An RCD that trips, a washing machine casing that gives a "tingle", an unusually high electricity bill, a damp wall with stains around a socket: all of these can be signs of earth leakage. A multimeter on its ohms range uses only a battery of a few volts and cannot detect insulation that has deteriorated; you need an insulation resistance tester (often called a megger or megohmmeter) that applies a DC voltage of 250–1000V. In Level 1 you learned what this instrument is. This lesson teaches you to test following the correct procedure from IEC 60364-6, to read and assess the results, and most importantly, to use the measurements to pinpoint exactly where the leakage is in a home.
By the end of this lesson, you will be able to:
- Choose the test voltage and minimum value according to the circuit voltage.
- Prepare the circuit safely before testing: isolate it, disconnect electronic equipment, and link L–N when needed.
- Measure L–PE, N–PE and L–N insulation for each circuit and record the results.
- Assess the results: good, doubtful or failed; and recognise the effect of humidity and temperature.
- Locate a leakage point using the section-splitting method and measure leakage current with a leakage clamp meter.
- Deal with the common causes of leakage in Vietnamese homes.
What insulation is and why it deteriorates
The PVC sheath of a cable, the plastic body of a socket and the insulation inside appliances all have a very high resistance, but not an infinite one. A new circuit has an insulation resistance of hundreds to thousands of megohms. Over time, insulation deteriorates because of:
- Moisture: water seeping into conduits, junction boxes, outdoor sockets and damp walls. This is the number one cause in the humid, muggy climate of the North and during the rainy season in the South.
- Heat: cables overloaded for long periods make the PVC brittle and cracked; cables run close to heat sources.
- Mechanical damage: cables pinched, nails driven close by, sharp conduit edges, rats chewing.
- Conductive dirt and dust in boards, in junction boxes in workshops, and in kitchens with a lot of grease.
- Ageing: cables over 20–25 years old, especially old rubber-insulated cables.
Test voltage and minimum values
| Nominal circuit voltage | DC test voltage | Minimum insulation resistance |
|---|---|---|
| SELV, PELV (extra-low voltage) | 250 V | ≥ 0.5 MΩ |
| Up to 500 V (including 230/400 V domestic) | 500 V | ≥ 1 MΩ |
| Above 500 V | 1000 V | ≥ 1 MΩ |
The values in the table come from IEC 60364-6 (TCVN 7447-6) and are the minimum acceptable levels. Practical experience: a newly installed circuit should read hundreds of MΩ; an old circuit below 2 MΩ needs monitoring and the cause needs to be found, even though it still "passes" by the standard. Some testers display ">999 MΩ" or "OL" when the insulation is very good.
Photo: Megger Ltd. / Wikimedia Commons, CC BY 3.0
Preparing before testing: safety for people and equipment
Warning: The tester applies 500V DC: enough to give a severe shock. Do not touch the test probes, and do not let anyone else touch equipment on the circuit being tested. After testing, the circuit may still hold a charge (especially long cables): let the tester discharge it automatically, or discharge it to earth before touching it. Never test a circuit that is still connected to the mains supply.
- Isolate, lock off, tag and prove dead following the Level 1 procedure.
- Disconnect sensitive equipment: unplug every appliance from the sockets; remove or disconnect LED drivers, dimmers, touch switches, smart switches, doorbells, surge protective devices (SPDs) and timers. A 500V DC test voltage can damage electronic components, and electronic components connected between L–N or L–PE will make the reading wrong.
- Switch the light switches on (after removing the lamps or drivers) so that the conductors beyond the switches are tested as well.
- Check the tester: the battery is good, shorting the two probes on the continuity range shows 0Ω, and leaving them open on the insulation range shows a very high value.
Procedure for testing one circuit
- At the board, switch off the circuit MCB. Disconnect the circuit's N conductor from the N bar (to separate it from the other circuits sharing the group's N bar).
- Test L–PE: one probe on the circuit phase conductor (MCB output), the other on the PE bar. Press test at 500V, wait for the value to stabilise (usually a few seconds; long cables take longer), and record it.
- Test N–PE: the same way, using the N conductor you just disconnected.
- Test L–N: between the circuit's phase and N conductors. If the value is low, check again that all appliances are unplugged and all lamps removed.
- Reconnect the N conductor to the same N bar it came from and tighten it to the correct torque.
- Fill in the test record: circuit name, test voltage, the three values, and the room temperature and humidity.
A shortcut permitted by IEC 60364-6: link L and N together and test against PE. If it passes, both L–PE and N–PE pass; only if it fails do you need to separate them and test individually to find out which conductor is faulty.
Photo: Liftarn / Wikimedia Commons, CC BY-SA 3.0
Reading and assessing the results
| Measured value (230 V circuit, 500 V test) | Assessment | Action |
|---|---|---|
| > 100 MΩ | Very good | Record it |
| 10 – 100 MΩ | Good | Record it, compare with the next test |
| 2 – 10 MΩ | Acceptable, needs monitoring (old circuit) | Check for damp spots, retest when dry |
| 1 – 2 MΩ | Borderline | Find the cause, plan the remedial work |
| < 1 MΩ | Fail | Do not energise the circuit; find the leakage immediately |
| ≈ 0 MΩ | Complete short or earth fault | Find the fault point (see the diagnosis lesson) |
Two important points when assessing results:
- Temperature and humidity: insulation resistance falls sharply when it is damp. For the same circuit, reading 3 MΩ on a muggy morning and 80 MΩ on a dry afternoon is perfectly normal. Record the test conditions; comparing the trend across tests taken under the same conditions is more valuable than a single reading.
