Ten years ago, the average apartment had one or two air conditioners and a gas cooker. Today the same apartment has an air conditioner in every room, a double induction hob, an oven, a tumble dryer, and more and more families are buying electric scooters and electric cars that they charge at home. These loads have something in common: high power, many hours of continuous running, and power electronics inside. Connecting them to a shared socket circuit, or using ordinary plugs, is the leading cause of melted sockets, burnt cables inside walls and main breaker trips. This lesson teaches you to design a dedicated circuit for each type of high-power load, choose the right cable, breaker and RCD type, and most importantly assess whether the existing supply can carry the new load before you accept the job.
By the end of this lesson, you will be able to:
- Convert air conditioner capacity (BTU, HP) into electrical power and current.
- Design dedicated circuits for air conditioners, induction hobs and EV chargers with suitable cables, breakers, RCDs and isolators.
- Distinguish the EV charging modes Mode 2 and Mode 3 and the requirements for DC residual current protection.
- Assess the capacity of the meter, the service cable and the main breaker when a customer wants to add a large load.
- Check high-load connections by torque tightening and temperature measurement to prevent fires.
Why high-power loads need dedicated circuits
A general socket circuit with 2.5 mm² cable and a 20 A MCB is designed for many small appliances used on and off. When a 2–7 kW appliance runs for hours on that circuit:
- The current is close to or above the cable's capacity, and the cable smoulders inside the wall all summer long.
- 10–16 A sockets and plugs are the weakest point: the spring contacts get hot, the plastic discolours, and finally it melts and shorts.
- A fault on the large appliance also cuts power to the other appliances on the same circuit.
- You cannot choose a suitable RCD for each type of electronic load.
The rule: every air conditioner from about 12,000 BTU upwards, every induction hob, oven, dryer, water heater and every EV charging point gets its own circuit from the board, with its own breaker and its own label.
Air conditioners: converting capacity and the supply circuit
The figure advertised for an air conditioner is its cooling capacity (BTU/h or "horsepower" HP), not its electrical power. Electrical power is usually about 1/3 to 1/4 of the cooling capacity, depending on the unit's efficiency. Always read the rated electrical power and current on the outdoor unit's nameplate; the table below is only an estimate for preliminary design.
| Cooling capacity | Electrical power (≈) | Running current at 230 V (≈) | Suggested MCB | Suggested copper cable |
|---|---|---|---|---|
| 9,000 BTU (1 HP) | 0.8–0.9 kW | 4–5 A | C16 | 2.5 mm² |
| 12,000 BTU (1.5 HP) | 1.1–1.3 kW | 5–7 A | C16 | 2.5 mm² |
| 18,000 BTU (2 HP) | 1.6–2.0 kW | 8–10 A | C20 | 2.5 mm² |
| 24,000 BTU (2.5 HP) | 2.2–2.6 kW | 10–13 A | C25 | 4 mm² |
Note: 12,000 BTU/h ≈ 3.5 kW of cooling. Non-inverter units have a compressor starting current 3–6 times the running current for a moment; inverter units start softly but have high-frequency and small DC leakage currents, so use at least a Type A RCD, preferably Type F.
Wiring an air conditioner circuit
- Read the manufacturer's instructions to see whether the supply goes to the indoor unit or the outdoor unit. The interconnecting cable between the two units (usually 3–4 cores including L, N, signal and PE) must follow the terminal numbering 1-2-3 exactly; mixing up the signal wire and the phase can burn out the control board.
- Run a dedicated cable from the board, with a curve C MCB and a 30 mA RCD (or an RCBO). Size the cable from the table above and re-check it for length.
- Install an isolator (an isolator switch or an MCB in a sealed IP55 enclosure) near the outdoor unit so the maintenance technician can isolate it on the spot. On an outdoor balcony, the enclosure and cable entries must be watertight, and the cable must run in conduit arranged so that water cannot collect (conduit ends pointing downwards).
- Connect PE to the casings of both the outdoor and indoor units.
- Tighten the lugs to the correct torque, especially at the outdoor unit terminal block – a place that vibrates constantly.
- After a 30-minute test run, measure the current with a clamp meter and compare it with the nameplate.
