Lighting circuits are the job helpers are given most often: running conduit, pulling wire, fitting junction boxes, connecting switches and lampholders. It looks simple, but this is also where the most annoying faults for homeowners come from: a switch that breaks the neutral, so the lampholder is still live when the light is off; wire that cannot be pulled because the conduit has too many bends; a junction box plastered over inside the wall; a connection smouldering above a plasterboard ceiling. This lesson teaches you to build lighting circuits that work first time and can still be repaired 20 years later.
By the end of this lesson, you will be able to:
- Choose the type of conduit and its size according to the number of wires, and run conduit following the rules: straight routes, right angles and draw boxes.
- Position junction boxes and flush wall boxes, and keep clearance from water and gas pipes.
- Wire a light controlled by one one-way switch and a light controlled by two two-way switches (staircase), with the switch always breaking the line conductor.
- Test continuity and insulation before switching on, and then carry out a functional test.
Conduit: choosing the type and the size
Conduit protects wires from impact, moisture and rodents, and allows the wires to be replaced later without breaking open the wall. TCVN 9207:2012 (installation of electrical wiring in dwellings and public buildings) requires concealed wiring to be run in conduit, never buried directly in mortar.
| Type of conduit | Characteristics | Where it is used |
|---|---|---|
| Rigid round PVC conduit | Stiff and straight, joined with couplers, bent with a bending spring | Concealed in walls and floors, surface-mounted on ceilings |
| Flexible corrugated PVC conduit | Bends easily, poor resistance to crushing | Short sections to light fittings, above plasterboard ceilings |
| Steel or galvanised conduit | Impact resistant, good fire resistance | Workshops, places with heavy mechanical stress |
| Square trunking (plastic) | Surface-mounted, with a cover | Renovating old houses without chasing walls |
Photo: Anibal Maysonet / Wikimedia Commons, CC BY-SA 4.0
Sizing conduit by the number of wires
A common rule of thumb: the total outer cross-section of the wires (including insulation) should not exceed about 40% of the inner cross-section of the conduit. If the conduit is overfilled, wires are hard to pull, the insulation gets scratched, and the wires run hotter because they cannot shed heat. In practice:
- Ø16 conduit: up to about 3 wires of 1.5 mm² (lighting circuits).
- Ø20 conduit: about 3 wires of 2.5 mm², or 4–5 wires of 1.5 mm².
- Ø25 conduit: 4–6 mm² wires for water heaters, air conditioners and feeders.
These figures are for reference only; always check the conduit manufacturer's table and do a trial pull before the wall is plastered.
Rules for running conduit
- Run vertically or horizontally, never diagonally. Anyone drilling the wall later can then guess where the wires are: straight up and down above and below switches and sockets; horizontally in a band near the ceiling or near the floor.
- No more than two 90° bends between two boxes. With more bends, the wire cannot be pulled. Put a draw box in between.
- Bend conduit with a bending spring, with a large enough bend radius, never kinking or crushing the conduit.
- Keep power wiring and low-voltage wiring (network, cameras, aerials) in separate conduits, at least a few cm apart as recommended by the signal cable manufacturer.
- Keep clear of water and gas pipes, and never run electrical conduit directly under a water pipe that might leak.
- Fix the conduit with clips or mortar every 0.5–1 m or so, so it does not move during plastering.
- Install a draw wire (steel wire or plastic draw tape) as soon as the conduit is fitted, to make pulling the wires easy.
Junction boxes and flush wall boxes
Every connection must be inside a box with a cover that remains accessible. Junction boxes go in the ceiling (branch points for the lights), and flush wall boxes go at switches and sockets.
- Choose a box large enough for the number of connections; do not cram in wires so the cover breaks.
- Leave about 15–20 cm of spare wire in the box so there is enough to cut back during future repairs.
- Set flush wall boxes so their face is level with the finished wall surface (allowing for plaster and tiles).
