"Can you put up a TV bracket? There's a socket right underneath, so I don't know where the wire goes." Hanging a TV or fixing kitchen shelves is a job electricians get every week. But a drill bit that finds a buried cable can trip the breaker, cause a flash inside the wall and, in the worst case, give the person holding the drill an electric shock.
This guide shows you how to locate hidden wiring before you drill: reading the wall, gathering information, using detectors and knowing what they cannot see, drilling safely near a suspected cable, and what to do if you hit one.
Scope and safety. Written for residential electricians in Vietnam and for homeowners. It covers brick and concrete walls with cables in conduit, plasterboard (drywall) partitions and suspended ceilings, on a 230 V/50 Hz supply. It is not a guide to installing concealed wiring, adding a socket or finding which breaker feeds a circuit; those have their own articles. No detector is 100% reliable. Detectors reduce risk; they do not replace looking, asking and switching off the circuits concerned. If you hit a cable: let go of the trigger, do not touch the bit or chuck, and switch the circuit off at the board. If someone gets a shock, switch off the power before touching them and call 115. Figures marked for reference are rough working examples, not rules from a standard. Always follow the instructions for your detector and drill.
Why hitting a buried cable is dangerous
In Vietnamese houses, cables usually lie in corrugated or rigid PVC conduit in a chase cut into the brick or concrete, covered with plaster, often not far below the surface. A drill bit that reaches one can cause:
An electric shock through the drill. A double-insulated drill reduces the risk, but if your hand is on a metal part (bit, chuck, metal side handle), the wall is wet or the drill body is cracked, you can still get a shock.
A short circuit and arc. The bit bridges live and neutral or earth; the breaker trips, sometimes with a bang and a scorch mark.
Hidden damage. The bit cuts the insulation but not the copper. Nothing happens at first, but later, when the wall gets damp or a wall plug presses on the damaged spot, the circuit leaks current and the RCD trips "for no reason". This is the hardest fault to find.
The rule of the trade is simple: find, mark, choose a fixing point away from the cable route, and if you cannot avoid it, switch the circuit off before you drill.
Step 1: Read the wall before you use any tool
Start with your eyes. Many cable strikes happen just above or below a socket or switch.
Cables start and end at visible points
Every socket, switch, wall light, air conditioner and water heater outlet has a cable going into a flush box. From the box, cables commonly run:
Straight up towards the ceiling, especially from switches, because the cable goes to the light.
Straight down towards the floor, when cables run in the floor slab or along the bottom of the wall.
Horizontally between sockets at the same height on one wall.

Figure 1. Two cables entering a row of green flush boxes in a white wall, before the sockets are fitted. Every cable reaches its box through the wall, so the areas around and between boxes are where buried cables are most likely. (Photo: Pavel Danilyuk, Pexels)
Cables leaving the distribution board fan out through the wall around it, so treat that whole area as cable territory.
Do not rely on "safe zones" in Vietnam
Some countries' wiring rules tell installers to run concealed cables only in defined zones: vertically or horizontally from accessories, near ceilings and corners. You may see these zones in foreign guides and videos.
Do not rely on them in Vietnam. Many houses here were wired by different teams over the years, and cables often take the shortest path: diagonally across a wall, at an angle from the ceiling down to a socket, or across the middle of a wall. Floor slabs and beams also carry conduit in directions you cannot guess. Use the patterns above as a first guess, then confirm with information and tools.
Look for clues on the surface
Chase marks. Fine straight or diagonal cracks, or a slightly different texture, can show a filled chase.
Repairs and patches. A rectangle of fresh plaster often marks an old box or a joint.
Ceiling openings. Downlights, ceiling junction boxes and inspection hatches show where cables come down into walls.
Step 2: Gather information before drilling
Ask the owner
Was the house wired when it was built, or rewired later? By whom?
Does the owner have photos or videos taken before plastering? Many builders and owners in Vietnam photograph the walls when the conduit is in place, and these photos are the best map you will get.
Have air conditioners, water heaters or sockets been added since?
Has anyone drilled this wall before, and did anything happen?
Check drawings and the board
Use any electrical drawings as a guide, not as proof; houses are often built differently. Check the board labels to see which circuits serve this room, so you know which breakers to switch off later.