Photo: Judgefloro / Wikimedia Commons, CC0
Induction hobs, ovens and dryers
Household double induction hobs are usually rated at 3.5–4.2 kW in total; three-zone hobs or combination hobs can reach 6–7.4 kW. Even if the hob has a power-limiting function, the circuit must be designed for the maximum power on the nameplate.
| Appliance (single-phase 230 V) | Maximum current (≈) | MCB | Copper cable (in concealed conduit, ≤ 20 m) | Connection method |
|---|---|---|---|---|
| Double induction hob 3.5–4.2 kW | 15–18 A | C25 | 4 mm² | Fixed terminal block or 32 A industrial socket |
| Three-zone induction hob 7.2 kW | ≈ 31 A | C32 (or split over 2 phases as per the manufacturer) | 6 mm² | Fixed terminal block |
| Built-in oven 3 kW | ≈ 13 A | C16–C20 | 2.5 mm² | Dedicated good-quality 16 A socket |
| Tumble dryer 2.5 kW | ≈ 11 A | C16 | 2.5 mm² | Dedicated socket |
Many European induction hobs have a terminal block that allows single-phase, two-phase or three-phase connection using links. In a house with three-phase power, connecting across 2 phases exactly according to the manufacturer's diagram helps to share the load; always read the diagram on the underside of the hob – wrongly placed links can put 400 V across a 230 V circuit and burn out the hob the moment it is energised.
Photo: Stilfehler / Wikimedia Commons, CC BY-SA 4.0
Home EV charging
An EV charger is a special load: it runs close to its maximum current for many hours on end, usually at night at the same time as the air conditioners. Its diversity factor is always taken as 1. According to IEC 61851 and IEC 60364-7-722 (the part covering supplies for electric vehicles), the charging modes are:
| Mode | Equipment | Typical power | Circuit requirements |
|---|---|---|---|
| Mode 2 | Portable charging cable with an in-cable control box, plugged into an ordinary socket | 1.8–2.3 kW (8–10 A) | Dedicated socket circuit, high-quality socket, no adaptors or extension leads |
| Mode 3 – single-phase | Wall-mounted charging station (wallbox) | 7.4 kW (32 A) | Dedicated circuit, C40 MCB, 6–10 mm² cable depending on length |
| Mode 3 – three-phase | Three-phase wallbox | 11 kW (16 A/phase) or 22 kW (32 A/phase) | Dedicated 4-pole circuit, check the capacity of the three-phase supply |
| Mode 4 | DC fast charging station | ≥ 30 kW | Belongs to commercial installations, not ordinary housing |
Residual current protection for the charging point
The on-board charger in the car can produce smooth DC leakage current when it fails. DC leakage above 6 mA can saturate the magnetic core of Type AC and Type A RCDs and make them "blind". So every charging point needs:
- a dedicated 30 mA Type B RCD for the charging point; or
- a 30 mA Type A RCD combined with a 6 mA DC residual current detecting device (RDC-DD). Many wallboxes have an RDC-DD built in – read the documentation to confirm it, and only then use a Type A RCD upstream.
Each charging point has its own RCD and does not share an RCD with other circuits. If the house has a Type A or AC RCD upstream at the main board, DC leakage from the car can blind that main RCD as well – which is why DC leakage must be stopped right at the charging circuit.
Photo: Mariordo (Mario Roberto Durán Ortiz) / Wikimedia Commons, CC BY-SA 4.0
Mounting position and other requirements
- Mount the wallbox at the height recommended by the manufacturer (usually 0.8–1.2 m to the socket outlet), close to the parking space so the cable is not pulled tight or run over by the wheels.
- Outdoors: equipment rated IP54 or higher, with a canopy if the manufacturer recommends one; cables enter from below.
- Consider load management: many wallboxes have a clamp-on current sensor on the incoming cable and automatically reduce the charging current when the house load rises, avoiding main breaker trips. Highly recommended where the contracted capacity is limited.
- For electric scooters: use a dedicated socket for the charging area, with a 30 mA RCD; do not charge in escape routes or in bedrooms.
Assessing the supply before accepting a high-power load job
When a customer says "install a 7 kW car charger for me", the first question is not the price but whether the supply is big enough. Procedure:
- Read the meter and the supply contract details: single-phase or three-phase, the meter's current rating (for example 10(40) A means it can carry a maximum of 40 A continuously), and the utility's breaker.
- Check the service cable: cross-section of the cable from the meter to the main board, its length and the condition of the joints.
- Measure the existing load at peak time (summer evening) with a clamp meter on the incoming cable. Ask the customer about appliances they plan to buy.
- Add the new load with a diversity factor of 1 for EV charging and water heaters during periods of simultaneous use.
