Crimping an RJ45 network cable properly means arranging the 8 wires in one standard colour order (T568B: white-orange, orange, white-green, blue, white-blue, green, white-brown, brown; T568A swaps the orange and green pairs), cutting them square, pushing them fully into the RJ45 plug so the cable jacket sits inside the plug, crimping with the tool, then testing all 8 wires with a cable tester. Both ends on the same standard make a straight-through cable, the type used for almost every connection today. A cable that "has internet" is not necessarily good: one bad wire on pins 4, 5, 7 or 8 and the computer runs at 100 Mbps instead of 1 Gbps without the user knowing. This lesson is written the way a lead technician coaches an apprentice, with a colour table, 7 crimping steps, how to read the tester lights and a worked example making 12 patch cords for a small office.
By the end of this lesson, you will be able to:
- Recite the T568A and T568B colour orders and identify pin 1 on an RJ45 plug.
- Crimp a Cat5e or Cat6 RJ45 plug to standard: wires reaching the end, jacket held inside the plug, short untwisted length.
- Test a cable with an 8-light tester and read open, crossed and shorted wires.
- Check the real 1 Gbps link speed on a computer and know when specialist test equipment is needed.
- Estimate materials and time for crimping cables for a small office with figures that add up.
Learning network installation properly? Crimping network cable belongs to step 5 of the roadmap, office cabling and rack installation. See the 8-step network and internet technician roadmap to learn in the right order.
Network cable, the RJ45 plug and the T568A and T568B standards
The common network cable is unshielded twisted pair (UTP): 8 copper wires twisted into 4 pairs, orange, green, blue and brown; each pair has one solid-coloured wire and one white wire with a coloured stripe. Twisting lets the two wires in a pair cancel each other's interference, so keeping the twists right up to the plug is a technical requirement, not a cosmetic one.
The RJ45 plug and pin numbering
The plug usually called RJ45 (technically 8P8C: 8 positions, 8 contacts) is a clear plastic body with 8 copper blades (Figure 1). Hold the plug with the latch facing down, the copper contacts facing up and the cable end pointing toward you: pin 1 is on the left, pin 8 on the right. Counting pins the wrong way is the number one reason beginners reverse the whole colour sequence.
Photo: Thomas Wydra / Wikimedia Commons, Public domain
T568A and T568B colour order
| Pin | T568B | T568A | Used by 100 Mbps |
|---|---|---|---|
| 1 | White-orange | White-green | Yes |
| 2 | Orange | Green | Yes |
| 3 | White-green | White-orange | Yes |
| 4 | Blue | Blue | No (needed for Gigabit) |
| 5 | White-blue | White-blue | No (needed for Gigabit) |
| 6 | Green | Orange | Yes |
| 7 | White-brown | White-brown | No (needed for Gigabit) |
| 8 | Brown | Brown | No (needed for Gigabit) |
A tip for T568B: "white-orange, orange, white-green, blue, white-blue, green, white-brown, brown" – the blue pair sits in the middle (pins 4 and 5), and the green pair is "split" across pins 3 and 6. T568A simply swaps the orange pair with the green pair.
Which standard to use
Electrically the two are equally good. What matters is that the whole installation uses one standard consistently, on plugs, keystone jacks and patch panels. In Vietnam, technicians and office projects usually use T568B; some projects, especially those following an owner's own specification, require T568A. Ask and write it into the work order before you start.
Straight-through and crossover cables, and when to use each
Straight-through cable
Both ends on the same standard (B–B or A–A). This is the cable for computer to switch, router to modem, camera to recorder, and almost every connection today.
Crossover cable
One end T568A, the other T568B. It used to connect two devices of the same kind (computer to computer, switch to switch). Most current devices detect the direction automatically (Auto MDI-X), so a straight-through cable works in these cases too. Only make a crossover when old equipment requires it and you have checked its documentation.
