Vietnam lies in a region with a high density of thunderstorms; many provinces have more than 100 thunderstorm days a year. Lightning does damage in two ways: by striking the building directly (broken roofs, fire, danger to life) and through surges travelling along power lines, network cables and antenna cables into the house (TVs, modems, air conditioner control boards and cameras burnt out in batches after a single storm). A Level 3 electrician must understand and be able to install both layers of protection, know how to test the lightning earthing system, and above all install surge protective devices (SPDs) correctly – something that very many boards in Vietnam have, but wired so badly that they are almost useless.
By the end of this lesson, you will be able to:
- Explain the three parts of a direct-strike lightning protection system: air termination, down conductors, earthing.
- State the basic requirements of TCVN 9385:2012 (the Vietnamese lightning protection standard) and the IEC 62305 series for materials, down conductor spacing and earth resistance.
- Understand the principle of equipotential bonding and why the lightning earth must be connected to the electrical safety earth.
- Choose Type 1, 2 and 3 SPDs by location; read the ratings Uc, In, Imax, Iimp, Up.
- Connect SPDs following the short-lead rule, with backup protection, and check the failure indicator.
- Plan periodic inspection of the lightning protection system.
Direct strikes and surges
A lightning stroke carries a peak current of several tens of kiloamperes (up to 200 kA) for a few tens of microseconds. When it strikes a building directly, this current needs a path to earth with low resistance and low inductance; otherwise it finds its own way through the structure, electrical wiring and water pipes, causing flashovers, fire and shattered materials.
Even when lightning strikes hundreds of metres from the house – a power pole, a tall tree or the house next door – the electromagnetic field and the rise in ground potential create surges of a few kV to tens of kV that travel into the house along the power lines, network cables and TV cables. These surges are very short but enough to destroy electronic equipment. In practice, most lightning damage in Vietnamese homes is caused by surges, not by direct strikes.
| Protection layer | Protects against | Main equipment | Reference standards |
|---|---|---|---|
| Direct-strike protection (external) | Lightning striking the building | Air terminals, roof conductors, down conductors, earth rods | TCVN 9385:2012, IEC 62305-3 |
| Equipotential bonding | Potential differences, internal flashover | Equipotential bar, bonding conductors | IEC 62305-3, TCVN 7447 |
| Surge protection (internal) | Surges on power and signal lines | Type 1, 2, 3 SPDs; signal line SPDs | IEC 62305-4, IEC 61643, TCVN 7447-5-53 |
The direct-strike lightning protection system
Air termination
These are the highest points, so that lightning strikes them instead of the structure: air terminals (upright metal rods), conductors stretched along the ridge and roof edges, or a mesh on a flat roof. IEC 62305 defines the protected zone using the rolling sphere method (radius 20, 30, 45, 60 m for protection levels I to IV), the protective angle method and the mesh method (mesh size from 5 × 5 m to 20 × 20 m depending on the level). Ordinary houses usually use level III or IV; high-rise buildings, places where many people gather and flammable stores need a higher level according to the design.
In Vietnam, "early streamer emission" (ESE) air terminals advertised with a large protection radius are very common. These are designed to the French standard NF C 17-102; the international IEC standards community has not recognised that they perform better than ordinary rods. The electrician installs according to the approved design documents; when advising customers, do not promise that "one rod protects the whole area".
Photo: Infrogmation of New Orleans / Wikimedia Commons, CC BY-SA 4.0
Down conductors
They connect the air termination to the earthing system by the shortest, straightest route, avoiding sharp bends (lightning current rises very steeply, and the inductance of a bend creates a high voltage that can cause a side flash). Basic requirements:
- Material: copper, hot-dip galvanised steel or aluminium with the minimum cross-section given in the standard (per IEC 62305-3: about 50 mm² for copper and steel, 70 mm² for aluminium, for solid round or flat conductors).
- At least two down conductors per building (except very small buildings where the design allows), evenly spread around the perimeter. Average spacing between conductors per IEC: 10 m (levels I–II), 15 m (level III), 20 m (level IV).
- Fixed firmly to the wall with clips, spaced about 1 m apart.
- A test joint (a removable joint) at a height of about 0.3–1.5 m above ground, so the earth can be disconnected to measure its resistance.
- The section near ground level (about 2–3 m) is mechanically protected with insulating conduit to prevent impact damage and reduce the danger from touch voltage.
