The two most common calls about rooftop water tanks sound like opposites but share the same culprit: "Water is pouring from the pipe on the roof into the yard and the pump runs non-stop" and "This morning I turned on the tap and there was no water; the tank on the roof is bone dry". In most cases, the fault is in the float: a mechanical float valve that does not close or does not open, or an electric float switch that does not cut off or does not start the pump. But sometimes the float is fine and the fault is in the water supply, the pump or the wiring.
This lesson belongs to the "Pumps, water tanks & water heaters" step of the residential plumber roadmap. By the end of this lesson, you will be able to narrow down the fault safely, check a mechanical float valve, test an electric float switch with the power off, replace floats, adjust water levels and carry out acceptance checks before handing over to the customer.
Safety before you start
Working at height: tanks are usually on the roof or on tall steel stands. Use a sturdy ladder with someone holding it and wear non-slip shoes; do not go onto the roof when it is raining, slippery or very windy; where there is no railing, wear a safety harness.
Isolate the pump's power: electric float switches carry 220 V mains wiring. Before touching a float switch or junction box, switch off the pump's circuit breaker, verify with a voltage tester or multimeter, and hang a "Work in progress" sign.
Never touch electrical wires with wet hands or while standing in water: dry your hands and stand somewhere dry. The pump circuit should have residual current protection (RCD/ELCB); if pressing the test button does not trip it, or the float cable has cracked insulation, stop and call an electrician.
Shut off the water before removing a mechanical float valve: close the mains supply valve or the pump delivery valve, otherwise water will spray out when you loosen the nut.
Keep domestic water clean: wash your hands, use clean tools, do not let oil, grease or metal filings fall into the tank, and replace the lid as soon as you finish. Never climb into a tank or an enclosed cistern.
Underground cisterns: an open cistern hatch is a deep hole right in the walkway: have someone keep watch, put up a barrier and cover it when you leave.
Understand the system before diagnosing
Before going up on the roof, ask the customer and look at the pipework to find out which type of system the house has.
Type 1: mains water flows straight up to the rooftop tank through a float valve
Where mains pressure is sufficient, the supply pipe runs directly up to the rooftop tank and ends in a mechanical float valve (ball valve). When the water reaches the set level, the float rises and pushes the arm to close the valve. The house has no pump to fill the tank. Overflow is almost certainly caused by the float valve; no water is caused by low mains pressure at peak times, a closed valve, a blocked strainer or a float stuck closed.
Type 2: underground cistern, pump and rooftop tank (common in townhouses)
Mains water enters the underground cistern through a mechanical float valve. The pump draws from the cistern and pushes water up to the rooftop tank. The pump is controlled by an electric float switch: the switch in the rooftop tank runs the pump when the tank is low and stops it when the tank is full; many houses also have a float switch in the cistern to stop the pump when the cistern is empty, preventing dry running. These two switches are wired in series in the control circuit: the pump only runs when the rooftop tank needs water and the cistern still has water.

Common types of electric float switch
Cable-suspended float switch: a sealed plastic float hanging on a cable, containing a ball or weight and a small switch. When the float tilts up or hangs down, the switch changes state. Many types have three wires: one common wire and two wires for opposite functions (one pair closes when the float rises, the other closes when it hangs down). Wire colours vary by manufacturer, so check the diagram or measure.
Mechanical float switch mounted on the tank lid: a switch box mounted on the lid or the tank wall, with a cord hanging down carrying two floats (one upper, one lower) and a counterweight. The distance between the two floats determines the pump start and stop levels.
One important point: the float's contact is a small switch. Only wire the pump directly through the float if the pump current is within the contact rating printed on the float; if it exceeds that, the float must control the pump through a contactor. Read the pump label and the float label before drawing conclusions; rewiring the pump control panel is a job for an electrician.
7-step procedure for narrowing down and repairing the fault
Step 1. Question the customer and observe from the ground
Ask briefly and take notes:
Where is the water overflowing from: the tank's overflow pipe, the tank lid, or a joint?
When it overflows, is the pump running? When the tank is empty, does the pump run, or does it hum without delivering water?
Is the mains supply normal today?
Has anyone recently repaired or cleaned the tank or replaced the pump?
