An electrician's helper works from the lead electrician's pointing finger. The lead electrician works from the drawings. This is the first line between Level 1 and Level 2: you must be able to pick up the full drawing set for a house on your own and understand how many circuits it has, where each circuit runs, what cable size it uses, which circuit breaker protects it, and where the lights and sockets go and at what height. Misreading a single symbol can mean chasing the wrong wall from end to end, putting an induction hob socket on a run that only has 1.5 mm² cable, or missing a dedicated circuit for an air conditioner that nobody notices until the walls have been skimmed and painted.
By the end of this lesson, you will be able to:
- Recognise the types of drawings in a residential electrical drawing set and know which drawing answers which question.
- Read the title block, scale, legend and common device symbols based on IEC 60617.
- Read a wiring layout plan: number of conductors on a run, circuit codes and mounting heights.
- Read the single-line diagram of a distribution board: main breaker, RCD, final circuits, cable cross-sections and loads.
- Take off a preliminary bill of materials from the drawings and spot gaps or contradictions in the drawings that need to be queried.
What a house's electrical drawing set contains
A townhouse, villa or apartment with a full design will usually have an electrical section made up of the drawings below. Self-built family homes sometimes have only one layout plan and one board diagram, sometimes even hand-drawn; even so, the information you need to read is the same.
| Drawing | Answers the question | The lead electrician uses it to |
|---|---|---|
| Design notes and technical specification | Which standards apply, what type of materials, general installation methods | Know the quality requirements and material specifications |
| Lighting layout plan | Where the lights are, which switch controls which light | Mark out the positions of lights, switches and junction boxes |
| Socket-outlet and power equipment layout plan | Where the sockets, air conditioners, water heaters and hob are, and on which circuit | Mark out sockets and equipment supply points |
| Distribution board schematic (single-line diagram) | Which breakers the board has, what each final circuit feeds, what cable size it uses | Build the board, select and check the protective devices |
| Earthing and lightning protection diagram | Where the earth rods are and how the earthing conductor runs | Install the earthing system |
| Installation details | Heights, spacing, special mounting methods | Install to the correct dimensions |
| Bill of materials (quantity schedule) | How many metres of cable, how many devices | Order materials and check quantities |
Photo: Onafowokan Michael Olutusen / Wikimedia Commons, CC BY-SA 4.0
Read the title block, scale and legend first
Beginners tend to look straight at the drawing itself. An experienced lead electrician reads the title block first, because it tells you:
- Project name, work package and drawing number: so you are sure you are holding the right sheet for the floor you are working on.
- Revision and revision date: many problems on site come from a crew working from an old revision after the owner has moved the kitchen. Always ask, "Is this the latest revision?"
- Scale: a scale of 1:100 means 1 cm on paper equals 1 m on site; at 1:50, 1 cm equals 0.5 m. When measuring distances on a printout, remember that the print may have been reduced from the original sheet size; give priority to dimensions written as numbers.
- Designer and checker: the people to ask when the drawing is unclear.
After the title block comes the symbol legend. Each design office may draw symbols slightly differently. The legend on that particular drawing is the final authority, not your memory of the drawings from your last job.
Common symbols
Most electrical drawings in Vietnam use symbols based on IEC 60617 (the international standard for graphical symbols for electrical diagrams), plus a few symbols specific to each design office.
Symbols on cable runs
- Small diagonal ticks across the line: the number of ticks is the number of conductors in the run. Three ticks means three conductors (for example L, N, PE).
- Circuit code next to the run: for example "C3" or "L2" means the run belongs to circuit number 3 in the board. This code must match the board diagram.
- A note such as "CV 2×2.5 + E2.5 – PVC Ø20": CV cable, 2 cores of 2.5 mm² plus a 2.5 mm² earth conductor, drawn into PVC conduit with a 20 mm diameter.
- An arrow at the end of a run: the cable goes up to the floor above or down to the floor below.
Mounting heights
A floor plan is a view from above, so it cannot show heights. Heights are given by a note such as "h = 1.2 m" next to the symbol, or stated generally in the technical specification (for example "switches at 1.25 m, general sockets at 0.4 m above finished floor level"). Pay attention to the phrase finished floor level: when you are running conduit, the floor may still be bare structural concrete, without the 5–8 cm of screed and tiles that will go on top.
The single-line diagram of the distribution board
A single-line diagram draws each circuit as one single line, even though in reality the circuit has 2–3 conductors (or 4–5 conductors on a three-phase supply). This style lets you read the structure of the board quickly.
Read a single-line diagram in order from the supply down to the loads:
- Incoming supply: from the electricity meter, showing the cable type and cross-section (for example "CXV 2×10").
- Main switching device: the main circuit breaker (MCB or MCCB), showing the number of poles, rated current and breaking capacity (for example "MCB 2P 40A 6kA").
- Residual current protection: RCD/RCCB or RCBO, showing the rated residual operating current (30 mA) and type (AC, A).