- Label the function of the wires in the box with coloured tape or tags if there are several circuits.
Photo: Dmitry G / Wikimedia Commons, Public domain
A light with one switch: the switch always breaks the line
This is the most important rule in the lesson: the switch must be in the line conductor (L), and the neutral (N) goes straight to the light. If the switch is placed in the N conductor, the lampholder remains at line potential relative to earth when the light is off, and anyone changing the bulb can get a shock.
- The line conductor from the lighting circuit breaker goes into the ceiling junction box and is joined to the wire going down to the switch.
- From the switch, the "switched line" wire (usually a different colour, or marked brown) goes back up to the junction box and is joined to the wire to the light.
- The N conductor from the board goes into the junction box and is joined straight to the light.
- The PE conductor (green-yellow) goes to lights with a metal housing or an earth terminal.
- Screw (Edison) lampholders: the line goes to the centre contact and N to the screw thread, so that the thread (which is easy to touch) is not live when the light is off.
Two two-way switches (staircase circuit)
A staircase circuit lets one light be switched on and off from two places. Each two-way switch has three terminals: a common terminal (COM, often marked L) and two terminals L1 and L2.
- The line conductor goes to the COM terminal of switch 1.
- Two "strapper" (traveller) wires connect L1 to L1 and L2 to L2 between the two switches.
- The COM terminal of switch 2 goes up to the light.
- The N conductor goes straight to the light.
When both switches are in the same position (both on L1 or both on L2), the circuit is closed and the light is on. Flip either switch and the circuit opens, so the light goes off. If you need to switch from 3 or more places, add an intermediate switch between the two strapper wires.
Warning: Never "borrow" an N conductor from another circuit (a different breaker or a different RCD) to supply a light. The RCD will then trip for no apparent reason, and when one breaker is switched off, the N conductor may still carry current from the other circuit and give someone a shock.
Fitting a switch into a flush wall box
- Switch off, lock off and tag as in Lesson 2, and test to confirm the circuit is dead.
- Strip the wires to the length printed on the back of the switch, insert them into the terminals and tighten to a moderate torque.
- Fold the wires neatly into the back of the box in a Z shape, so no wire is trapped between the switch plate and the fixing screws.
- Tighten the screws evenly on both sides and check with a spirit level that the switch plate is level.
- Common mounting height: switches about 1.2–1.5 m above the finished floor, or according to the specific design of the building.
Photo: Paul Cutler from Chaska, USA / Wikimedia Commons, CC BY 2.0
Checks before switching on
- Continuity: with the breaker off, use a meter to measure from the line conductor at the board to the lampholder with the switch on (≈0 Ω) and off (open circuit). For a two-way circuit, test all 4 combinations of switch positions.
- Correct polarity: confirm that the switch is in the line conductor (with power on, the centre contact of the lampholder has no voltage when the switch is off).
- Insulation: remove the bulbs and use a 500V DC insulation resistance tester to measure between L–N, L–PE and N–PE. TCVN 7447-6 (IEC 60364-6) requires at least 1 MΩ for 230V circuits; in practice, new circuits usually reach hundreds of MΩ.
- PE continuity to lights with metal housings.
- Switch on, operate the switches several times and watch for sparks, burning smells or RCD tripping.
Pulling wire into conduit: how to avoid jams and scratches
Pulling wire is the job helpers do most during the first-fix stage. Done right, one person can pull a whole reel of wire through 10 m of conduit; done wrong, two people pull endlessly without success and the insulation gets scraped down to the copper inside the conduit.
- Check the conduit is clear: before plastering, blow through or do a trial pull of the draw wire through each section. Any section that jams must be fixed immediately; after plastering it is too late.
- Prepare the pulling head: strip about 5 cm of the wires, twist the conductors into the hook of the draw wire, wrap with tape into a tapered point, and stagger the wires so the head is not bulky.
