At Level 1 you memorised the quick table "1.5 mm² for lighting, 2.5 mm² for sockets, 4 mm² for water heaters". That quick table is right for the common cases, but a lead electrician must know why it is right and when it is wrong: cable running in conduit buried in a wall together with many other circuits, a 40-metre run out to a storage shed, a rising main from the meter up to the fourth floor. This lesson teaches the three steps of cable selection: by current-carrying capacity, corrected for installation conditions, and then checked for voltage drop. Finally, it covers coordinating the cable with its protective circuit breaker.
By the end of this lesson, you will be able to:
- Read the current-carrying capacity table for PVC-insulated copper cable according to the installation method.
- Apply correction factors for ambient temperature and for grouping of several circuits together.
- Calculate the voltage drop of a single-phase circuit and compare it with the permitted limit.
- Coordinate correctly: design current ≤ breaker rated current ≤ cable current-carrying capacity.
- Choose the correct cross-section for the PE and neutral conductors.
The principle of coordinating cable and breaker
Everything in this lesson revolves around one simple inequality from TCVN 7447 (IEC 60364-4-43):
Ib ≤ In ≤ Iz
- Ib: the design current of the circuit (previous lesson).
- In: the rated current of the breaker protecting the circuit.
- Iz: the continuous current-carrying capacity of the cable, after correction for the installation conditions.
In other words: the breaker must be large enough not to trip under normal load, but smaller than what the cable can withstand, so that it trips before the cable overheats. If you fit a 32A breaker on 2.5 mm² cable because "the 20A breaker keeps tripping", you have broken this inequality, and the cable can burn without the breaker tripping.
Step 1. Current-carrying capacity by installation method
The same 2.5 mm² cable will dissipate heat better and carry more current when run exposed in free air than when drawn into conduit buried in a thermally insulated wall. That is why a current-carrying capacity table always comes with an installation method. The reference table below is for PVC-insulated copper cable, 2 loaded conductors (single phase), 30°C ambient temperature, following IEC 60364-5-52:
| Cross-section (mm²) | In conduit in a thermally insulated wall (A1) | In conduit on/in a masonry wall (B1) | Cable clipped direct to the wall (C) |
|---|---|---|---|
| 1.5 | 14.5 | 17.5 | 19.5 |
| 2.5 | 19.5 | 24 | 27 |
| 4 | 26 | 32 | 36 |
| 6 | 34 | 41 | 46 |
| 10 | 46 | 57 | 63 |
| 16 | 61 | 76 | 85 |
These are reference values for learning the way of thinking; for real design work, use the tables in the current standard and the cable manufacturer's catalogue (CADIVI, LS Vina, Tran Phu and others all publish current ratings by installation method). Most houses in Vietnam use conduit in masonry walls, which is close to column B1.
Photo: Cjp24 / Wikimedia Commons, CC BY-SA 4.0
Step 2. Correcting for temperature and grouping
The table above assumes 30°C and a single circuit on its own. When real conditions differ, multiply by correction factors:
Iz = Iz0 × k1 × k2
Temperature factor k1
Under a metal sheet roof, the roof space in a Vietnamese summer can exceed 40°C. For PVC insulation, the reference factors are: 35°C ≈ 0.94; 40°C ≈ 0.87; 45°C ≈ 0.79; 50°C ≈ 0.71. A cable running across a hot metal roof space can lose almost 30% of its current-carrying capacity.
Grouping factor k2
When several loaded circuits share one conduit or are bunched together, the reference factors are: 2 circuits ≈ 0.80; 3 circuits ≈ 0.70; 4 circuits ≈ 0.65; 6 circuits ≈ 0.57. This is why good electricians do not cram 4–5 circuits into one conduit, and why large-load circuits must have their own conduits.
Example: A socket circuit in 2.5 mm² cable in conduit in a masonry wall (Iz0 = 24A), sharing the conduit with 2 other circuits (k2 = 0.7), in a hot ceiling space at 40°C (k1 = 0.87). Iz = 24 × 0.87 × 0.7 ≈ 14.6A. A 20A breaker is now larger than Iz: you must drop to 16A, separate the conduits, or increase the cable to 4 mm².
