In the previous lesson you learned how a grid-tied PV system is built and how to calculate the number of modules per string. This lesson moves on to practice: installing the system so that it is safe for the installer, safe for the house for 25 years, and can be signed off with measured results. The two hazards specific to solar are falls from height when working on the roof and high-voltage direct current that cannot be switched off. Incident statistics from countries with a lot of installed solar show that most PV system fires start on the DC side: MC4 connectors crimped incorrectly or mated across brands, cables cut on the edge of metal roofing, DC isolators with the wrong rating, water getting into junction boxes. All of these are workmanship faults that can be prevented.
By the end of this lesson, you will be able to:
- Prepare a safety plan for roof work: harness, anchor points, ladder, weather.
- Explain why the DC side is dangerous and apply the rule "treat every string as live".
- Install mounting rails and modules, run DC cables, and crimp and mate MC4 connectors correctly.
- Select and install DC isolators, DC SPDs and earthing for the array frames.
- Test before switching on the inverter: polarity, Voc, Isc, insulation resistance; commission the system and write the test report.
- Carry out the safe isolation procedure for maintenance or in the event of a fire.
Why the DC side is more dangerous than the AC side
- The source cannot be switched off: as long as there is light, the modules produce voltage. Switch off the AC breaker, shut down the inverter, even open the DC isolator – the cable from the roof down to the isolator is still live. Only darkness or completely covering all the modules removes the voltage.
- High voltage: a 10-module string has a Voc of 450–520 V DC. Direct current through the body causes continuous muscle contraction, making it hard to let go.
- A DC arc does not extinguish itself: alternating current passes through zero twice every cycle, so an arc goes out easily; direct current has no zero crossing, so pulling an MC4 apart under load can create a sustained arc at thousands of degrees, hot enough to burn the connector and the surrounding materials.
- Low short-circuit current: Isc is only about 5–10% higher than Imp, so in a fault the fuse often does not blow and the arc can be sustained. You cannot rely on overcurrent protection the way you do on the AC side.
Golden rule: Treat every DC cable and connector as always live. Never unplug or plug in an MC4 while the string is carrying current. Only work after the inverter has been switched off on the AC side, the DC isolator has been opened (on load → off load), and you have confirmed zero current with a DC clamp meter.
Safe working on the roof
Falls from height are the leading cause of death in solar installation – more than electric shock. Before going up on the roof:
- Assess the roof: metal sheet or tile, pitch, condition of the purlins, skylight sheets (polycarbonate, translucent plastic roofing) – never step on skylight sheets; they cannot bear a person's weight.
- Ladder: set at a 4:1 angle, extending at least 1 m above the roof edge, tied off at the top, with someone footing the ladder while you climb up and down.
- Full-body harness with a lanyard attached to a solid anchor point (the main structure, not a water pipe or antenna). It is mandatory on roofs steeper than 15° or where the roof edge has no guardrail.
- Weather: do not work in rain, on a wet roof, in strong wind (a module acts like a sail) or when there is a thunderstorm. At midday a metal roof can be above 70 °C – wear gloves and soft-soled non-slip shoes, and work early in the morning and in the afternoon.
- Moving modules: two people for each 2.2–2.3 m module, using a hoisting rope or a lift; never carry a module up a ladder on your own.
- The area below: barriers and falling-object warnings.
Photo: CoCreatr from Yokohama, Japan / Wikimedia Commons, CC BY-SA 2.0
Installing the mounting system and modules
- Metal sheet roofs: use dedicated clamps that match the sheet profile (seam clamps, cliplock clamps) or screws driven through into the purlins with EPDM washers to prevent leaks. Never screw into the sheet alone.
- Tile roofs: roof hooks fixed to the battens/purlins; trim the tiles where the hooks pass so the tiles still sit flat and do not carry load.
- Concrete roofs: triangular frames to create the tilt, with the frame feet fixed by expansion bolts or concrete ballast blocks; waterproof every drilled hole.
- Place the mid clamps and end clamps within the clamping zone on the module frame given in the manufacturer's documentation (usually from 1/4 of the module length), and tighten them to the torque marked on the clamp. Clamping outside the zone makes the module sag and causes micro-cracks in the cells.
- Leave a gap of at least 10–15 cm under the modules for ventilation, to lower cell temperature.
- Never step on a module. Micro-cracks are invisible to the eye but reduce output and create hot spots over time.