Figure 2. A grey PVC conduit set into a chase in a block wall before plastering, running up to a metal flush box, with a worker's hand beside it. Once plastered, none of this is visible; a photo taken at this stage shows exactly where the conduit runs. (Photo: Korbla Johnny, Wikimedia Commons, CC BY-SA 4.0)
Look inside a box (power off)
With the circuit switched off and proved dead, an electrician can remove the cover plate of a nearby socket or switch and see whether the conduit enters from above, below or one side. This shows the first part of the cable's route. Refit the plate before switching back on.
Step 3: Choose the right detector and understand its limits
Each type of tool "sees" something different.
Non-contact voltage tester (voltage pen)
A voltage pen detects the electric field around an energised AC conductor and can sometimes pick up a live cable close to the surface.
Limits:
It only finds cables that are live at that moment. It will not find a cable that is switched off, a neutral or earth conductor, or the cable to a light after a switch that is turned off.
It may miss cables that are deep, in metal conduit or behind foil.
Damp walls can spread the field and make the pen beep over a wide area, while a dry, thick wall can hide the cable completely.
Always check a voltage pen on a known live socket before and after use. If it does not light on the known source, its battery or the pen is faulty.
Stud and cable detectors (multi-detectors)
Handheld multi-detectors usually have several modes:
Metal mode finds metal: copper conductors, steel conduit, but also nails, wall plug screws, metal lath and, in concrete, steel reinforcement bars. In reinforced concrete, it will beep over the rebar grid, so a signal does not always mean a cable.
AC (live wire) mode works like a voltage pen and has the same limits: it only finds live cables.
Stud mode finds changes in density behind plasterboard, such as timber or metal studs.
Higher-end wall scanners using radar or several sensors can also show plastic pipes, but no scanner is perfect, and detection depth depends on the wall and the target.
Cable tracer (tone generator and receiver)
A cable tracer sends a signal into a cable at a socket or switch, and you follow it along the wall with a receiver. Where routes are unpredictable, it is very useful because it shows the actual route of one cable. Most models are connected to a de-energised circuit; follow the instructions, and leave connecting it to the wiring to a competent electrician.
Step 4: Scan the wall properly
Calibrate on a clear spot
Most detectors calibrate when switched on or when you press a button while holding them on the wall. Do this on a spot you believe is clear, away from sockets and corners. If it beeps everywhere, recalibrate elsewhere. Follow the manual for your model.
Scan in a grid
Scan before switching anything off. The AC mode needs the cables to be live, so do your AC scan first.
Hold the detector flat on the wall and move it slowly in straight lines.
Scan horizontally across the whole area, then vertically, in lanes about a hand's width apart (for reference).
Where the detector signals, approach from both sides and mark the edges with a pencil. The cable is usually near the middle of the two marks.
Join the marks to see the line. A line that runs diagonally is normal in Vietnamese houses; follow it as far as it goes.
Scan a wider area than you need, so you can see where cables enter and leave the zone.
Interpret the results with care
No signal does not mean no cable. It may be dead, deep, behind metal or simply too small for the detector to pick up.
A signal does not always mean a cable. It may be rebar, a nail, a metal box, a water pipe or damp.
Combine all sources: the visual clues, the owner's information and photos, and every detector mode. Where they disagree, treat the area as "cable possible".
Step 5: Plan where you drill
Once you have marked the suspected cable routes, choose the fixing points.
Move the fixing points first. Many brackets have several fixing holes; choose ones away from the marked lines. Moving a bracket slightly is cheaper than repairing a cable.
Avoid the strips directly above, below and beside boxes, even if the detector shows nothing.
Tell the owner where the cable routes are, so the next person drilling knows.
Think about water pipes too. In bathrooms and kitchens, PPR water pipes run in walls and floors, often near the cables for the water heater and washing machine, and a metal detector does not see plastic pipes. Note where taps and heater connections are, and see our separate plumbing guide on locating pipes in walls before drilling.
Step 6: Switch off before drilling near a suspected cable
If you must drill inside or close to a zone where a cable could be:
Finish scanning first. Once the power is off, the AC mode and voltage pen will no longer find the cables.
Switch off the circuits that serve the area at the distribution board. If you are not sure which circuits run through the wall, switch off the main switch.
Prove it dead. Check with a voltage tester on the sockets and lights in that area, and check your tester on a known live source before and after.