From the ground, listen for whether the pump is running, look at the overflow pipe, and check whether the water meter turns when nobody is using water. These three observations usually point the way: pump running and tank overflowing means a fault on the rooftop tank float switch side; pump off but tank still overflowing means water is entering through a float valve (type 1) or the pump is still being powered by another route; water meter turning continuously, cistern overflowing means the cistern float valve.
Step 2. Determine which route the water is entering the tank by
Switch off the pump's breaker. If water keeps flowing into the rooftop tank, it is entering from the mains through a float valve (or there is an auxiliary supply). If water stops when the pump is switched off, the overflow fault is in the pump control circuit: the rooftop float switch does not cut off, the wrong pair of wires is connected, or someone has bridged the float switch.
For the no-water symptom, work the other way round: check the source first. Is there water in the cistern? Are the valves on the suction and delivery lines open? Is the pump breaker on? Do not remove any float until you are sure the water supply and power supply are normal.
Step 3. Check the mechanical float valve by hand
Open the tank lid, watch the float while water is flowing in, then lift the float by hand to its highest position:
Lifting it stops the water completely: the valve is fine. The problem is that the float does not rise high enough: the set level is too high relative to the overflow pipe, the float has taken on water and sits low, the arm is bent, or the float is catching on the tank wall, the suction pipe or the float switch cable.
Lifting it, water still drips or flows: the valve is damaged inside: the washer is worn, hardened or torn, or scale or sand is stuck in the valve seat. Clean it, replace the valve insert or replace the float valve.
Letting it drop, no water flows in: there is mains water but the float valve does not open, usually because scale is blocking the valve orifice, the inlet strainer is clogged, or the arm is stuck in the closed position.
Shake the float gently: if you hear water sloshing inside, the float is punctured and must be replaced.

Step 4. Test the electric float switch with the power off
Switch off the pump breaker and verify there is no voltage on the float cable before you start:
Look: is the float catching on pipes, the float valve or other cables, or trapped so it cannot tilt? Is the cable sheath cracked or chewed by rats, are any joints submerged?
Disconnect the two float wires from the circuit (at the junction box, without cutting the cable). Set the multimeter to the continuity range or a low resistance range and connect it to the two wires in use.
Simulate an empty tank: let the float hang down (cable type) or pull the float assembly down to the low level (two-float type). The rooftop tank float switch must show continuity, meaning it lets the pump run.
Simulate a full tank: lift the float. The rooftop tank float switch must be open circuit, meaning it stops the pump.
Repeat several times. If it is intermittent, or still shows continuity when lifted, the contact is faulty: replace the float switch.
The cistern float switch (dry-run protection) works the other way round: float up (water present) = continuity, float hanging (empty) = open circuit. If the reading is the opposite of the intended function, the float has very likely been wired with the wrong pair of wires. For three-wire types, measure each pair and compare with the manufacturer's diagram. Never bridge the two float wires "to make the pump run": that is exactly how tanks overflow and pumps run dry.

Step 5. When the floats are fine but the pump still doesn't deliver water
If both the rooftop and cistern float switches test correctly but the tank is still empty, the fault is in the pump or the pipework. There are two cases:
Pump does not run, no sound: check the breaker, fuse, wire connections and the pump's thermal protection. Measuring voltage and checking the capacitor and motor is a job for an electrician.
Pump runs and makes a noise but delivers no water: the cistern is too low and the suction inlet is exposed; the pump has lost its prime; the suction strainer or foot valve is clogged or stuck; air is leaking into the suction line at a joint; the delivery valve is closed. Switch the pump off immediately if it is running without water, because dry running easily damages the seal. Re-prime and fix the leak before running it again.
And do not forget the simplest possibility: weak or interrupted mains supply, so the cistern is empty and the dry-run float switch is correctly stopping the pump.
Step 6. Replace the float valve or float switch
Replacing a mechanical float valve:
Close the valve supplying the float valve (mains valve or pump delivery valve) and open the tank lid.
Take the old float valve with you when buying a replacement to compare: the connection thread size (for example the thread matching "phi 21" or "phi 27" pipe — the common Vietnamese names for 21 mm and 27 mm pipe), the arm length, and whether it mounts through the tank wall or on the end of a pipe.
Undo the retaining nut, holding the valve body firmly so you don't twist the pipe or crack the hole in a plastic tank wall.
