Rooftop solar has become a familiar job for residential electricians: homeowners want lower bills, want a backup source, or simply see the neighbours putting panels up and want the same. But a PV system is nothing like a lighting circuit or a socket circuit. The module side is high-voltage direct current that cannot be switched off by tripping a breaker – as long as there is daylight, the modules keep generating. The inverter side is power electronics running in parallel with the utility grid. To install safely and give the right advice, you have to understand every block in the system, read module and inverter datasheets, size strings within the correct voltage window, and know how the system behaves when the grid goes down.
This lesson covers how the system is built – the foundation for the next lesson on installation practice and DC-side safety. By the end of this lesson, you will be able to:
- Name each block of a grid-tied PV system and explain what it does: modules, strings, DC combiner box, inverter, AC panel, bidirectional meter.
- Read a module label: Pmax, Voc, Vmp, Isc, Imp and temperature coefficients.
- Tell apart grid-tied inverters, hybrid inverters with storage and stand-alone (off-grid) inverters, and know which ones keep supplying power during a grid outage.
- Do a rough calculation of how many modules go on one string so that it stays inside the MPPT window and never exceeds the maximum DC voltage.
- Estimate energy yield from installed capacity and explain the factors that reduce yield, such as shading, temperature and dust.
The big picture of a grid-tied PV system
A grid-tied rooftop solar system for a home (typically 3–15 kWp) is made up of the following blocks, in the order energy flows through them:
- PV array: the modules mounted on aluminium rails fixed to the roof. Modules convert light into direct current.
- String: several modules connected in series into a chain so their voltages add up. A system may have 1–4 strings.
- DC side: dedicated solar cable, MC4 connectors, a DC isolator, string fuses when several strings run in parallel, and a DC-rated SPD.
- Grid-tied inverter: contains the maximum power point tracker (MPPT), the DC → AC inverting stage, grid synchronisation and anti-islanding protection.
- AC side: AC circuit breaker, RCD as specified by the manufacturer, AC SPD, and the connection into the house distribution board.
- The utility's bidirectional (import/export) meter, plus the inverter's smart meter if the export-limiting (zero export) function is used.
- Monitoring: a Wi-Fi or LAN module that sends data to the manufacturer's app.
Photo: Gray Watson User:E090 / Wikimedia Commons, CC BY-SA 3.0
PV modules: reading the rating label
The back of every module carries a label with its ratings at Standard Test Conditions, STC (irradiance 1000 W/m², cell temperature 25 °C). Example for a common 550 Wp monocrystalline module:
| Symbol | Meaning | Example value | What it is used for |
|---|---|---|---|
| Pmax | Maximum power | 550 W | Calculating total capacity in kWp |
| Voc | Open-circuit voltage | 49.6 V | Checking maximum string voltage (cold, no load) |
| Vmp | Voltage at the maximum power point | 41.7 V | Checking the string stays within the MPPT window |
| Isc | Short-circuit current | 14.0 A | Selecting cable and fuses, checking the MPPT maximum input current |
| Imp | Current at the maximum power point | 13.2 A | Calculating operating current |
| Voc temperature coefficient | Change of Voc with temperature | −0.27 %/°C | Correcting Voc for cold weather |
| Pmax temperature coefficient | Change of power with temperature | −0.35 %/°C | Estimating power loss on hot middays |
| Max system voltage | Maximum system voltage | 1500 V DC | Insulation limit of the module |
| Max series fuse | Maximum series fuse rating | 25 A | Selecting the string fuse |
Two things every electrician must remember: Voc rises when it is cold (on early winter mornings in northern Vietnam, module temperature can drop to 5–10 °C) and power falls when it is hot (at midday in summer, cell temperature can reach 60–70 °C). STC values are only a reference point; in real midday sun a 550 Wp module usually delivers only about 430–480 W.
Common module types
- Monocrystalline (mono) PERC, TOPCon: the most common today, 21–23% efficiency, uniform black colour.
- Bifacial: also collects reflected light on the rear side; effective when mounted high above a light-coloured surface, but offers little benefit when mounted close to a metal roof.
- Polycrystalline (poly): older generation, speckled blue colour, lower efficiency; still encountered when servicing older systems.
- Half-cell: cells cut in half, splitting the module into two parallel halves, which reduces losses and the impact of partial shading.
Building strings: series, parallel and MPPT
Connecting modules in series (the + of one module to the − of the next) means voltages add up while current stays the same. Connecting strings in parallel means currents add up while voltage stays the same. Residential grid-tied inverters work most efficiently at a DC voltage of a few hundred volts, so modules are always wired in series into strings.
Every inverter has one or more MPPT (Maximum Power Point Tracking) inputs. Each MPPT continuously adjusts its operating voltage to draw the maximum power from its string. The rules:
- All modules in the same string must be the same type, facing the same direction, at the same tilt.
- Two roof faces with different orientations (for example an east face and a west face) must go to two different MPPTs.
- If two strings are paralleled on one MPPT, they must have the same number of modules and the same light conditions.