- Final circuits: each circuit shows its breaker (for example "C16"), cable cross-section ("2.5 mm²"), load name ("Living room sockets") and sometimes the design load as well.
- N bar and PE bar: show how the neutral and earth conductors are connected.
Photo: Dmitry G / Wikimedia Commons, CC BY-SA 3.0
Warning: If the diagram shows the socket circuit or the bathroom circuit without passing through a 30 mA residual current device, do not simply build it as drawn. Go back to the designer; a 30 mA RCD on socket circuits and in damp areas is an additional protection requirement under TCVN 7447 (IEC 60364-4-41).
Cross-checking the layout plan against the board diagram
The most important drawing-reading skill for a lead electrician is cross-checking. Every circuit code on the layout plan must have a matching circuit in the board, and vice versa. How to do it:
- Draw up a table: column 1 is the circuit code from the board diagram, column 2 is the breaker and cable size, column 3 is the devices on the layout plan that belong to that circuit.
- Go through each layout plan and tick off every device as you assign it in the table.
- Check: are there any devices that do not belong to any circuit? Is there a circuit in the board with no devices? Is any circuit carrying too much load (for example one C16 circuit for the hob, washing machine and water heater together)?
- Check the large loads: air conditioners, water heaters, induction hobs and pumps must each have their own circuit sized to their power.
The next lesson teaches you how to calculate loads so you can check whether the figures in the diagram are reasonable.
From the drawings to a preliminary bill of materials
The lead electrician is often asked by the owner or the main contractor, "How much material do we need?" If the design includes a bill of materials, you check it; if not, you take it off the drawings yourself:
- Count the devices: number of lights, switches (sorted into one-way and two-way, and number of gangs), sockets, flush boxes and junction boxes.
- Measure the conduit runs: measure on the layout plan using the scale, and add the vertical drops down and up the walls (from the ceiling down to a switch is roughly the ceiling height minus the switch height).
- Calculate the cable length: conduit length multiplied by the number of conductors in the run, plus the tails left in boxes and in the board, plus a waste allowance of about 5–10%.
- Distribution board: list every device shown in the single-line diagram, and choose an enclosure with enough modules plus spare ways.
Photo: Onafowokan Michael Olutusen / Wikimedia Commons, CC BY-SA 4.0
When the drawings are incomplete or contradictory
Drawings are never perfect. Common situations and how to handle them:
- A device position clashes with a door, a column or a water pipe: take photos on site, mark it on the drawing, and ask the designer or the owner before moving it.
- A circuit code on the layout plan does not exist in the board: note it down and report it immediately; do not add a breaker on your own initiative.
- Cable size does not match the breaker (for example 1.5 mm² cable with a 25A breaker): report it to the designer; this is a safety defect.
- The owner wants changes: record the changes in writing (text message, signed note) and update them on the as-built drawings. Level 4 has a dedicated lesson on as-built documentation.
The rule: the lead electrician has the right to propose changes, but must never change a safety-related part of the design without confirmation.
Common mistakes
| Mistake | Consequence | How to avoid it |
|---|---|---|
| Using an old revision of the drawing | Chasing in the wrong place, rework | Check the revision number and date in the title block |
| Measuring distances on a reduced printout | Positions off by tens of centimetres | Use the dimensions written as numbers, or check the scale against a known dimension |
| Confusing heights above the structural floor with heights above the finished floor | Sockets too low or covered by tiles | Ask for the finished floor level and mark a datum line on the wall |
| Not cross-checking the layout plan against the board diagram | Missing circuits, loads grouped wrongly | Draw up a circuit–device table |
| Misreading a symbol | Installing the wrong type of device | Always read the legend of the drawing itself |
Pass criteria for this lesson
- Given a sample apartment drawing set, correctly read the title block, scale and revision within 5 minutes.
- Correctly name at least 15 symbols on the layout plan, checked against the legend, with no errors.
- Draw up a circuit–device table for the whole apartment and find the errors deliberately planted in the sample drawings (at least 3 out of 4).
- Produce a preliminary material take-off (number of devices, metres of conduit, metres of cable by cross-section) within 10% of the answer key.
- Explain every element of the single-line diagram: main breaker, RCD, each final circuit and the cable sizes.
Frequently asked questions
What if a family home has no electrical drawings?
The lead electrician should draw at least a layout plan and a distribution board diagram before starting work, and have the owner sign them off. A clear hand drawing is still far better than nothing, and it becomes the basis for quoting, handover inspection and future repairs.
Do I need to learn drawing software such as AutoCAD?
At Level 2, being able to read drawings is enough. At Level 4 (electrical design for townhouses), knowing how to use drawing software helps you produce more professional documentation. Many electricians use PDF files on their phones and zoom in to read the details on site.
Do the symbols on drawings follow Vietnamese standards?
There are Vietnamese standards for electrical diagram symbols, and most symbols in use today are compatible with IEC 60617. Even so, each design office may add its own symbols, so the legend on the drawing is always the deciding reference.
Further reading
Applying the board diagram to cable and breaker selection: Selecting cable sizes and circuit breakers.