Cat5e, Cat6 or Cat6A
- Cat5e: enough for 1 Gbps up to 100 m, cheap, thin wires that are easy to crimp.
- Cat6: 1 Gbps up to 100 m, and 10 Gbps over shorter runs (about 55 m); it has a plastic cross spline separating the pairs and needs Cat6 plugs.
- Cat6A: 10 Gbps up to 100 m, thick, stiff and expensive; for backbones and server rooms.
The maximum length of one copper link is 100 m including the patch cords at both ends. Choose solid copper cable; copper-clad aluminium (CCA) is cheaper but has higher resistance, breaks easily when crimped and performs poorly when powering cameras or access points over PoE.
Tools and materials
A network technician's basic kit includes a cable stripper, a tester, a punch-down tool (for keystones and patch panels) and an RJ45 crimping tool (Figure 2). A good kit lasts for years; do not economise on the crimper.
Photo: www.heimnetzwerke.net / Wikimedia Commons, CC BY 4.0
Tool list
- RJ45 crimping tool with a parallel or ratchet action (it only releases after a full crimp); about 250,000–800,000 VND (roughly US$10–31) as a 2026 reference, depending on type and area.
- Cable stripper with adjustable blade depth so it does not nick the wire insulation; about 50,000–150,000 VND.
- 8-light cable tester in two parts (main unit and remote); about 150,000–600,000 VND.
- Sharp wire cutters, a tape measure, a marker and labels.
Materials
- The right cable (Cat5e or Cat6), solid copper; read the print on the jacket.
- RJ45 plugs that match the cable: Cat6 plugs for Cat6 cable; plugs for solid-core cable (in-wall) differ from plugs for stranded cable (flexible patch cords), so check the box.
- Strain-relief boots to protect the latch, slid onto the cable before crimping.
Check the crimper before use
The crimping tool's jaw must press all 8 blades evenly (Figure 3). A worn or misaligned jaw leaves the blades on one side not fully down, and the cable works only sometimes. Crimp a test plug and look from the side: all 8 blades should be level and below the plastic surface.
Photo: No machine-readable author provided. Magma assumed (based on copyright claims). / Wikimedia Commons, CC BY-SA 3.0
The 7-step RJ45 crimping process
Safety warning: Unplug the cable from the switch or modem before cutting or re-terminating it, because it may be supplying PoE power to a camera or access point. Stripper blades and cutters are very sharp; cut away from your body, and collect copper offcuts at once so they do not fall into keyboards or sockets. When running cable in ceilings or at height, use a sturdy ladder with someone holding it; never run network cable in the same conduit or tray as power cables, do not touch exposed power wiring in the ceiling, and if you suspect leakage, call an electrician and switch off power to the area before working.
Steps 1–3: prepare the cable end
- Slide on the boot first (forget this and you must cut and re-crimp).
- Strip the outer jacket about 25–30 mm: rotate the stripper once and pull, without nicking the wire insulation inside. On Cat6, cut the cross spline flush with the jacket.
- Separate the pairs and straighten them: untwist each pair only as much as needed, straighten each wire with your fingers, and arrange them left to right in the colour order of your chosen standard.
Steps 4–5: cut and insert the wires
- Cut the wires square: hold the 8 wires flat between thumb and forefinger and cut straight in one go, leaving about 12–13 mm beyond the jacket. A short untwisted length means low crosstalk; for Cat5e and Cat6, keep untwisting to no more than about 13 mm.
- Push into the RJ45 plug (contacts up, latch down): push evenly until all 8 wire ends touch the end wall and you can see 8 copper dots from the front. The jacket must go inside the plug, past the cable clamp.
Steps 6–7: inspect, then crimp
- Check the colours one last time through the clear plastic before crimping. A mistake caught here costs one plug; caught after crimping, it costs a plug and a piece of cable.
- Crimp: place the plug in the 8P jaw and squeeze firmly to the end of the stroke (a ratchet tool releases by itself). Tug the cable gently to check it is secure, then push the boot up.
