The lesson on Ohm's law showed that a loose 0.2 Ω connection at 15A produces 45W of heat, enough to burn out a junction box without the circuit breaker ever noticing. Investigations into electrical house fires in Vietnam often give the cause as "a short circuit", but behind a great many of them is a poor connection: wires carelessly twisted by hand, wrapped in tape, stranded wire cut through by a screw, lugs crimped with ordinary pliers. This lesson covers the first hands-on skill that the lead electrician will grade you on.
By the end of this lesson, you will be able to:
- Strip wire to the correct length for each type of terminal, without nicking the conductor or breaking strands.
- Make the three common types of joint: lever-type push-in connectors (WAGO style), screw terminals and crimped butt connectors; and know when hand-twisting is and is not acceptable.
- Choose the right type of terminal (bootlace ferrule, ring terminal, fork terminal, butt connector) according to the cross-section and connection point.
- Crimp terminals with a ratchet crimping tool and check the crimp with a pull test and a visual inspection.
- Tighten terminal and breaker screws to the correct torque, and recheck connections after the power is switched on.
Three requirements of a good connection
- Low and stable contact resistance: a large enough contact area and enough clamping force, which does not decrease over time or with temperature and vibration.
- Mechanical strength: withstands pulling and bending when a box cover is closed or a socket faceplate is fitted, without the wire pulling out or the conductor breaking.
- Complete insulation: no copper exposed outside the connector body or terminal, and adequate clearance from other conductive parts.
One more requirement that is often forgotten: it must be inspectable. TCVN 7447-5-52 (IEC 60364-5-52) requires connections to be located where they are accessible for inspection and maintenance, meaning inside a junction box with a cover, never plastered permanently into a wall.
Stripping wire to the right length
Every type of terminal has a recommended strip length printed on its body or in its instructions, usually 8–11 mm for push-in connectors and 10–12 mm for DIN-rail breakers. Strip too much and copper is left exposed outside the terminal, with a risk of short circuits. Strip too little and the plastic insulation, not the copper, gets clamped in the terminal, giving poor contact.
- Use wire strippers with a hole of the correct size, or automatic strippers.
- Hold the wire square to the tool, squeeze decisively and pull straight off. Do not rotate the tool around the wire (this easily nicks the conductor).
- Inspect the conductor: no nicks, no broken strands. For stranded wire, gently smooth the strands so they twist back in their original lay direction.
Method 1: lever-type push-in connectors
Lever-type connectors (the best known is the WAGO 221 range) use a steel spring to clamp the wire, so the clamping force does not depend on the installer's hand and does not loosen over time. This is the recommended way of making joints in domestic junction boxes today.
- Read the data on the body: permitted cross-section (for example 0.2–4 mm², some types up to 6 mm²), rated current (for example 32A), strip length (11 mm).
- Lift the lever all the way up.
- Push the wire in fully until, through the transparent body, you can see the end touching the inner wall.
- Close the lever. Gently tug each wire to make sure it is clamped.
Photo: Lucasbosch / Wikimedia Commons, CC BY-SA 4.0
Do not exceed the rated current
Every connector has a rated current, for example 32A. Do not use one small connector to gather too many heavily loaded wires. Do not connect aluminium wire to a connector designed for copper unless the manufacturer allows it.
Method 2: screw terminals and connecting to breakers and sockets
Screw terminals are found on circuit breakers, sockets, switches and DIN-rail terminal blocks. With solid single-strand wire, insert it straight in and tighten. With stranded wire, you must first crimp on a bootlace ferrule; otherwise the screw will press the strands apart and cut them, and the connection will work loose after a few heating and cooling cycles.
Tightening torque
Breaker manufacturers state the recommended tightening torque, typically about 2–2.5 N·m for common MCBs and 0.5–0.8 N·m for socket and switch terminals. Beginners tend either to tighten too lightly (for fear of breaking something) or too hard (cracking the housing or stripping the thread). Professionals use a torque screwdriver for distribution boards. If you do not have one yet, practise with a torque screwdriver a few times to get a feel for the right force.