Calculating the number of modules per string
Take as an example a 5 kW single-phase grid-tied inverter rated: maximum DC voltage 600 V, MPPT range 90–550 V, start-up voltage 100 V, maximum input current 16 A per MPPT, 2 MPPTs. The modules are the 550 Wp units from the table above.
- Voc at the coldest (assume cell temperature 5 °C, i.e. −20 °C relative to 25 °C): cold Voc = 49.6 × (1 + 0.0027 × 20) ≈ 49.6 × 1.054 ≈ 52.3 V.
- Maximum number of modules = 600 / 52.3 ≈ 11.5 → at most 11 modules per string.
- Vmp at the hottest (cell 70 °C, i.e. +45 °C; take the Vmp coefficient as roughly equal to the Voc coefficient): hot Vmp ≈ 41.7 × (1 − 0.0027 × 45) ≈ 41.7 × 0.88 ≈ 36.6 V.
- Minimum number of modules so that hot Vmp stays comfortably above the lower MPPT limit (use 120 V for a safety margin): 120 / 36.6 ≈ 3.3 → at least 4 modules.
- Current check: Isc 14 A < 16 A allowed per MPPT → one string per MPPT is fine.
Conclusion: to install about 5.5 kWp (10 modules) you could use one string of 10 modules, or – better, if the roof has two faces – 2 strings × 5 modules into 2 MPPTs. A 10-module string runs at about 417 V Vmp and can reach 523 V Voc in cold weather – a lethal voltage, even with the AC breaker switched off.
Practical note: Always double-check with the inverter manufacturer's string design software (most brands offer an online tool). The figures in this lesson are examples; modules from two different manufacturers can have significantly different Voc and temperature coefficients.
Inverters: grid-tied, hybrid and stand-alone
| Type | Battery storage | During a grid outage | Used for |
|---|---|---|---|
| Grid-tied (on-grid, grid-tie) | No | Shuts down within a few hundred milliseconds (anti-islanding); the house loses power even in full sun | Lowering bills, lowest cost |
| Hybrid | Yes (usually 48 V or high-voltage lithium batteries) | Switches to supplying the backup/EPS load port; loads on the grid port still lose power | Lowering bills and providing backup |
| Stand-alone (off-grid) | Yes | Does not depend on the grid | Sites with no grid or a very poor grid |
| Micro-inverter | No | Shuts down like a grid-tied unit | One small inverter per module; the DC side is only a few tens of volts, reducing DC risk |
Photo: Asurnipal / Wikimedia Commons, CC BY-SA 4.0
Anti-islanding – why a grid-tied inverter shuts down during an outage
When the grid goes down, utility line workers may be repairing the lines outside. If the inverter kept exporting, a line that is "supposed to be dead" would be energised again from the customer's side – this is called islanding. Every compliant grid-tied inverter must detect loss of grid and disconnect within the specified time. What this means for you: never improvise wiring to make a grid-tied inverter run stand-alone, and never connect a generator to the same busbar as a grid-tied inverter without a design approved by the manufacturer.
Inverter label ratings you must read
- Max DC input voltage: the DC voltage that must never be exceeded (including cold Voc).
- MPPT voltage range and start-up voltage.
- Max input current per MPPT and max short-circuit current.
- Rated AC output power, max AC current: used to select the AC breaker and cable.
- Number of MPPTs and number of string inputs per MPPT.
- IP rating (IP65 for outdoor installation under a canopy), operating temperature range, and power reduction when hot (derating).
- With or without an isolation transformer: this affects the RCD requirement on the AC side. Read the manufacturer's manual to choose a Type A or Type B RCD; many transformerless inverters only need a Type A RCD because they already have internal residual current monitoring.
The DC side: components unique to solar
- Solar cable (PV1-F, H1Z2Z2-K): tinned copper conductors, UV-resistant double insulation, rated for 90–120 °C and 1–1.5 kV DC. Common sizes are 4 mm² and 6 mm². Do not use ordinary building wire for outdoor DC runs.
- MC4 connectors: IP67 waterproof, with a locking mechanism. Only mate two halves from the same manufacturer and the same product line; mixing brands is a common cause of overheating and burnt connectors.
- DC isolator: rated for DC voltage (for example 1000 V DC) and current, and able to break a DC arc. An ordinary AC breaker cannot extinguish a DC arc at several hundred volts.
- gPV string fuses: needed when there are 3 or more strings in parallel (reverse current from the other strings can exceed what a single faulty string can withstand).
- DC SPD, Type 2 for PV (with a Ucpv rating suited to the system voltage), installed in the DC box and/or at the inverter.
Photo: Asurnipal / Wikimedia Commons, CC BY-SA 4.0
The AC side and connecting into the house
- The inverter connects to the house distribution board through a dedicated breaker sized for the inverter's maximum AC current (for example a 5 kW single-phase inverter: current ≈ 22–25 A → 32 A MCB, 4–6 mm² cable depending on length).
- Connect the inverter close to the main breaker, not at the end of a socket circuit.