Photo: No machine-readable author provided. David.Monniaux assumed (based on copyright claims). / Wikimedia Commons, CC BY-SA 3.0
What a good plug looks like
Look at Figure 4: 8 wires touching the end wall in the right colour order, the jacket inside the plug and held by the plastic clamp, and 8 contacts pressed evenly. If you can see loose wires between the back of the plug and the jacket, or one wire shorter than the rest, cut it off and crimp again.
Testing network cable: from an 8-light tester to real speed
Never install a cable for a customer without testing it. A cable with one wrong pin that still "has internet" is a hidden fault, and by the time the customer complains about slowness it is very hard to find.
Reading an 8-light tester
Plug both ends into the main unit and the remote, then switch on. A continuity tester runs its lights in sequence on both units; a pair tester like the one in Figure 5 lights up by pair: 1–2, 3–6, 4–5, 7–8.
Photo: Reise Reise / Wikimedia Commons, CC BY-SA 4.0
| Tester lights | Fault | Fix |
|---|---|---|
| Lights 1→8 in sequence on both units | Pass (straight-through) | Label it and install |
| One light stays off | Open wire, or a wire not reaching its contact | Inspect the plugs and re-crimp the suspect end |
| Remote lights out of order (e.g. 3 before 2) | Crossed wires | Compare colours at both ends, re-crimp the wrong end |
| Two lights at once | Short between wires | Cut off the plug, re-strip and check for nicked insulation |
| No lights at all | Flat battery, loose plug or a cable broken right through | Change the battery, replug, test each section |
A fault a simple tester cannot see: split pairs
The classic mistake of inventing your own order: wiring adjacent pairs as "white-orange, orange, white-green, green, white-blue, blue, white-brown, brown" identically at both ends. An 8-light tester still shows a pass because pin 1 connects to pin 1, pin 2 to pin 2, and so on. But pins 3 and 6, which must be one twisted pair, are now wires from two different pairs. They are not twisted together, so interference rises sharply and the cable is unstable or only reaches 100 Mbps. The only way to avoid it is to follow the standard colour order exactly, without "improvising".
Checking real speed
- Plug a computer into a Gigabit switch and look at the link speed in the network settings: it should be 1.0 Gbps (1000 Mbps). 100 Mbps means a wire on pins 4, 5, 7 or 8 is bad.
- Copy a large file between two machines on the network or test speed to a local server: a good cable gives steady speed without drops.
- Projects that require formal acceptance (buildings, large sites) need a cable certifier that measures loss and crosstalk against the standard; this is usually done by a team with specialist equipment.
Worked example: crimping 12 patch cords for a 12-desk office
A 12-desk office already has a wall outlet at each desk. You are asked to make 12 Cat6 patch cords, 3 m long, from wall outlet to computer, T568B at both ends, and test them all. Prices below are 2026 references and vary by area and brand.
Materials
- Cable: 12 cords × 3 m = 36 m, plus 4 m spare for re-cuts = 40 m.
- Cat6 RJ45 plugs: 12 cords × 2 ends = 24 plugs. Buy a box of 50 for spares and future jobs.
- Boots: 24.
| Item | Quantity × unit price | Amount |
|---|---|---|
| Solid copper Cat6 cable (cut from a 305 m box) | 40 m × 10,000 VND | 400,000 VND |
| Cat6 RJ45 plugs | box of 50 × 4,000 VND | 200,000 VND |
| Strain-relief boots | 24 × 1,000 VND | 24,000 VND |
| Total materials | 624,000 VND | |
Check: 400,000 + 200,000 + 24,000 = 624,000 VND. After the job, 26 plugs (50 − 24) remain for next time. Ready-made 3 m Cat6 patch cords usually cost about 50,000–90,000 VND each, or about 600,000–1,080,000 VND for 12: crimping your own is not much cheaper; the advantage is exact lengths and being able to act quickly.