- Using the structural reinforcing steel as natural down conductors is allowed when the design permits it and the reinforcement is welded/tied continuously and tested.
Lightning earthing
Copper-bonded or galvanised steel rods (typically Ø16, 2.4 m long), driven in groups and connected together with bare copper cable or steel tape buried about 0.5–0.8 m deep, at least about 1 m away from the building foundations. Underground joints use exothermic welding (cadweld) or dedicated clamps. TCVN 9385:2012 generally requires the lightning earth resistance to be no more than 10 Ω (measured when disconnected from other systems); where the soil has high resistivity, add more rods, extend the ring electrode, or use resistance-reducing compound as per the design.
Equipotential bonding: lightning earth and safety earth
When lightning strikes, the potential of the lightning earthing system can rise to tens or even hundreds of kV for an instant. If the electrical safety earth of the house (the PE conductor) is a completely separate set of rods, an enormous potential difference appears between appliance casings (connected to PE) and the structure or water pipes – causing flashovers inside the house, burnt appliances and danger to people.
That is why modern standards (IEC 62305, IEC 60364) require the earthing systems to be bonded together at the main earthing terminal (MET), either directly or through a spark gap where there is a technical reason for separation. Metal water pipes, steel frames, antenna masts and solar panel frames must all be equipotentially bonded. This is where many electricians still hold the old belief that "the lightning earth must be kept completely separate"; follow the design and the current standards.
In addition, maintain a separation distance between lightning down conductors and the electrical wiring and network cables inside (usually from a few tens of centimetres to more than a metre depending on height, calculated according to IEC 62305-3). Do not run power cables or camera cables parallel and close to a lightning down conductor.
Photo: Paolo Neo / Wikimedia Commons, Public domain
Surge protection: SPDs
An SPD (Surge Protective Device) contains a non-linear component – a zinc oxide varistor (MOV), a gas discharge tube or a spark gap. At normal voltage the SPD is practically an open circuit. When a surge arrives, the SPD's resistance drops very quickly, diverting the surge current to PE and holding the voltage at the equipment to the level Up (the voltage protection level). Once the surge has passed, the SPD returns to its open state.
Types of SPD by location
| Type (IEC 61643-11) | Test waveform | Location | When it is needed |
|---|---|---|---|
| Type 1 | Iimp 10/350 µs, e.g. 12.5–25 kA/pole | Main board at the service entrance | Buildings with a direct-strike protection system, or supplied by an overhead line |
| Type 2 | In 8/20 µs, e.g. 20 kA, Imax 40 kA | Main board or floor distribution board | Most houses; the minimum you should have |
| Type 3 | Combination wave Uoc | Close to sensitive equipment (sockets, power strips with SPD) | Expensive equipment more than 10 m from the board |
| Combined Type 1+2 | Both Iimp and In | Main board of a house | A compact solution for houses with a lightning rod |
Reading SPD ratings
- Uc – maximum continuous operating voltage: on a 230/400 V TN system, choose Uc ≥ 275 V AC for SPDs connected between phase and PE/N. In some places the Vietnamese network voltage is high during off-peak hours; if Uc is too low, the SPD ages quickly.
- In / Imax – nominal / maximum discharge current (8/20 µs): the ability to withstand repeated surges and the largest single surge.
- Iimp – lightning impulse current (10/350 µs), only given for Type 1 SPDs.
- Up – voltage protection level: the lower the better. Household appliances withstand impulses of about 1.5–2.5 kV, so choose Up ≤ 1.5 kV at distribution boards supplying electronic equipment.
Photo: Stan Zurek, Editor-in-Chief of Encyclopedia Magnetica, E-Magnetica.pl / Wikimedia Commons, CC BY-SA 4.0
Connecting SPDs correctly
The factor that decides how effective an SPD is, is the length of its connecting leads. Surge current rises extremely steeply; each metre of wire has an inductance of about 1 µH, adding about 1 kV of voltage for every kA/µs. If the leads from the phase bar to the SPD and from the SPD back to the PE bar total 1.5 m, the voltage the equipment actually has to withstand can be Up plus several kV – the SPD is then almost useless.
- Total lead length (from the tap-off point on the phase conductor to the SPD, plus from the SPD to the PE bar) ≤ 0.5 m; ideally use V-wiring (conductors in and out directly through the SPD terminals) where the manufacturer allows it.