Earthing the frames and modules
- The aluminium module frames and aluminium rails must be equipotentially bonded to each other using toothed earthing clips (grounding clips, WEEB) or earthing lugs at the earthing holes provided on the module frame.
- A copper earth conductor (usually 6–16 mm² green/yellow or bare copper, depending on the design) runs from the rails to the common earth bar of the house.
- At aluminium-to-copper contacts, use bimetallic lugs or stainless steel washers to prevent galvanic corrosion.
- If the house has a direct-strike lightning protection system, keep the separation distance between the array and the air terminals/down conductors specified in the lightning protection design, or bond them as the designer specifies – never connect them on your own initiative.
Running DC cables
- Use dedicated solar cable (H1Z2Z2-K or PV1-F), 4 mm² or 6 mm², red for positive and black for negative, or clearly marked at both ends.
- Tie cables under the modules to the rails with stainless steel ties or UV-resistant cable ties – ordinary nylon cable ties become brittle and break after 1–2 years of sun, and the cable drops and rubs on the edge of the roofing.
- Do not let cables lie on the roof sheet, do not leave cable loops where water collects, and do not let cables rub on sharp metal edges. Every point where a cable passes an edge must have a protective sleeve or grommet.
- Run the positive and negative cables of the same string close together to reduce the induction loop area in case of a nearby lightning strike.
- From the roof to the inverter: run the cable in metal conduit or UV-resistant plastic conduit, as short as possible, and not in the same conduit as AC cables.
- Fix labels reading "Solar DC cable – live when the sun is out" along the conduit every 5–10 m and at every junction box.
MC4 connectors: crimping and mating correctly
MC4 connectors are the weakest point of a DC system. One poorly made MC4 joint carrying 13 A can heat up enough to melt its plastic within a few months.
- Use MC4 connectors from the same manufacturer and the same product line as the connectors on the modules. Two "MC4-compatible" connectors from different brands often have different tolerances; mixing them is prohibited by most manufacturers and is a reason for refusing warranty claims.
- Strip the cable to the specified length (usually 7–8 mm) without cutting any strands.
- Crimp the metal contact with a dedicated MC4 crimping tool using the die for the cable size. Do not use ordinary pliers and do not solder.
- Pull-test the crimped contact: it must not come loose.
- Push the contact into the housing until it clicks, then tighten the gland nut to the correct torque with MC4 spanners (not with pliers).
- Mate the male and female halves until they lock, then pull-test. Check polarity with a meter before connecting the string to the DC box.
- MC4 connectors must not sit in puddles or lie on the roof sheet; clip them up onto the rails.
Photo: Orion Lawlor / Wikimedia Commons, CC0
DC box, DC isolator and SPD
- DC isolator rated for a DC voltage higher than the string's cold Voc (for example 1000 V DC) and a rated current above 1.25 × Isc. Follow the polarity shown on the isolator body – some types are polarised, and if wired the wrong way round they cannot extinguish the arc.
- Place the DC isolator close to the inverter (many inverters have a built-in DC isolator); with long DC cable runs, or where the design requires it, add another DC isolator near the array.
- DC SPD, Type 2, with Ucpv higher than the cold Voc, with a short and straight PE connection.
- gPV fuses for each string when there are 3 or more strings in parallel, rated according to the module's "max series fuse".
- An outdoor DC box must be rated IP65, with cables entering from the bottom through correctly sized cable glands, and a breather vent against condensation if the manufacturer supplies one.
Photo: Ja.hess10 / Wikimedia Commons, CC BY-SA 4.0
Testing before switching on the inverter
According to IEC 62446-1 (requirements for testing, documentation and maintenance of grid-connected PV systems), every string must be tested and recorded before being put into service:
| Test | Instrument | Method | Pass criterion |
|---|---|---|---|
| Polarity check | DC multimeter (CAT III 1000 V) | Measure at the string ends before the DC isolator | Correct + / − signs, no reversal |
| Voc of each string | DC multimeter | DC isolator open, measure between + and − | Within about 5% of the value calculated for the actual temperature; identical strings differ very little from each other |
| Isc or Imp of each string | Dedicated PV tester, or DC clamp meter with the inverter running | Measure under stable irradiance | Consistent with irradiance; identical strings differ little from each other |
| Insulation resistance | 1000 V DC insulation tester | Measure between (+ joined to −) and earth, following the instrument's instructions | Not below the minimum in IEC 62446-1 (usually ≥ 1 MΩ); record the value |
| Continuity of frame earthing | Low-resistance ohmmeter | Between rails, module frames and the earth bar | Very low, stable resistance |
Testing warning: Your multimeter must have a high enough DC rating (CAT III 1000 V). Do not change the range while the probes are touching the string. Do not measure Isc by shorting the two poles directly through the meter – use a dedicated PV tester, or measure the operating current with a DC clamp meter once the inverter is running. Only carry out insulation testing with the DC isolator open and the inverter isolated.