- Compare: if the total exceeds about 80% of the capacity of the meter/main breaker/service cable → propose one of these options: upgrade the supply with the utility (to three-phase), limit the charging current (16 A instead of 32 A), install load management, or schedule charging after midnight.
- Record the results on the survey sheet and explain to the customer with numbers, rather than just saying "it's not enough".
Example
A single-phase townhouse, 10(40) A meter, 40 A main breaker, 10 mm² service cable. The evening peak measured 24 A (3 air conditioners, lighting, fridge, TV). The customer wants a 7.4 kW (32 A) wallbox. Total 24 + 32 = 56 A, far above 40 A. Options: (1) set the wallbox limit to 10 A (2.3 kW) when charging in the evening, giving a total of 34 A ≈ 85% – close to the limit, not good enough; (2) use automatic load management so the charging current varies with the house load; (3) apply to upgrade to three-phase and use an 11 kW three-phase wallbox at 16 A. The electrician presents all three options with cost and timescale so the customer can choose.
Checking high-load connections: torque and temperature
With 15–32 A flowing for hours, a connection with a contact resistance of only 0.05 Ω already dissipates P = I² × R = 32² × 0.05 ≈ 51 W concentrated in a few millimetres – enough to burn the plastic of a terminal block. Therefore:
- Use a torque screwdriver or torque wrench and tighten to the torque marked on the breaker or terminal block (usually 2–3.5 N·m for MCB terminals).
- Stranded conductors must be fitted with crimped pin ferrules or suitable lugs, not twisted and pushed into the terminal.
- After 1–2 hours at maximum load (all hob zones on, the car charging), measure the terminals with an infrared thermometer or thermal camera: a difference of more than about 10 °C compared with the neighbouring terminal is a sign that it needs re-checking.
- Record the measured temperatures in the commissioning report.
Warning: Never supply an induction hob, EV charger or large air conditioner through a multi-way adaptor or a coiled extension lead. A coiled lead dissipates heat poorly and heats up very quickly under high current; this is a very common house-fire scenario.
Common mistakes
| Mistake | Consequence | Correct practice |
|---|---|---|
| Plugging the induction hob into a shared 10 A socket | Socket and plug melt and short | Dedicated circuit, terminal block or 32 A industrial socket |
| Sizing the cable from the air conditioner's cooling capacity | Wrong design, wasteful or undersized | Read the electrical power and current on the outdoor unit nameplate |
| EV charger on a Type AC RCD shared with other circuits | RCD may be blinded by DC leakage | Dedicated Type B RCD, or Type A + RDC-DD |
| Not assessing the supply before installing a charger | Main breaker trips, meter overloaded | Measure the peak load, offer a current-limiting option |
| Mixing up the air conditioner signal wire | Outdoor or indoor unit control board burns out | Follow terminal numbers 1-2-3, double-check before energising |
| No isolator near the outdoor unit | Maintenance technician works on a live circuit | Watertight isolator near the outdoor unit |
Pass criteria for this lesson
- From the nameplates of 3 air conditioners, 1 induction hob and 1 wallbox, choose the correct MCB, cable and RCD type for each circuit and explain why.
- Carry out a supply survey for a sample house: read the meter, measure the peak load, conclude whether the supply is sufficient and propose at least 2 options.
- Tighten terminals with a torque screwdriver to the correct torque; measure connection temperatures after running under load and record them in the report.
- Correctly distinguish Mode 2 and Mode 3 and state the 6 mA DC leakage protection requirement.
Frequently asked questions
Can I charge an electric car from an ordinary socket?
Yes, with the Mode 2 cable supplied with the car, at low current (8–10 A), provided the socket is on a dedicated circuit, is of good quality and has a 30 mA RCD. Do not use adaptors or extension leads. For regular charging, install a Mode 3 wallbox because it is safer and faster.
Does an induction hob need an earth wire?
Yes. Induction hobs have a metal casing or metal frame and power electronics; the PE conductor is mandatory, together with a 30 mA RCD of Type A or better.
Does an inverter air conditioner allow smaller cables?
The lower starting current means the breaker trips less often, but the maximum running current must still be taken from the nameplate. Do not reduce the cable size just because the unit is an inverter type.
Further reading
Review how to choose cables and breakers in the lesson Choosing cable sizes and circuit breakers and how to quote after a site survey in the lesson Quoting and taking on electrical jobs.