair clamp, silicone tape (low pressure) | Cut out the section, cement in a repair coupling or a cemented union | Cement cured for the time stated on the tin for pressurised lines |
HDPE | Compression fittings (small sizes), welding (large sizes) | Pipe repair clamp | Cut out the section, compression coupling | Tightened correctly, pipe not under tension |
Galvanised steel | Threads + PTFE tape | Pipe repair clamp, epoxy putty suitable for water pipes | Replace the section with a union, or switch to plastic pipe using a threaded adaptor | Putty cured as per the packaging; threaded joints not seeping |
Acceptance test table:
Item | Tool / how to check | Pass criteria |
|---|---|---|
New joints | Dry tissue paper wrapped around the joint | Paper stays dry after turning the water on and after one round of real water use |
Whole system | Water meter, all taps closed | The meter stays still throughout the observation period |
Concealed pipe before plastering | Pressure test pump and gauge | The needle doesn't drop during the required test time (test pressure and duration: refer to the design documents and pipe manufacturer) |
Related equipment | Pump, water heater | Running normally again; the water heater is only powered once it is full of water |
Safety and acceptance checklist
☐ Switched off the power in the flooded area (from a dry place) or confirmed there is no electrical risk.
☐ Closed the right valves (branch valve, main valve, roof tank outlet valve) and switched off the relevant pump.
☐ Drained all water from the pipe section before welding or cementing.
☐ The damaged section has been cut out completely back to sound pipe.
☐ The jointing method matches the pipe type; no mixing of cements, no heat-welding of uPVC.
☐ Waited long enough for cooling (PPR) or cement curing (uPVC) as the manufacturer instructs.
☐ Turned the water on slowly, bled the air, no water hammer.
☐ Paper is dry at every new joint; the water meter stays still with all taps closed.
☐ Concealed pipes passed the pressure test before plastering and tiling.
☐ Temporary repairs (if any) are left exposed, and the client has been told the date for coming back to replace them.
☐ Took photos, explained the cause and showed the client where the valves are.
Frequently asked questions
Can I wrap tape or use all-purpose glue on the burst pipe?
It's not a good idea. Ordinary tape and all-purpose glue can't withstand water pressure and won't stick to a wet pipe surface; they only slow the leak for a few hours. Shut off the water first, then use a pipe repair clamp or self-fusing silicone tape if a temporary repair is needed, and replace the section of pipe when you can.
Can uPVC pipe cement be used on PPR pipe?
No. PPR is polypropylene, and uPVC pipe cement can't "weld" this type of plastic. PPR pipe can only be joined by heat-fusion welding or by threaded fittings and unions designed for PPR. A cemented joint on PPR pipe may hold at first but will blow apart under pressure.
The PPR pipe has just been drained but water still seeps out at the cut. Can it be welded?
Don't weld while water is still seeping. Check the valves again: a valve may not be fully closed, or there may be another water source (the roof tank, another branch). Open the lowest tap to drain everything and wait for the pipe to dry. If an old valve won't close completely, consider closing a valve further upstream or replacing the valve before repairing the pipe.
Why does the outdoor plastic pipe crack in a new place every few months?
Plastic pipe exposed to the sun for a long time ages and gradually becomes brittle. Once the pipe is brittle, other sections are about to crack too. Replace the whole outdoor section and protect the pipe from direct sunlight (run it in a channel or a cover box, or coat it with a paint suitable for plastic pipe). If the house has a pump, also check the water pressure and whether the pump is cycling on and off constantly, because fluctuating pressure also makes pipes fail sooner.
Practical exercise
Valve map: walk around your own home or a friend's, and draw a diagram of where the main valve after the meter, the roof tank outlet valve, the branch valves and the pump breaker are. Note clearly which valve to close to cut off water to the second floor.
Repair a PPR section on the practice bench: take a section of PPR pipe with both ends welded and fixed to a frame. Drill a hole in the middle to simulate a burst. Cut out the damaged section and rejoin it with two couplings and an insert piece. Pressure-test with a hand pump and record the result.
Cement a uPVC repair coupling: on a section of uPVC pipe fixed at both ends, cut out a short piece and rejoin it with a repair coupling. Time your work and note the cement curing time from the tin before testing with water.
Client role-play: one person plays a homeowner panicking about a burst pipe at 10 p.m. You guide them over the phone on how to close the valves and switch off the power safely, then explain the plan: a temporary repair tonight and a permanent repair tomorrow.