Step 3. Checking the voltage drop
A long cable has resistance, and the current flowing through it loses part of the voltage. The appliance at the end of the line receives a lower voltage: lights are dim, motors struggle to start, and air conditioner compressors run hot. The approximate formula for a single-phase circuit (ignoring reactance for small cables):
ΔU = 2 × L × I × ρ / S
- L: one-way length of the circuit (m), multiplied by 2 because the current goes out on the phase conductor and returns on the neutral.
- I: design current (A).
- ρ: resistivity of copper at operating temperature, about 0.0225 Ω·mm²/m.
- S: cross-section (mm²).
Commonly used limits for low-voltage installations in buildings: the voltage drop from the point of supply to the appliance should not exceed about 3% for lighting and 5% for other loads (following IEC 60364-5-52 Annex G; see the applicable design standard for the exact requirement). At 220V, 3% ≈ 6.6V and 5% ≈ 11V.
Example: a pump in a storage shed 40 m from the board
A 1.1 kW pump, cos φ 0.8, current ≈ 6.3A. Try 1.5 mm² cable: ΔU = 2 × 40 × 6.3 × 0.0225 / 1.5 ≈ 7.6V (3.4%). A motor load draws 5–7 times its running current when starting, so the momentary voltage drop rises to more than 20%: the pump will struggle to start. Choose 2.5 mm²: ΔU ≈ 4.5V (2%). Conclusion: 2.5 mm², even though the current is only 6.3A, because the line is long and the load is a motor.
PE and neutral conductors
- The neutral conductor in a single-phase circuit carries the same current as the phase conductor, so it always has the same cross-section as the phase conductor.
- The PE (protective earth) conductor: for phase conductors up to 16 mm², the PE conductor has the same cross-section as the phase (TCVN 7447-5-54, IEC 60364-5-54, Table 54.2). For phase conductors from 16 to 35 mm², the PE must be at least 16 mm². Above 35 mm², the PE must be at least half the phase conductor size.
- The PE conductor is always green-and-yellow and is never used for any other purpose.
Photo: Dmitry G / Wikimedia Commons, CC BY-SA 3.0
Aluminium cable and supply mains
The line from the grid to the meter, and sometimes from the meter into the house, may be aluminium cable (aerial bundled cable, ABC). Aluminium conducts about 1.6 times worse than copper, so it needs a larger cross-section for the same current. More importantly, the aluminium–copper joint must use bimetallic lugs or purpose-made connectors, as you learned at Level 1. Inside the house, the cable after the meter should be copper.
Photo: Xofc / Wikimedia Commons, CC BY-SA 4.0
The 6-step cable selection procedure
- Determine the Ib of the circuit (load calculation lesson).
- Select a breaker with In ≥ Ib from the standard range: 6, 10, 16, 20, 25, 32, 40, 50, 63A.
- Determine the installation method, ambient temperature and number of circuits grouped together → calculate k1 and k2.
- Select the cross-section for which Iz0 × k1 × k2 ≥ In.
- Calculate the voltage drop; if it exceeds the limit, increase the cross-section.
- Select the matching N and PE conductors; record everything in the circuit schedule on the drawing.
Note: there is one more condition. The cable must withstand the short-circuit current for the time it takes the breaker to trip, and the earth fault loop impedance must be low enough for the breaker to trip quickly. For ordinary residential circuits protected by MCBs, this condition is usually met; the MCB lesson and the inspection and testing lesson will come back to measuring earth fault loop impedance.
Results table for the townhouse from the previous lesson
| Circuit | Ib (A) | In (A) | Conditions | Cable selected |
|---|---|---|---|---|
| Ground floor lighting | 2 | 10 | Own conduit, B1 | 1.5 mm² |
| Living room sockets | 12 | 20 | Own conduit, B1 | 2.5 mm² |
| Kitchen sockets | 14 | 20 | Own conduit, B1 | 2.5 mm² (or 4 mm² if sharing a conduit) |
| First floor water heater | 11.4 | 16–20 | Own conduit | 2.5–4 mm² |
| Induction hob | 16 | 25–32 | Own conduit | 4–6 mm² as per the manufacturer's instructions |
| Bedroom air conditioner | 5 | 16 | Hot ceiling space, 40°C | 2.5 mm² |
| Incoming supply | 55 | 63 | Own conduit, 15 m long | 16 mm² copper |
Voltage drop check on the incoming supply: ΔU = 2 × 15 × 55 × 0.0225 / 16 ≈ 2.3V (1%). Pass. Adding the voltage drop of the final circuits, the total is still below the limit.