- When designing the board, remember the busbar and main breaker now carry current from two sources: the grid and the inverter. The combined rating must not exceed what the busbar can carry.
- Fix warning labels at the distribution board and the meter: "This installation has two sources of supply – solar power. Isolate both sources before working".
- Connection procedures, bidirectional meters and policies for selling exported power change over time; advise customers to contact their local power company for current regulations, or configure zero export with a smart meter when selling power is not yet permitted.
Estimating yield and the factors that reduce it
Daily energy yield ≈ installed capacity (kWp) × equivalent peak sun hours × system factor. Average peak sun hours in Vietnam are about 3.5–4 hours/day in the North and 4.5–5 hours/day in the Central and Southern regions. The system factor (losses from temperature, cabling, inverter and dust) is usually 0.75–0.85.
Example: a 5.5 kWp system in Ho Chi Minh City: 5.5 × 4.5 × 0.8 ≈ 19.8 kWh/day, or about 590 kWh/month. In Hanoi with the same capacity: 5.5 × 3.7 × 0.8 ≈ 16.3 kWh/day, and it can be much lower in winter.
| Factor | Effect | How to reduce it |
|---|---|---|
| Shading (water tanks, antenna masts, trees, neighbouring buildings) | One shaded module can drag down the whole string | Survey shading hour by hour, split strings, use optimizers or micro-inverters |
| High temperature | 0.3–0.4% power loss for every °C above 25 °C | Leave a ventilation gap under the modules; do not mount them flush against a metal roof |
| Dust, bird droppings | 5–15% loss if not cleaned for a long time | Clean regularly with clean water; do not use hard brushes |
| Orientation and tilt | South-facing at 10–15° tilt gives good results in Vietnam | Split east–west roofs onto two MPPTs |
| Long DC cables, small cross-section | Losses, heating | Keep DC voltage drop below about 1–2% |
Site survey before advising on an installation
- Roof: roof type (metal sheet, tile, concrete), orientation, pitch, usable area, condition of the structure and waterproofing, safe access to the roof.
- Shading: record obstructions, observe or use a shading simulation app hour by hour.
- Energy use: look at 6–12 months of bills and when most power is used (day or night). For a household that uses most of its power at night and has no storage, the benefit of a grid-tied system is low.
- Existing installation: single-phase or three-phase, distribution board, earthing, location for the inverter (well ventilated, covered, out of direct sun, easy to reach).
- Cable route from the roof to the inverter: short, in protective conduit, not sharing trunking with AC cables and signal cables.
- Backup needs: does the customer need power during outages? → this decides between grid-tied and hybrid.
Common mistakes
| Mistake | Consequence | The right way |
|---|---|---|
| Sizing strings from STC Voc and forgetting cold weather | Voc exceeds the maximum voltage, inverter damage, voided warranty | Correct Voc for the lowest temperature at the site |
| Combining modules from two roof faces on one MPPT | Significant yield loss | One MPPT per roof face |
| Promising the customer "you'll still have power in an outage" with a grid-tied system | Customer loses trust, disputes | Explain anti-islanding; if backup is needed, use a hybrid |
| Using an AC breaker on the DC side | Cannot extinguish a DC arc, equipment burns | A DC isolator rated for DC voltage |
| Mating MC4 connectors from different brands | Poor contact, heating, fire | Same brand, same product line, correct crimping tool |
| Placing the inverter in a closed loft or in direct sun | Inverter derates and fails early | A ventilated, covered location with enough clearance for cooling |
Pass criteria for this lesson
- Draw the block diagram of a grid-tied PV system and correctly mark the boundary between the DC side and the AC side.
- From a module label and an inverter label, calculate the minimum and maximum number of modules per string with temperature correction, with a result no more than 1 module off from the manufacturer's software.
- Explain to a customer in plain words, within 2 minutes, the difference between a grid-tied and a hybrid inverter during a power cut.
- Estimate the monthly yield of a 5 kWp system in your own area with a reasonable margin of error.
- Prepare a survey sheet covering roof, shading, energy use and inverter location for a real house.
Frequently asked questions
With grid-tied solar, can I still use power during a power cut?
No. A grid-tied inverter shuts itself down when the grid fails, to protect the people repairing the lines. To have power during an outage you need a hybrid inverter with battery storage and a backup load port, or an ATS-and-generator solution as covered in a later lesson.
How many years do solar modules last?
Reputable manufacturers usually give a 25–30 year performance warranty, with about 80–87% of rated power remaining at the end of that period. Inverters have a shorter life, usually 10–15 years, so customers need to know that the inverter will have to be replaced at some point.
Do the module frames need to be earthed?
Yes. The aluminium frames and mounting rails must be equipotentially bonded and connected to the common earthing system of the house, using copper conductors of a suitable size and dedicated earthing clamps that prevent galvanic corrosion between aluminium and copper. Details are in the DC-side installation lesson.
Further reading
Review earthing and distribution boards in the lesson Installing an MCB/RCBO distribution board and earthing and cable selection in the lesson Choosing cable sizes and circuit breakers.