- One person pushes, one person pulls: the person at the entry end keeps the wires straight and feeds them evenly without twisting; the person at the exit end pulls steadily, without jerking.
- Do not pull too hard: if it feels unusually heavy, stop and check for bends or obstructions. Pulling too hard can stretch the copper conductor and reduce its cross-section.
- Label both ends of the wires as soon as they are pulled (for example "L1 – living room light", "SW1") to avoid mix-ups when connecting.
- Leave spare wire of about 15–20 cm at each box, as mentioned above.
Do not use oil or grease to lubricate the wires, as it can damage PVC insulation; if necessary, use a purpose-made cable-pulling lubricant gel.
Installation sequence for a lighting circuit
To avoid missing anything, helpers should memorise the standard order of work for each lighting circuit in a new house:
- Receive the drawing or instructions for the positions of lights, switches and junction boxes from the lead electrician; mark them on the walls and ceiling with a marker or chalk.
- Cut chases in the wall with a wall chaser, just deep enough for the conduit to sit below the plaster.
- Fit the flush wall boxes, lay the conduit, fix it in place and insert the draw wire.
- The lead electrician inspects the conduit routes before plastering and takes photos for the record (photos of conduit routes are extremely valuable for later repairs).
- After plastering, skim coating and painting, pull the wires and label them.
- Make the connections in the junction boxes and fit the switches and lampholders.
- Test before switching on, carry out a trial energisation and fill in the test sheet.
Common mistakes
| Mistake | Symptom | How to fix it |
|---|---|---|
| Switch in the N conductor | Light switched off, but a voltage tester still glows at the lampholder | Move the switch to the line conductor |
| Strappers and COM mixed up in a two-way circuit | Works from one side only, or "sometimes works, sometimes doesn't" | Identify COM with a meter and rewire |
| Too many bends | Wire cannot be pulled | Add a draw box |
| Junction box plastered over | Cannot be repaired when a fault occurs | Place boxes where they have an accessible cover, and mark them |
| N borrowed from another circuit | RCD trips for no apparent reason | Each circuit has its own N from the same breaker |
Pass criteria for this lesson
- Run conduit on a practice board: vertical/horizontal routes, no more than 2 bends of 90° between two boxes, fixed every 0.5 m, wire pulls without jamming.
- Wire a one-switch circuit and a two-way two-switch circuit; all 4 switch combinations give the correct result on the meter before switching on.
- Measure to confirm that the switch breaks the line conductor (the lampholder is dead when switched off).
- Insulation resistance L–N, L–PE, N–PE ≥ 1 MΩ at 500V DC, recorded on the test sheet.
- Junction boxes have covers, 15 cm of spare wire, and joints made with push-in connectors or terminal blocks.
Frequently asked questions
Does wiring above a plasterboard ceiling need conduit?
It should. Wires above plasterboard ceilings are easily chewed by rats and pierced by the screws used to fix the frame. Use flexible or rigid conduit fixed to the frame or to the floor slab above, and never just lay the wires on top of the plasterboard.
Can switches be installed in a bathroom?
Under TCVN 7447-7-701 (IEC 60364-7-701) for bathrooms, switchgear is restricted according to the zones around the bath and shower. The common safe approach is to put the switch outside the bathroom door.
Do smart switches need a neutral wire?
Many types need an N conductor at the switch box to power their electronics. When running new conduit, it is a good idea to pull an N conductor down to the switch box in advance for future upgrades. Level 3 has a separate lesson on smart homes.
Why does an LED light still glow dimly or flicker when the switch is off?
Common causes: the switch is breaking the N conductor instead of the line, or the "switched line" wire runs a long way in parallel with another line conductor in the same conduit, creating a small capacitive current that is enough to make a low-power LED glow faintly. First recheck that the switch is in the line conductor; if it is and the light still glows, the lead electrician may suggest fitting an anti-glow capacitor or changing the type of lamp.
Further reading
A more detailed practical article: Installing two-way switches and earthed sockets.