Time
- Crimping 24 plugs × 4 minutes (for a practised hand) = 96 minutes.
- Testing 12 cords × 1 minute = 12 minutes.
- Measuring and cutting cable, labelling both ends = 12 minutes.
- Total: 96 + 12 + 12 = 120 minutes, or 2 hours. Beginners take about 8–10 minutes per plug, so allow double the time and some spoiled plugs.
Handover to the customer
Test all 12 cords with the tester in front of the customer, plug them into computers and show the 1 Gbps link speed. Labels at both ends carry the desk number matching the wall outlet number. Record the results in the handover note.
Common crimping mistakes and how to fix them
Jacket not inside the plug
Sign: loose wires visible between the back of the plug and the jacket. Cause: stripping too much or cutting the wires too long. Consequence: a light tug pulls wires out, and interference is high. Fix: cut it off, re-strip and trim the wires to about 12–13 mm.
Counting pins backwards
Sign: the tester shows the whole order reversed at one end. Cause: holding the plug latch-up while arranging the wires. Fix: always hold it latch down, contacts up, cable toward you.
Cable only runs at 100 Mbps
Sign: the network works but the link speed is 100 Mbps and file copies stall around 11 MB/s. Cause: a wire on pins 4, 5, 7 or 8 not making contact, or a split pair. Fix: retest and re-crimp both ends in the correct colour order.
Plug works for a few weeks, then becomes intermittent
Sign: the connection drops when the cable is touched. Cause: stranded-wire plugs on solid-core cable (or the reverse), insufficient crimp force, or CCA cable with broken cores. Fix: use the right plug for the cable type, check the crimper and choose solid copper cable.
Frequently asked questions
Should I crimp T568A or T568B?
Both work well. Use one standard consistently across the installation; in Vietnam most technicians and office projects use T568B unless the project documents specify otherwise.
Will a cable work if the two ends use different standards?
One end T568A and the other T568B is a crossover cable. With Auto MDI-X equipment it still works, but it is not what was intended and it causes confusion during maintenance. Re-crimp so both ends match.
What is the maximum length of a network cable?
For Cat5e and Cat6 copper, one link is at most 100 m including the patch cords at both ends. Longer runs need an intermediate switch or a move to fibre.
Should I crimp RJ45 plugs onto in-wall cable?
In a standard office system, in-wall cable should terminate on keystone jacks (wall outlets) and a patch panel using a punch-down tool, with RJ45 patch cords connecting the devices. Crimping a plug directly onto solid in-wall cable is only for single, temporary runs.
The tester says pass but the network is still slow?
An 8-light tester only checks continuity. Also check the link speed on the computer, split pairs, CCA cable, or cable running next to power wiring. Full network troubleshooting and weak Wi-Fi are covered in the lesson how to fix weak Wi-Fi.
Practice exercise and self-assessment
- Crimp 10 RJ45 plugs on 5 patch cords, 1 m each, to T568B, and time each plug.
- Test all 5 cords and record the results; deliberately crimp one cord wrong (swap pins 1 and 2) to see what the tester shows.
- Plug each cord into a computer and a Gigabit switch and record the link speed.
Self-assessment criteria
- Pass: 5/5 cords test all 8 wires in the right order and give a 1 Gbps link.
- Pass: the jacket is inside the plug on all 10 ends, with untwisted wire no longer than about 13 mm.
- Pass: average time under 5 minutes per plug after 10 plugs.
- Not yet: any cord running at 100 Mbps, any plug with loose wires showing at the back, or not yet able to read faults from the tester lights.
Once your crimping is reliable, move on to the next roadmap step: Mesh Wi-Fi, site surveys & troubleshooting, where correctly terminated cable is the foundation for access points and wired-backhaul mesh to run reliably.
Keep learning network installation: after office cabling and racks come mesh Wi-Fi, troubleshooting, a full 20-person office fit-out and quoting. See the 8-step network and internet technician roadmap.