Wrap new PTFE tape in the direction of tightening and fit the washers on the correct sides of the tank wall as per the instructions supplied. Tighten by hand, then a little more with a spanner; do not overtighten on a plastic tank.
Fit the float and arm, making sure the float moves up and down freely without touching the tank wall, the suction pipe or the float switch cable.
Open the valve slowly, check that the joint does not leak, then adjust the shut-off level in step 7.
Replacing an electric float switch: choose a switch of the same type, with a contact rating suited to the pump current (see the label) and the correct pair of wires for its function (tank filling or dry-run protection). Switch off, verify it is dead and photograph the old wiring. Put wire joints in a watertight box in a dry, high position; never leave joints submerged in the tank. Secure the float cable so the float only moves within the intended range. If you are not used to electrical wiring, do the mechanical work and ask an electrician to make the connections.
Step 7. Adjust the water levels, test run and carry out acceptance checks
The shut-off level (tank full) must be some distance below the overflow pipe opening so that water does not run out of the overflow when the float shuts off. This gap is usually just a few centimetres; for the exact figure, refer to the tank and float instructions. For mechanical float valves, adjust with the adjusting screw or bend the arm slightly (on types that allow it); for cable-suspended float switches, adjust the length of the hanging cable; for two-float switches, adjust the position of the upper float.
The start level (tank needs more water) should be far enough below the shut-off level that the pump does not cycle on and off continuously. If the two levels are too close, or ripples make the float bob around the threshold, the pump switches on and off frequently and wears out quickly.
Test run at least one complete cycle: drain some water from the tank to below the start level, switch on the breaker, check that the pump starts by itself, the tank fills to the set level, the pump stops by itself, and no water runs out of the overflow pipe. Check that the overflow pipe is clear and drains to a safe place, then replace the tank lid.
Quick reference table: symptom – likely cause – how to check – fix
Symptom | Likely cause | How to check | Fix |
|---|---|---|---|
Rooftop tank overflowing, pump running | Rooftop float switch not cutting off: snagged, contacts welded, wrong pair of wires, bridged | Switch off, test continuity while lifting and lowering the float | Free the float, connect the correct pair, replace the float switch |
Rooftop tank overflowing, pump off | Mains water entering through a float valve that doesn't close | Lift the float by hand to see if the water stops | Adjust the level, replace a punctured float, clean or replace the valve |
Cistern overflowing, water meter turning continuously | Faulty cistern float valve | Lift the cistern float and see if the meter stops | Repair or replace the cistern float valve |
Rooftop tank empty, pump not running | Rooftop float switch not closing; cistern float switch signalling empty; power cut, breaker tripped | Check the cistern and the breaker; test both float switches with the power off | Replace the faulty float switch; if the cistern is empty, wait for mains water; refer electrical faults to an electrician |
Rooftop tank empty, pump running but delivering no water | Pump lost its prime, suction inlet exposed, suction strainer clogged, valve closed | Listen to the pump, check the cistern level, check the valves | Switch off the pump, re-prime, clean the strainer, fix the leak |
Pump switching on and off repeatedly while filling the tank | Start and stop levels too close; float bobbing on ripples | Watch the float while the pump is running | Increase the difference, move the float away from the delivery pipe outlet, secure the cable |
Reference table: figures to record during the repair
Figure | How to determine it | Illustrative example (for reference) | Notes |
|---|---|---|---|
Distance from the shut-off level to the overflow pipe opening | Measure with a ruler when the float has just shut off | A few cm | According to the tank and float instructions |
Volume of water between the start and stop levels | Measure the height difference and multiply by the tank's cross-section, or estimate from the markings | Assume about 500 litres | Too little and the pump cycles frequently |
Actual pump flow rate to the tank | Time how long the pump takes to deliver a known volume of water | Assume 20 litres/minute | Usually lower than the label figure because it also depends on the delivery height and pipework |
Pumping time per cycle | Volume difference divided by the flow rate | 500 ÷ 20 = 25 minutes | If the pump runs for an abnormally long time, check for leaks and the suction inlet |
Pump current and float contact rating | Read the pump label and the float label | See the actual labels | If the pump current exceeds the float rating, a contactor must be used |
The figures in the example column only illustrate the calculation and are not standards. Record the real measurements for each house so you can compare next time.