Stop others switching it back on. Put a note on the board, close the cover and tell everyone in the house. Where the board allows, lock it off.
Plan for no power. Use a battery drill or a socket on a circuit you know does not run through this wall.
Switching off reduces the risk of shock and arcing but does not stop you damaging the cable, so still drill carefully. An RCD or RCBO adds protection against shock, but is not a reason to skip these steps.
Step 7: Drill with the right technique
Prepare the drill and yourself
Use a drill in good condition, preferably double-insulated, with no cracks in the body and no damaged lead.
Hold it only by its insulated grips. Keep your hands off the chuck and the bit while it is running.
Wear eye protection, and a dust mask when drilling masonry. Work from a stable step or ladder.
Keep your hands dry and stand on a dry floor.
Set a depth stop
Use the depth rod on the drill's side handle, or a stop collar on the bit, so the hole is only as deep as the wall plug needs plus a small margin. Measure the plug against the bit before you start. Controlled depth reduces the chance of reaching a deeper cable.
Drill carefully
Use the bit size and type the wall plug and the wall need.
On ceramic tiles, start without hammer action until you are through the tile, then switch to hammer action for the brick or concrete if needed.
Drill straight and let the drill do the work; do not lean your whole weight on it.
Watch and listen. Stop immediately if the bit suddenly drops forward (it may have entered a conduit or a void), if coloured plastic or copper appears in the dust, if you see a spark, or if the lights go off.
Plasterboard walls and ceilings
In plasterboard partitions and suspended ceilings, cables often run loose or in flexible conduit between studs or lie on top of the ceiling boards. Use the stud mode to find the frame, keep away from areas above and below boxes, and use hollow-wall fixings. Where possible, look into the cavity through an existing opening, such as a downlight hole, with the power off.
Step 8: What to do if you hit a cable
Immediately
Let go of the trigger. Do not touch the bit, the chuck or any metal part.
Do not pull the drill out with your hands on metal. Leave it where it is for now.
Switch off at the board. Switch off the circuit, or the main switch if you do not know which circuit it is. If the breaker or RCD has already tripped, leave it off.
If anyone has had a shock, switch the power off before touching them, call 115 and give first aid if you are trained.
Check the damage
With the power off and proved dead, remove the drill and look into the hole with a torch for coloured insulation shavings, copper fragments or soot.
Even if nothing happened, the insulation may be cut. Do not just switch back on and hope. Have an electrician test the circuit, including an insulation resistance test, before it goes back into use. We have a separate guide on insulation resistance testing.

Figure 3. A two-pole voltage tester with indicator lights for different voltages and a second probe on a lead, on graph paper (maker's logo blurred). Before touching a damaged cable, an electrician proves the circuit dead with a tester like this, checked first on a known live source. (Photo: Dmitry G, Wikimedia Commons, CC BY-SA 3.0)
Repair it properly
Never wrap a damaged cable in tape and plaster over it. A taped joint buried in a wall cannot be inspected, can loosen, overheat or let in moisture, and causes trouble later when nobody remembers where it is.
The proper repair is decided and carried out by a qualified electrician. The usual options are:
Replace the damaged cable between its two ends. If it runs in conduit, a new cable can often be pulled through without breaking the wall (see our guide on replacing concealed wiring).
Make a joint in an accessible junction box. The damaged section is cut out and the joint made with suitable connectors in a box with a removable cover that stays accessible.
Reroute the circuit if the damaged route cannot be repaired properly.
After the repair, the circuit must be tested before it is switched on, and the RCD tested with its test button.