Never put two wires of different sizes under the same screw
The screw will clamp the larger wire tightly and leave the smaller one loose. If you need to branch off, use a distribution terminal block, a bus bar, or crimp both wires into a correctly sized twin ferrule.
Method 3: crimp terminals and butt connectors
| Type | Shape | Used when |
|---|---|---|
| Bootlace ferrule | Tin-plated copper tube with a coloured plastic collar | Stranded wire into screw terminals and breakers |
| Ring terminal | Round ring with a hole for a bolt | Connecting to bus bar bolts, earth rods, motors |
| Fork (spade) terminal | Open U shape | Screw terminals where the screw does not need to be fully removed; avoid where there is vibration |
| Solid pin terminal | Flat or round pin end | Small clamp-type terminals |
| Butt splice | Tube joining two wire ends | Extending wires, joints in cable trays |
Photo: StromBer / Wikimedia Commons, CC BY-SA 3.0
Choosing the terminal size
Crimp terminals are marked with the matching wire cross-section (for example 1.5 mm², 2.5 mm²), and ring terminals also with the bolt hole size (M4, M5, M6). The collar colour of a bootlace ferrule follows the manufacturer's colour system; under the widely used DIN 46228 standard, 1.5 mm² is red or black and 2.5 mm² is blue or grey, depending on the system. Always read the cross-section printed on the card or box, do not rely on the colour alone.
Crimping correctly
- Strip the wire to exactly the length of the terminal's copper barrel (for insulated terminals the copper must go fully into the barrel, with none showing at the collar).
- Lightly twist the strands and push them into the terminal until the conductor reaches the bottom, or protrudes a few mm from the end of the tube (for bootlace ferrules).
- Place the terminal in the die of the correct size in the tool. A ratchet tool only releases once full crimping force has been applied, guaranteeing a sound crimp.
- Squeeze through the full stroke until the ratchet releases.
- Check: pull hard by hand (a 2.5 mm² wire must withstand a substantial pull without coming out); look for an even crimp, no cracks in the barrel and no stray strands outside.
Photo: 魔私利戸 / Wikimedia Commons, CC BY-SA 3.0
Hand-twisting and tape: when is it still acceptable?
Many experienced electricians still habitually twist two wires together and wrap them in tape. This may be acceptable for some temporary joints on small wires with small loads, when done properly (enough tight turns, soldered, then covered with heat-shrink tubing). But for junction boxes in new homes, you should use push-in connectors or terminal blocks, because:
- The clamping force of a twisted joint depends on the installer's hand, is hard to check and easily loosens over time.
- PVC tape ages and peels off after a few years in a warm junction box.
- During repairs, a twisted joint has to be cut off, so the wires get shorter each time.
Never twist copper and aluminium wires together. Never make joints inside conduit or plaster them into a wall; every joint must be inside a junction box with a cover.
Warning: Never join wires while they are live, even if "it's only a lighting wire". A joint made in a hurry on a live circuit is usually both dangerous for the person doing it and of poor quality.
Checks after switching on
Poor connections usually show up under load. After finishing the work and switching on the power:
- Run the circuit close to its rated load (for example a water heater or electric kettle on a socket circuit) for 15–30 minutes.
- Switch off, open the junction box and check the temperature of the connections by touch or with an infrared thermometer. A connection that is noticeably hotter than the surrounding wire has a problem.
- The lead electrician may use a thermal camera for larger distribution boards (Level 4: periodic maintenance).
Copper meets aluminium: why they must not be joined directly
Many older houses in Vietnam still have aluminium wire running from the meter into the house, or the utility's twisted aluminium overhead cable. When you have to join copper wire to aluminium wire, there are two physical problems:
- Galvanic corrosion: copper and aluminium in contact in a damp environment form a small "battery"; the aluminium gradually corrodes and an insulating aluminium oxide layer forms on the contact surface.
- Different thermal expansion and "creep": aluminium expands more than copper and is softer; under sustained clamping pressure it deforms plastically, so the connection loosens a little more with each heating and cooling cycle.