Energising and commissioning
- Re-check all tightening torques on the AC side, the earthing and the warning labels.
- Close the AC breaker for the inverter first so that the inverter sees the grid.
- Close the DC isolator. The inverter runs its self-tests (insulation, grid measurement) for 1–5 minutes and then starts feeding the grid.
- Set the correct country/grid code as required by the power company, set export limiting if needed, and connect the Wi-Fi monitoring.
- Monitor for at least 30 minutes: voltage and current of each MPPT, AC power, no error messages.
- After 1 hour at high output, use a thermal camera or infrared thermometer to check the MC4s, the DC isolator and the AC cable terminations.
- Test an AC disconnection: the inverter must stop exporting within a few seconds (anti-islanding is working).
- Write the report: string diagram, test results for each string, configuration settings, installation photos, and emergency shutdown instructions for the homeowner.
Safe isolation procedure for maintenance or in a fire
- Switch off the AC breaker supplying the inverter (or the main breaker).
- Wait for the inverter to stop exporting (the display shows loss of grid).
- Open the DC isolator.
- Confirm zero DC current with a DC clamp meter before touching any MC4.
- If you need to work on the cable between the array and the isolator: do it after dark or cover all the modules completely with opaque sheeting; still wear insulating gloves.
For the homeowner: post the diagram and emergency shutdown instructions next to the inverter; in a fire, tell the fire brigade that the house has solar power and where the DC isolator is. Some markets require module-level rapid shutdown devices; if a customer wants a high level of safety, recommend optimizers or micro-inverters that provide this function.
Common mistakes
| Mistake | Consequence | The right way |
|---|---|---|
| Unplugging an MC4 while the inverter is running | DC arc, burns, burnt connector | Isolate AC → isolate DC → confirm zero current, then unplug |
| Mating MC4s from different brands, crimping with ordinary pliers | Heating, fire after a few months | Same brand, dedicated crimping tool, pull test |
| Using ordinary nylon cable ties to secure cables | Ties become brittle and break, cable rubs on roof edges and faults to earth | Stainless steel ties or UV-resistant cable ties |
| Reversed polarity on one string | Inverter damage, voided warranty | Check the polarity of each string before connecting |
| Screwing into the roof sheet with no purlin behind it | Leaks, frame ripped off by wind gusts | Fix into the purlins or use the correct seam clamps |
| Not using a harness on a pitched roof | Fall from height, death | Full-body harness, solid anchor, ladder tied off |
| Not testing insulation before start-up | Inverter isolation fault, leakage to the frames | Test the insulation of each string and record it in the report |
Pass criteria for this lesson
- Prepare a roof safety plan for a sample job: anchor points, ladder, method for moving modules, weather conditions for stopping work.
- Crimp 10 MC4 connectors in a row, with 10/10 passing the pull test and the visual inspection according to the manufacturer's instructions.
- Measure and fully record polarity, Voc, operating current and insulation resistance for 2 strings, and explain the results compared with the calculation.
- Recite and carry out the safe isolation procedure in the correct order in the practical test, without missing a single step.
- Prepare a PV handover report with the string diagram, test data, photos and emergency shutdown instructions.
Frequently asked questions
Is it completely safe to work on modules at night?
It is much safer, but street lights, site floodlights or even moonlight can still produce a few volts to a few tens of volts on a string. Still wear gloves and test before touching.
Can I use a good-quality AC breaker on the DC side?
No, unless the device is clearly marked with a DC rating for a sufficient voltage (for example a 1000 V DC MCB with polarity markings). Ordinary AC breakers cannot extinguish a DC arc at several hundred volts.
What should I do when the inverter shows "Isolation fault" or "Riso low"?
Isolate safely following the procedure, test the insulation of each string separately to narrow down the fault, and check for cut cables, flooded MC4s and cracked module junction boxes. This fault often appears on dewy early mornings and clears once things dry out – a sign that insulation is deteriorating, and it must not be ignored.