Real-life situations
Situation 1: the tank overflows every night even though the float switch was replaced
A townhouse with a cistern, pump and rooftop tank. Every night water runs out of the overflow pipe, and the previous plumber replaced the float switch without fixing it. The plumber switches off the pump breaker while it is overflowing: water still flows into the tank, so the pump is not the source. Tracing the pipes reveals a mains branch running straight up to the tank through an old float valve, added during a previous repair "in case of power cuts". At night the mains pressure rises, and the float valve's washer is worn so it does not seal; lifting the float by hand, it still drips. The plumber replaces the float valve, sets its shut-off level lower than the float switch so the two floats don't compete, monitors it for one night and the overflow stops. Lesson: always check which route water is entering the tank by before replacing parts.
Situation 2: empty tank, silent pump
In the morning there is no water, the pump is not running and the breaker is still on. The cistern has very little water, the dry-run float is hanging down and the water meter is not moving: the neighbourhood has a water cut, and the float switch is correctly stopping the pump. The plumber quickly checks the rooftop float switch (with the power off) and finds continuity when hanging and open circuit when lifted, and explains to the customer that the pump will start by itself when the water comes back. In the afternoon the water returns and the pump starts by itself. Nothing is replaced; only the inspection fee agreed in advance is charged.
Safety and acceptance checklist
Pump breaker switched off, absence of voltage verified and sign hung before touching float switches and junction boxes.
Sturdy ladder with someone holding it; cistern hatch fenced off and covered when leaving.
Valve closed before removing the float valve; threads wrapped with PTFE tape in the correct direction, no leaks.
Float valve and float switch move freely without catching on the tank wall, pipes or other cables.
Rooftop float switch: continuity when hanging, open when lifted. Cistern float switch: continuity when floating, open when hanging. Tested again after installation.
Wire joints in a watertight box in a dry place; no submerged joints; float switch not bridged.
Float contact rating suits the pump current, or a contactor is used.
A full cycle test run completed: the pump starts and stops by itself, no water from the overflow pipe, no frequent cycling.
Overflow pipe clear; tank lid closed tightly, no tools left in the tank.
The cause explained and the work done recorded for the customer.
Frequently asked questions
The tank has an overflow pipe, so does a little overflow matter?
The overflow pipe is a backup outlet for when a float fails. Water coming out of the overflow regularly means a float is faulty: it wastes water and electricity and can easily cause damp walls and ceilings. It should be fixed promptly.
Should I remove the cistern float switch to avoid hassle?
No. When the mains supply is cut and the cistern runs dry while the pump keeps running, the pump runs dry, which easily damages the seal and overheats the motor. A dry-run float switch is cheap protection for the pump.
Why does the pump run non-stop with a newly installed float switch?
The most common reason is the wrong pair of wires: the pair with the opposite function has been used, so lifting the float closes the circuit. Switch off, measure each pair of wires again and compare with the manufacturer's diagram. Also check whether the float is tied too short or snagged so it cannot rise.
Is it better to repair a mechanical float valve or replace it?
Replace it if the float is punctured, the arm is broken or the valve body is cracked. If there is only some trapped scale or a worn washer and replacement inserts or washers are available for that model, cleaning and replacing the washer is enough. When the repair cost is close to the price of a new float valve, tell the customer and let them choose.
Practice exercises
Draw the water supply diagram of your own home or a sample house: mains supply, cistern, pump, rooftop tank, floats and overflow pipe.
With a cable-suspended float switch that is not wired up, use a multimeter to identify the pair of wires that closes when the float rises and the pair that closes when it hangs down, and record them.
Under the guidance of a senior plumber, with the pump power off, adjust the shut-off level of a rooftop tank to below the overflow pipe opening and test run one complete cycle.
Write a short handover note for the customer: cause, work done, levels set, pumping time per cycle.
Self-assessment criteria — you pass when:
You always switch off and verify the absence of voltage before touching an electric float switch.
You can determine which route water is entering the tank by and narrow the fault down to the float valve, float switch, pump or water supply.
You can test an electric float switch and know which pair of wires is used for the rooftop tank and which for dry-run protection.
You replace floats with the correct size, set sensible levels and confirm the work with a complete test cycle without overflow.