The result is that contact resistance rises, the connection heats up, heat speeds up oxidation, and this loop leads to a fire. The correct approach:
- Use copper–aluminium bimetallic lugs: an aluminium barrel crimped onto the aluminium wire, with a copper contact palm.
- Or use purpose-made connectors clearly marked as suitable for Al/Cu joints ("Al/Cu" printed on the body).
- Clean the aluminium surface with a wire brush and apply anti-oxidation compound as instructed by the lug manufacturer before crimping.
- This is work at the supply end, usually the responsibility of the utility or the lead electrician; a helper only does it when assigned and under supervision.
Step-by-step practical exercise
Lead electricians often set the following exercise to assess a helper's jointing skills. Practise on a wooden board before going out on site:
- Preparation: 2 m of 1.5 mm² wire and 2 m of 2.5 mm² wire (one solid type and one stranded type), 5 push-in connectors, 10 bootlace ferrules, 5 M5 ring terminals, one DIN-rail terminal block and one old circuit breaker.
- Stripping: cut 20 pieces of 10 cm, strip both ends and measure with a vernier caliper. Note any ends that are wrong.
- Push-in connectors: make 5 three-wire joints and test each wire with a moderate tug.
- Crimping: crimp 10 ferrules and 5 ring terminals, then cut one crimp lengthwise with a hacksaw to see inside: the strands should be evenly compressed with no large voids.
- Connecting to devices: connect wires to the breaker and the terminal block, tighten with a torque screwdriver, then shake and bend the wires a few times and retighten to check that the screws have not loosened.
- Self-assessment: compare against the table of mistakes below and count your errors. Repeat until there are none left.
Cutting open a crimp to look inside is how skilled tradespeople learn fastest: you will immediately see the difference between a crimp made with a ratchet tool and one made with ordinary pliers.
Common mistakes
| Mistake | Consequence | Remedy |
|---|---|---|
| Stranded wire connected directly under a screw | Splayed and broken strands, loose connection, overheating | Crimp on a bootlace ferrule |
| Crimping with ordinary electrician's pliers | Insufficient crimping force, wire pulls out | Ratchet crimping tool |
| Two wires of different sizes under one screw | The smaller wire is loose | Distribution terminal block or twin ferrule |
| Stripping too much | Exposed copper, short circuit | Strip to the length printed on the terminal |
| Overtightening | Cracked breaker housing, broken conductor | Tighten to the recommended torque |
| Joints inside conduit or plastered into the wall | Cannot be inspected or repaired | Put joints in a box with a cover |
Pass criteria for this lesson
- Strip 20 ends of 1.5 and 2.5 mm² wire to exactly 11 mm (tolerance ±1 mm), with no nicked conductors or broken strands.
- Make 5 joints with push-in connectors; each passes a pull test without coming out, with the wire end visibly touching the inner wall.
- Crimp 10 bootlace ferrules and 5 ring terminals that pass a pull test and show none of the 4 faults in Figure 5.
- Connect wires to a circuit breaker and a socket, tightened to the correct torque with a torque screwdriver according to the manufacturer's data.
- After 30 minutes at a 15A load, no connection is hotter than the surrounding wire when checked with an infrared thermometer.
Frequently asked questions
Are push-in connectors as durable as twisting and soldering?
Good-quality push-in connectors are tested to IEC 60998 for thermal cycling and vibration, and their spring clamping force remains stable for many years. A good soldered joint is also durable, but it depends on skill and takes time. In homes, the right type of push-in connector is a good choice.
Should I tin the ends of stranded wire with solder before connecting them to a screw?
No. Solder is soft and gradually "creeps" under the clamping pressure of the screw, so the connection loosens over time. Use a bootlace ferrule.
What is the difference between tin-plated and bare copper terminals?
Tin plating resists oxidation and keeps good contact over the long term, especially in damp locations. Use tin-plated terminals in homes.
Further reading
Apply these jointing techniques to distribution boards in the lesson Installing a distribution board with MCBs, RCBOs and earthing.