- Long circuits and many circuits in parallel: the insulation resistance of many sections in parallel adds up to a lower value. Testing the whole house at once and getting 5 MΩ does not necessarily mean there is a fault, but testing each circuit separately will show clearly which one is poor.
Finding the leakage: the section-splitting method
Once you have identified the circuit with poor insulation, apply half-splitting as in the diagnosis lesson, but measure with the insulation tester instead of an ohmmeter:
- Test the whole circuit at the board: for example L–PE = 0.4 MΩ.
- Open a junction box or socket in the middle of the run and disconnect the conductors that continue onwards. Test again at the board: if the value rises to > 100 MΩ, the leakage is in the second half; if it is still low, it is in the first half.
- Keep splitting the faulty section until you are down to one section between two points, or to one specific accessory (socket, junction box).
- Visually inspect that point: water collected in a junction box, a damp socket, a crushed cable, a taped joint that has soaked up water.
Leakage current clamp meter
When the power cannot be switched off for long (a shop, a home with elderly or sick occupants), use a leakage current clamp meter (resolution 0.01–0.1 mA) to search while the circuit is live: clamp both the L and N conductors of a circuit together. Normally the reading is close to 0; if there is leakage, the leakage current is displayed. Clamp each circuit in turn, then each appliance (clamping the appliance supply cord) to narrow it down. Clamping the main PE conductor on its own also gives the total leakage current to earth for the whole house. This method is safer provided you follow the rules for working near live parts, but it cannot replace the insulation resistance test in a commissioning record.
Common causes of leakage in Vietnamese homes and how to fix them
| Location | Cause | Remedy |
|---|---|---|
| Sockets on balconies, in yards, at gates | Driving rain, no protective cover | Replace with IP44 or better sockets with covers, mounted higher, with the conduit entering from below so water does not run along it |
| Junction boxes in walls near toilets | Damp walls, water collecting in the box | Waterproof the wall, replace joints with sealed connectors, relocate the junction box |
| Water heater | Leaking heating element | Replace the element, check the magnesium anode regularly |
| Pumps, garden lights | Cable buried without protective conduit, joints buried directly | Use direct-burial cable, put joints in sealed IP67 boxes or use adhesive-lined heat-shrink sleeves |
| Cables over 20 years old | Aged PVC, brittle and cracked | Rewire run by run, starting with the circuit with the lowest reading |
| Bathroom ceiling lights | Steam condensing inside the lamp holder | Luminaires with an IP rating suitable for the bathroom zone (IEC 60364-7-701) |
Photo: "craignoble666" / Wikimedia Commons, CC BY-SA 4.0
Testing appliance insulation
For an appliance suspected of leaking (water heater, washing machine, pump), test at 500V DC between the L and N pins of the plug linked together and the metal casing or the PE pin of the appliance. Class I appliances (earthed appliances) are generally required to read ≥ 1 MΩ in periodic inspection under electrical equipment testing guidelines. Many appliances have electronic controllers, so you may use the 250V setting or measure the leakage current during operation as instructed by the manufacturer. The heating element of a water heater can be removed and tested on its own, between the terminal and the element sheath.
Common mistakes
| Mistake | Consequence | Correct practice |
|---|---|---|
| Testing with LED lamps, dimmers or SPDs still connected | Damaged equipment, falsely low results | Disconnect all electronic equipment |
| Not disconnecting N from the shared N bar | Other circuits are included in the measurement | Separate the N of the circuit under test |
| Reading the result the instant you press the button | Value not yet stable (cable capacitance still charging) | Wait for a stable value; wait longer on long cables |
| Touching the conductors straight after testing | Shock from the residual charge | Let the tester discharge it, or discharge through PE |
| Using a multimeter ohms range instead of an insulation tester | Poor insulation goes undetected | Use a 500 V DC test voltage |
| Drawing conclusions from a single test on a humid day | False alarms or missed faults | Record conditions, retest, compare trends |
Pass criteria for this lesson
- Prepare the circuit correctly with the 4 steps before testing, without damaging any electronic equipment on the practice board.
- Test L–PE, N–PE and L–N on 6 circuits and fill in the record correctly within 30 minutes.
- Correctly assess 6 given test results according to the table (good, monitor, fail).
- Find a simulated leakage on the practice board by section splitting with no more than 3 splits.
- Measure the leakage current of each circuit with a leakage clamp meter and identify the circuit with the highest leakage.
Frequently asked questions
Do newly installed circuits need an insulation test?
Yes, it is mandatory before energising for the first time. It is part of the initial verification under IEC 60364-6 and a required item in the commissioning record covered in the next lesson.
Which insulation tester should a domestic electrician buy?
A digital tester with 250/500/1000V ranges, a continuity function with a 200 mA test current, and automatic discharge after testing. If the budget allows, a multifunction installation tester that combines insulation, continuity, earth fault loop impedance and RCD trip time testing is the professional's choice.
The reading is low but the RCD does not trip. Is that a problem?
A 30 mA RCD only trips when the actual leakage current exceeds about 15–30 mA. An insulation resistance of 1 MΩ at 230V gives a leakage current of about 0.23 mA, not enough to trip it. But poor insulation is a sign of deterioration and will keep getting worse; dealing with it early is far cheaper than waiting until something catches fire.
Further reading
Review how to use test instruments in Using a multimeter for electricians and the causes of breakers and RCDs tripping in Diagnosing a breaker that keeps tripping.