Figure 4. Two round junction boxes with screw terminal blocks, wired by a student at an electrical school in the Czech Republic. In a real repair, the joint is made in a box like this, closed with its cover and left accessible, never wrapped in tape and buried in a wall. Colours and accessories in Vietnam may differ. (Photo: 01x07x2022000, Wikimedia Commons, CC0)
Reference table: detection methods compared
Method | What it can find | What it can miss or confuse | Best use |
|---|---|---|---|
Reading the wall (boxes, board, surface clues) | Likely routes from accessories | Diagonal or unusual routes | First step on every job |
Owner's photos before plastering, drawings | Actual conduit routes at the time | Later changes; drawings may not match the house | Best map if available |
Non-contact voltage tester | Live cables close to the surface | Dead cables, neutrals, switched-off light feeds, metal conduit, deep cables; false alarms on damp walls | Quick check near accessories |
Multi-detector, metal mode | Copper, steel conduit, nails | Rebar, metal lath and screws give false signals; small deep cables missed | Plastered brick walls |
Multi-detector, AC mode | Live cables | Same limits as a voltage pen | Combine with metal mode |
Multi-detector, stud mode | Studs in plasterboard | Not a cable detector | Plasterboard walls and ceilings |
Cable tracer (on a dead circuit, by an electrician) | The route of one specific cable | Needs access to the cable ends; other cables nearby can confuse | Unpredictable routes |
Practical examples
Example 1: TV bracket above a socket
A client wanted a TV bracket centred above a low socket. The AC scan found a live signal running diagonally from the socket towards the ceiling corner, not straight up, and the owner's photos from before plastering confirmed it. The bracket was moved slightly to one side so all four holes cleared the line, and the socket circuit was switched off while drilling as a precaution.
Example 2: Kitchen shelf on tiles
On a tiled kitchen wall, the metal mode signalled almost everywhere: it was picking up rebar in the concrete behind the tiles. The electrician used a cable tracer on the dead socket circuit to find the real route, marked it, switched off the kitchen circuits, drilled through the tile without hammer action, then used hammer action with a depth stop.
Example 3: Curtain rail on a plasterboard partition
Before fixing a curtain rail to a plasterboard partition, the electrician switched off the circuit, removed the switch plate by the window and saw the cable leave the box sideways, not upwards. The stud and AC modes confirmed a cable running horizontally between the studs at switch height, so the rail brackets were fixed into studs well above that line.
Safety checklist
Read the wall: boxes, board, ceiling openings, surface clues.
Ask the owner about photos before plastering, drawings and later changes.
Check your voltage pen or detector on a known live source before and after use.
Calibrate the detector and scan in a grid, horizontally and vertically, before switching off.
Mark the suspected routes; choose fixing points away from them.
If drilling near a suspected route: switch off the circuits (or the main), prove them dead, put a note on the board.
Use a drill in good condition, held by insulated grips; wear eye protection and a dust mask.
Set a depth stop; drill straight; stop at any sudden drop, spark, coloured shavings or loss of power.
If you hit a cable: let go, do not touch metal parts, switch off at the board, call 115 if anyone is hurt.
Have the circuit tested and repaired properly by a qualified electrician; never tape and bury a joint.
Frequently Asked Questions
If the detector shows nothing, is it safe to drill?
Not necessarily. The AC mode cannot see dead cables, neutrals or cables after a switch that is off, and the metal mode can miss small cables that are deep. Combine the detector with reading the wall, asking the owner and switching off the circuit when you have to drill near a possible route.
Should I switch off the main switch every time I drill?
Not always. Well away from any suspected route, it is usually not needed. Near one, switch off the circuits serving that area, or the main switch if unsure. Scan and mark first, because live-cable detection stops working once the power is off.
I drilled into a cable but nothing happened. Do I need to do anything?
Yes. The bit may have cut the insulation without touching the copper. Switch the circuit off, inspect the hole and have an electrician test the circuit, including an insulation resistance test, before switching it on again.
Can I repair the cable with tape and plaster over it?
No. A taped joint buried in a wall cannot be inspected and can fail later. Replace the cable, or make the joint in an accessible junction box with proper connectors, and have it done by a qualified electrician.
Do cables in plasterboard walls need checking too?
Yes. Cables there often run loose between studs or lie on the boards, so screws reach them easily. Use the stud and AC modes, avoid the areas above and below boxes and use hollow-wall fixings.
Practice Exercises
Read the wall. Sketch every socket, switch, light and board in one room and draw where you think the cables run. List what information would confirm it.
Detector check. Test your voltage pen or detector on a known live socket, then scan a wall in a grid. Mark every signal and note which mode found it.
Limits. Scan the same area with the circuit live and then switched off. Write down what the detector stopped finding and why.
Owner questions. Write five questions to ask a client before drilling, and what each answer tells you.
Strike response. List, in order, your steps if your drill hits a cable, from letting go of the trigger to re-energising after repair.
Case study. A client wants a TV bracket on a reinforced concrete wall, and the metal mode beeps everywhere. Explain how you would find the cable route and which tools you would use.