Checking the real cable on site
A correct design with the wrong materials still fails. The lead electrician should check the cable drums or coils on delivery:
- Read the marking printed on the sheath: manufacturer, cross-section, insulation type, rated voltage (for example 450/750V) and manufacturing standard. Reject cable with no printing or faint, illegible printing.
- Count the strands and measure the conductor diameter: a 2.5 mm² solid conductor has a diameter of about 1.78 mm; measure it with a vernier caliper. For flexible multi-strand cable, count the strands and compare with the catalogue.
- Weigh it: 100 m of 2.5 mm² copper cable contains about 2.2 kg of copper (copper density 8.9 g/cm³). An unusually light coil is a sign of an undersized or adulterated conductor.
- Measure the resistance of a coil: the standard maximum DC resistance of a 2.5 mm² conductor is about 7.41 Ω/km at 20°C. A 100 m coil measuring about 0.74 Ω is acceptable; a clearly higher value means the conductor is undersized.
A coil of counterfeit, undersized cable can "pass" every visual check, but your Iz table assumes genuine 2.5 mm² cable, while what is actually inside the wall is equivalent to only 2 mm². That is why the inspection records at the end of Level 2 require the cable brand and batch to be written down clearly.
Self-study exercises
- An 18000 BTU air conditioner circuit with a rated current of 8A runs through a metal roof space at 45°C, sharing a conduit with 1 lighting circuit. Select the breaker and the cable.
- A garden socket circuit is 35 m long, and the largest load is a 1.8 kW pressure washer (cos φ 0.85). Check the voltage drop with 2.5 mm² and with 4 mm² cable.
- A rising main from the main board on the ground floor up to the board on the fourth floor is 18 m long, Ib = 32A. Select the breaker and the phase, N and PE conductors.
Hint for question 1: Ib = 8A, choose In = 16A; 2.5 mm² cable, B1 Iz0 = 24A × k1 (0.79) × k2 (0.8) ≈ 15.2A, which is less than 16A: fail. You must increase to 4 mm² (32 × 0.79 × 0.8 ≈ 20.2A) or run it in its own conduit (24 × 0.79 ≈ 19A).
Common mistakes
| Mistake | Consequence | The right way |
|---|---|---|
| Fitting a bigger breaker when it keeps tripping | Cable overheats and burns | Keep In ≤ Iz and find the cause |
| Cramming many circuits into one conduit | Iz drops by 30–40% | Calculate k2 or separate the conduits |
| Ignoring voltage drop on long runs | Motors struggle to start, lights are dim | Calculate ΔU and increase the cross-section |
| PE conductor smaller than the phase conductor | Cannot carry the fault current adequately | PE = phase conductor size up to 16 mm² |
| Using cable of unknown origin with undersized cores | Real cross-section smaller than marked | Use branded cable, weigh it and count the strands |
Pass criteria for this lesson
- Explain Ib ≤ In ≤ Iz using a real-life example.
- Correctly look up Iz0 for 3 installation methods and apply k1 and k2 to 3 given scenarios.
- Calculate the voltage drop for 2 long circuits, with an error ≤ 5%, and conclude pass/fail.
- Draw up a circuit schedule for a sample house with at least 8 circuits: Ib, In, installation conditions, phase/N/PE cross-sections.
- Find the coordination errors in 3 sample distribution boards provided.
Frequently asked questions
Why does the cable manufacturer's table differ from the table in this lesson?
Each table is based on different assumptions: ambient temperature, insulation type (PVC 70°C or XLPE 90°C), number of loaded conductors and installation method. Read the notes under the table carefully. XLPE-insulated cable withstands higher temperatures, so its current rating is higher than PVC cable of the same cross-section.
Is cable that is bigger than necessary harmful?
Not electrically; it just costs more and is hard to connect to devices with small terminals (sockets and switches typically only accept up to 2.5 or 4 mm²). Do not upsize the cable and forget to check the terminals.
Do I need to calculate voltage drop for circuits inside an apartment?
Apartments usually have short circuits under 20 m, so the voltage drop is small. But multi-storey townhouses, garden houses and small workshops must be calculated, especially circuits with motors.
Further reading
Review the quick selection table in the lesson Selecting cable sizes and circuit breakers and how to deal with a tripping breaker in Diagnosing a breaker that keeps tripping.