- Lead cross-section according to the instructions: usually ≥ 6 mm² copper for Type 2 SPDs, ≥ 16 mm² for Type 1 SPDs.
- Place the SPD immediately after the main breaker, close to the board's PE bar.
- Provide backup protection (fuses or MCB) upstream of the SPD with the rating specified by the manufacturer, so that if the SPD fails short-circuit, the backup device trips rather than the main breaker.
- Connection scheme according to the earthing system: TN-C-S usually uses SPDs connected L–PE and N–PE (3+1 or 1+1 configuration with an N–PE spark gap); TT uses the "3+1"/"1+1" configuration with an N–PE gas discharge tube. Follow the manufacturer's diagram for the correct system.
- Multi-stage coordination: Type 1 SPD at the main board, Type 2 at the floor boards; the cable length between the two SPD stages should be at least about 10 m (or as specified by the manufacturer) so that they share the energy correctly.
Don't forget the signal lines
Lightning surges do not enter the house only through the power supply. TV coaxial cables, network cables coming in from an outdoor pole and camera cables running across the yard are all paths for surges. Install dedicated SPDs for coaxial and network (RJ45) cables at the point of entry into the house, earthed to the same PE bar. Outdoor cameras mounted on metal poles must have the pole bonded to the earthing system.
Warning: Do not work on roofs, antenna masts, lightning protection systems or overhead lines during a thunderstorm or when you can hear thunder within about 10 km. Stop outdoor work as soon as you see lightning and wait at least 30 minutes after the last thunder.
Periodic inspection and maintenance
- Every year, before the rainy and storm season: visually inspect the air termination, down conductor clips, corroded joints and conductors broken during roof alterations.
- Measure earth resistance at the test joint (open the joint to disconnect) using the 3-rod method learned in Level 2; compare with the design value and the previous measurement.
- Check continuity between the air termination and the test joint (measure the resistance with a low-resistance ohmmeter).
- Check the SPD indicators after every storm season and after every nearby strike; replace failed modules.
- Keep a logbook: inspection date, measurement results, damage and action taken. This is an important record at handover and for insurance purposes.
Common mistakes
| Mistake | Consequence | Correct practice |
|---|---|---|
| SPD leads 1–2 m long, coiled up in the board | The SPD cannot protect the equipment | Total lead length ≤ 0.5 m, run straight |
| SPD without backup protection | A short-circuited SPD trips the main breaker or sets the board on fire | Backup fuse/MCB as specified by the manufacturer |
| Down conductor bent around windows and railings | Side flashes, structural damage | Straight, shortest route to earth |
| Lightning earth completely separated from the safety earth | Large potential differences, flashover inside the house | Bond at the main earthing terminal according to the design |
| Camera cable running right next to a lightning down conductor | Cameras and recorder burnt out after a storm | Keep the separation distance, use signal SPDs |
| SPD indicators not checked for years | The SPD has already failed and the house is no longer protected | Check every storm season |
Pass criteria for this lesson
- Draw a lightning protection layout for a 5-storey flat-roofed townhouse: air termination, number and position of down conductors, test joints, earth ring electrode, equipotential bonding points.
- Measure the lightning earth resistance at the test joint and conclude pass/fail against 10 Ω.
- Choose the correct SPD type, Uc, Up and backup protection for the main board of a house with and without a lightning rod.
- Install an SPD in a sample board with a measured total lead length of ≤ 0.5 m.
- Prepare a periodic inspection checklist for the lightning protection system covering all items.
Frequently asked questions
A townhouse in a narrow alley surrounded by taller buildings – does it need direct-strike protection?
A risk assessment is needed as part of the design (IEC 62305-2). A house inside the protected zone of a taller neighbouring building has a lower risk of a direct strike, but it should still have SPDs, because surges travel along the power network shared by the whole neighbourhood.
Can a surge-protected power strip replace the SPD in the board?
No. A power strip with an SPD is Type 3, can only absorb a small amount of energy, and only supplements protection for equipment close to it. The main board still needs a Type 2 (or Type 1+2) SPD.
Can an SPD whose indicator has turned red still be used?
No. The module has disconnected itself from the circuit for safety and no longer provides protection. Replace the module with one of the same type and the same Uc.
Further reading
Review the earth testing method in the lesson Installing a distribution board with MCBs, RCBOs and earthing and safe working in the lesson Safety rules before touching electrical wires.